General Industry (29 CFR 1910)

Electric Power Generation, Transmission, and Distribution

Verified vs OSHA sources · 2026-10-19

29 CFR 1910.269

29 CFR 1910.269 covers the operation and maintenance of electric power generation, control, transformation, transmission, and distribution lines and equipment, including equivalent installations of industrial establishments ((a)(1)(i)(A)). It sets the rules for deenergizing and grounding, minimum approach distances to energized parts, protection from electric arcs, work on or near energized parts, job briefings, and the training of every employee whose work it covers.

29 CFR 1910.269 at a glance

What it covers
Operation and maintenance of electric power generation, transmission, and distribution
De-energize/ground
Deenergizing procedures of (m) for lines and equipment worked as deenergized; grounding methods of (n) where grounding protects employees
Approach distances
Minimum approach distances set under (l)(3) by voltage, exposure and altitude
Arc-flash
A reasonable incident-energy estimate for each employee exposed to arcs; arc-rated clothing and equipment when the estimate exceeds 2.0 cal/cm2 (1910.269(l)(8))
Who
Qualified employees for work on or near energized parts; training for every employee whose work the section covers ((a)(2))
Max penalty (2026)
$16,550 per serious violation; $165,514 per willful

What 29 CFR 1910.269 requires (plain English)

29 CFR 1910.269 covers the operation and maintenance of electric power generation, control, transformation, transmission, and distribution lines and equipment: the work of electric utilities, and equivalent installations of industrial establishments ((a)(1)(i)(A)); the voltage alone does not decide the scope.

Its core protections include: de-energizing and grounding lines and equipment before work (and the conditions for energized work); minimum approach distances that workers and their conductive objects must keep from energized parts, scaled to the voltage; protection from electric arcs, which requires the employer to assess the incident heat energy of potential arcs and provide arc-rated protective clothing and equipment; rules for specific tasks (grounding, live-line tools, aerial devices, enclosed spaces, and more); and requirements for host and contract employers to share information and coordinate. Only qualified employees, trained and demonstrating the required skills, perform work on or near energized parts.

1910.269 (with its construction counterpart in 1926 Subpart V) is the specialized rule for utility electrical work, distinct from the general electrical standards (1910.331–.335) that cover most other workplaces. 1910.269(a)(1) also reaches fuel and ash handling, water and steam installations and chlorine and hydrogen systems at a generating station, test sites for temporary electrical testing, work directly associated with covered installations, and line-clearance tree trimming for utilities; it does not apply to construction work (except line-clearance tree trimming and the generation-installation work named in 1926.950(a)(3)) or to installations and work practices covered by Subpart S; and it applies in addition to the other Part 1910 standards ((a)(1)(ii)-(iii)).

What the source requires, in summary

This section covers the operation and maintenance of electric power generation, control, transformation, transmission, and distribution lines and equipment.
29 CFR 1910.269(a)(1)(i)Summarized, not quoted.

Key facts about 29 CFR 1910.269

  • 1910.269 covers operation and maintenance of electric power generation, transmission, and distribution (1910.269(a)(1)(i)).
  • Lines and equipment worked as deenergized follow the deenergizing procedures of (m); where grounding is used to protect employees, the methods of (n) apply.
  • Workers keep the minimum approach distances that the employer sets under (l)(3), which depend on voltage, exposure and altitude.
  • Employers must make a reasonable estimate of the incident heat energy for each employee exposed to electric arcs (broad estimates covering several system areas are allowed if they represent the maximum exposure); clothing that could melt onto the skin or ignite and keep burning is prohibited; the outer layer must be flame resistant under four listed conditions; and employees wear protective clothing and equipment with an arc rating at least equal to the estimate whenever it exceeds 2.0 cal/cm2, covering the entire body except for the hand, foot, head and face exceptions of (l)(8)(v) (1910.269(l)(8)).
  • Only qualified employees work on or near energized parts, but training covers all employees whose work falls under the section, with extra skills for qualified employees and for line-clearance tree trimmers who are not qualified (1910.269(a)(2)).
  • Host and contract employers must share information and coordinate.
  • Its construction counterpart is 1926 Subpart V; line-clearance tree trimming and the generation-installation work named in 1926.950(a)(3) stay under 1910.269 (1910.269(a)(1)(ii)(A)).

Scope: who 29 CFR 1910.269 applies to

Regulatory framework
General Industry (29 CFR 1910)
Citation reference
29 CFR 1910.269
Enforcement status
In force and enforced
Jurisdiction
Federal OSHA (29 State-Plan jurisdictions may be stricter)

State-Plan states (e.g. California, Washington, Michigan) operate OSHA-approved programs that must be at least as effective as federal OSHA and frequently impose higher penalties or additional requirements.

Key requirements of 29 CFR 1910.269

#What the section requires or covers
1Establish minimum approach distances
2Use proper de-energizing and grounding procedures
3Provide arc-flash rated PPE
4Train qualified electrical workers
5Implement switching and tagging procedures
6Conduct job briefings before each job

Summarized from the text of 29 CFR 1910.269.

Common Electric Power Operations violations

Deficiencies OSHA cites under 29 CFR 1910.269 include the ones below, in no particular order. Each serious item carries up to $16,550 (2026).

  • Lines or equipment worked as deenergized without the deenergizing procedures of 1910.269(m), or grounding used to protect employees without the methods of (n).
  • Workers within the minimum approach distance of energized parts set under 1910.269(l)(3).
  • No reasonable estimate of incident heat energy for an employee exposed to arcs ((l)(8)(ii)); melting or ignitable clothing worn ((l)(8)(iii)); no flame-resistant outer layer where one of the four conditions applies ((l)(8)(iv)); arc rating below the estimate when it exceeds 2.0 cal/cm2 ((l)(8)(v)) (1910.269(l)(8)).
  • Unqualified employees performing energized or high-voltage work, or employees whose work falls under the section left out of the training (1910.269(a)(2)(i)-(iii)).
  • Host and contract employers not sharing information or coordinating (1910.269(a)(3)).

1910.269 is utility work: it is not the same as the general electrical rules (1910.331–.335)

The general electrical safe-work-practice rules (1910.331 through 1910.335) cover electrical work in most general-industry workplaces. 1910.269 is different: it applies specifically to the operation and maintenance of electric power generation, transmission, and distribution systems, utility line work and power plants (including equivalent installations in industrial establishments that only qualified employees access, 1910.269(a)(1)(i)(A)). 1910.269 has its own minimum approach distances, arc-flash (incident-energy) requirements, grounding rules, and qualified-worker provisions. Which one applies depends on the installation, the activity and the worker's qualification, so decide it task by task, not by the words 'utility' or 'power plant' (1910.269(a)(1)). Work practices conforming to 1910.332 through 1910.335 are treated as complying with the electrical safety-related work-practice requirements of 1910.269 listed in Table 1 of appendix A-2 when the work is done on an installation meeting 1910.303 through 1910.308 (Note 1 to paragraph (a)(1)(ii)(B)). (Construction of these systems is covered by the parallel 1926 Subpart V, except that 1910.269 still applies to line-clearance tree trimming and to the generation-installation work that 1926.950(a)(3) sends back to it: 1910.269(a)(1)(ii)(A).)

What OSHA inspectors look for

A compliance officer checks that lines and equipment are de-energized and grounded where required, that workers maintain minimum approach distances from energized parts, that arc-flash protection (rated clothing) is provided based on an incident-energy assessment, and that host/contractor duties and qualified-worker training are met.

Example: how a violation is cited

Hypothetical case: a line crew works on a distribution line treated as deenergized without the deenergizing procedures of 1910.269(m), and a conductor is still energized. 1910.269(m) sets the procedures for deenergizing transmission and distribution lines and equipment before employees work on them as deenergized. A serious violation carries a penalty of up to $16,550.

Illustrative example, not a specific OSHA case.

Electric Power Operations compliance checklist

Each item is a requirement of 29 CFR 1910.269 that OSHA may verify during an inspection.

  • Where lines and equipment are worked as deenergized, follow the procedures of (m), and where grounding protects employees, the methods of (n).
  • Set and maintain the minimum approach distances of (l)(3) from energized parts, by voltage, exposure and altitude.
  • Identify employees exposed to arcs and estimate the incident heat energy for each (broad estimates are allowed where they represent the maximum exposure); keep melting and ignitable fabrics out; require a flame-resistant outer layer under the four (l)(8)(iv) conditions; provide arc-rated clothing and equipment rated at or above the estimate whenever it exceeds 2.0 cal/cm2, covering the entire body except for the gloves, shoes, head and face exceptions of (l)(8)(v).
  • Train every employee whose work is covered by 1910.269 in the safety-related work practices that pertain to the job and in the other safety practices and emergency procedures (such as pole-top and manhole rescue), to a degree set by the risk ((a)(2)(i)); train qualified employees also in the skills of (a)(2)(ii) (distinguishing exposed live parts, nominal voltage, minimum approach distances, precautionary techniques and PPE); train line-clearance tree trimmers who are not qualified in the skills of (a)(2)(iii); and supervise and inspect compliance at least annually ((a)(2)(iv)).
  • Coordinate information and duties between host and contract employers.
  • Follow the task-specific rules (grounding, live-line tools, aerial devices, enclosed spaces).
  • Hold a job briefing before the work covering the hazards associated with the job, the work procedures involved, the special precautions, the energy source controls and the personal protective equipment requirements ((c)).

2026 penalties for 29 CFR 1910.269

Maximums set by 29 CFR 1903.15(d). 2026 maximums unchanged from 2025 (no CPI adjustment; OMB M-26-11), so not an increase; the serious and repeat policy minimums were revised with FOM chapter 6 (OSHA memo of May 21, 2026). The 2025 OSHA penalty levels remain in effect for 2026; OSHA made no inflation adjustment for 2026. 29 CFR 1903.15 identifies January 15, 2025 as the effective reference for these amounts, while OSHA's public penalties page currently references penalties assessed after Jan. 15, 2026.

Violation typeMinimumMaximumWhen it applies
Serious$1,085$16,550Death or serious physical harm could result, and the employer knew or could have known (29 U.S.C. 666(k)).
Other-Than-Serious$0$16,550Relates to safety/health but unlikely to cause death or serious harm.
Willful$11,823$165,514Intentional, knowing, or voluntary disregard of the requirement.
Repeated$4,256$165,514A substantially similar violation cited within the last 5 years.
Failure to AbateNone$16,550/dayup to $16,550 per day; the total is normally capped at 30 times the daily amount (FOM Ch.6)

Serious violations reach $16,550 and willful or repeat violations $165,514.

Maximums and the willful minimum are set by 29 CFR 1903.15(d); the serious and repeated minimums are OSHA policy floors from its annual penalty adjustment memo. OSHA applies gravity-based and size, good-faith and history reductions (FOM CPL 02-00-164 Ch.6). Estimates only, not legal advice.

The business case for Electric Power Operations compliance

1910.269(l)(8) has the employer make a reasonable estimate of the incident heat energy of any electric arc to which an employee would be exposed and provide protective clothing and equipment with an arc rating at least equal to the estimate whenever it exceeds 2.0 cal/cm2; 1910.269(a)(2) has the training of employees whose work is covered by the section.

State plans and their penalty rules

States listed by the volume of their federal construction citations, not by this standard. Penalties and enforcement vary by state. State-Plan states may impose higher penalties and additional requirements beyond federal 29 CFR 1910.269.

Frequently asked questions about 29 CFR 1910.269

What does OSHA 1910.269 cover?

1910.269 covers the operation and maintenance of electric power generation, control, transformation, transmission, and distribution lines and equipment: utility electrical work. It sets rules for de-energizing and grounding, minimum approach distances to energized parts, arc-flash protection based on an incident-energy assessment, and qualified-worker training for high-voltage work.

What is the difference between 1910.269 and 1910.331–.335?

1910.331 through 1910.335 are the general electrical safe-work-practice rules for most workplaces. 1910.269 is the specialized standard for the operation and maintenance of electric power generation, transmission, and distribution, utility line work and power plants, with its own minimum approach distances, arc-flash requirements, and grounding rules for much higher voltages. Construction of those systems is covered by 1926 Subpart V, except for line-clearance tree trimming and the generation-installation work named in 1926.950(a)(3), which stay under 1910.269. Overlaps are handled by the scope notes: 1910.269 does not apply to installations and work practices covered by Subpart S, work practices conforming to 1910.332 through 1910.335 are treated as complying with the Table 1 requirements of appendix A-2 on an installation meeting 1910.303 through 1910.308, and 1910.269 applies in addition to the other Part 1910 standards (1910.269(a)(1)(ii)-(iii)).

Does 1910.269 require arc-flash protection?

Yes. Under 1910.269(l)(8), the employer assesses the workplace to identify employees exposed to hazards from flames or from electric arcs, makes a reasonable estimate of the incident heat energy for each of them, keeps clothing that could melt or ignite and keep burning out, requires a flame-resistant outer layer under the four listed conditions, and provides arc-rated protection at least equal to the estimate whenever it exceeds 2.0 cal/cm2, with the exceptions for the hands, feet, head and face of (l)(8)(v).

Who can work on energized power lines?

Work on or near energized parts is performed by qualified employees: those trained and capable of working safely on energized circuits, familiar with the proper procedures, minimum approach distances, and protective equipment, and who have demonstrated the required skills. The employer chooses by task between work on de-energized lines and equipment and work on or near energized parts, each with its own conditions, and opening a switch alone is not enough: the applicable requirements for the control of hazardous energy must be met. Training is not limited to qualified employees: under (a)(2)(i) every employee performing work covered by the section is trained in the practices and emergency procedures that pertain to the job, and line-clearance tree trimmers who are not qualified have their own required skills ((a)(2)(iii)).

Regulatory history of 29 CFR 1910.269

1910.269 was published at 59 FR 4320 (January 31, 1994) and revised at 79 FR 20316 (April 11, 2014), which added the estimate of incident heat energy and the arc-rated protection of (l)(8) and aligned the section with 1926 Subpart V.

Related glossary terms

Key terms that appear in 29 CFR 1910.269, each with a full plain-English explainer.

Get the Binder in Order Before the Inspector Arrives. Are You Ready?

OSHA inspections come unannounced, apart from the few exceptions listed in 29 CFR 1903.6. Get the binder in order before the opening conference, not during it.

Serious Violation

$16,550

per violation (max)