Skip to content

Approaching: Feb 1, 2027 — 300A Posting Begins. Get ready →

General Industry (29 CFR 1910)

Wiring Design and Protection

Verified vs OSHA sources · 2026-10-19

29 CFR 1910.304

29 CFR 1910.304 sets the wiring design and protection requirements for general industry: the path to ground from circuits, equipment, and enclosures must be permanent, continuous, and effective, 125-volt, single-phase, 15- and 20-ampere receptacles in bathrooms and on rooftops must have ground-fault circuit interrupter (GFCI) protection, temporary wiring on construction-like activities has its own GFCI and assured-grounding rules, and circuits must have proper overcurrent protection.

29 CFR 1910.304 at a glance

What it requires
A permanent, continuous, effective ground path; GFCI protection for the receptacles the standard names; overcurrent protection
Who it covers
General-industry employers
Ground rule
The path to ground must be permanent, continuous, and effective (1910.304(g)(5))
GFCI rule
Required on 125-V, single-phase, 15/20-A receptacles in bathrooms and on rooftops (1910.304(b)(3)(i)); temporary wiring on construction-like work: 125-V, single-phase, 15/20/30-A non-permanent receptacles in use need GFCIs, others GFCIs or an assured grounding program ((b)(3)(ii))
Max penalty (2026)
$16,550 per serious violation; $165,514 per willful
Common confusion
The path to ground (g)(5) and GFCI protection (b)(3) are separate requirements, and a GFCI watches for an imbalance, not for every contact

What 29 CFR 1910.304 requires (plain English)

29 CFR 1910.304 governs the design and protection of electrical wiring in general industry: how circuits are grounded, protected against overcurrent, and safeguarded in areas where shock risk is high.

The path to ground from circuits, equipment, and enclosures must be permanent, continuous, and effective ((g)(5)). Ground-fault circuit interrupters are required on all 125-volt, single-phase, 15- and 20-ampere receptacles installed in bathrooms or on rooftops, a rule that applies to installations made after August 13, 2007 ((b)(3)(i); 1910.302(b)(4)), and temporary wiring installations used during construction-like activities, including certain maintenance, remodeling or repair activities involving buildings, structures or equipment, also need ground-fault protection: all 125-volt, single-phase, 15-, 20- and 30-ampere receptacle outlets that are not part of the permanent wiring and are in use by personnel need GFCI protection (a GFCI cord set at the receptacle closest to the source is acceptable); other receptacles not part of the permanent wiring need GFCI protection too, and where it is not available for them the employer must establish and implement an assured equipment grounding conductor program (written description at the jobsite, designated competent persons, visual inspection before each day's use, continuity and terminal tests before first use, after repair, after suspected damage and at least every 3 months, or 6 months for fixed items not exposed to damage, and a recorded test log) (1910.304(b)(3)(ii)). When a receptacle is replaced where no grounding means exists in the enclosure, 1910.304(b)(2)(iv)(C) allows a nongrounding-type replacement, a GFCI receptacle marked "No Equipment Ground" (with no equipment grounding conductor connected from it), or a grounding-type receptacle supplied through a GFCI and marked "GFCI Protected" and "No Equipment Ground". Circuits must also carry overcurrent protection sized to the conductors.

1910.304 works with the general electrical requirements (1910.303), wiring methods (1910.305), and safe work practices (1910.333), and it parallels the construction wiring-design standard (1926.404), which sets the GFCI-or-assured-grounding rule for construction temporary power; 1910.304(b)(3)(ii) applies a similar rule to temporary wiring on construction-like activities within general industry.

The regulatory text

“The path to ground from circuits, equipment, and enclosures shall be permanent, continuous, and effective.”
29 CFR 1910.304(g)(5)

Key facts about 29 CFR 1910.304

  • The path to ground from circuits, equipment, and enclosures must be permanent, continuous, and effective (1910.304(g)(5)).
  • GFCI protection is required on 125-V, single-phase, 15- and 20-ampere receptacles installed in bathrooms or on rooftops (1910.304(b)(3)(i)). Temporary wiring on construction-like activities (including certain maintenance, remodeling or repair) needs GFCI protection on non-permanent 125-V, single-phase, 15/20/30-ampere receptacles in use, and GFCIs or an assured equipment grounding conductor program for other receptacles ((b)(3)(ii)).
  • Conductors and equipment must be protected from overcurrent in accordance with their ability to safely conduct current (1910.304(f)(1)(i)).
  • It works with 1910.303 (general), 1910.305 (wiring methods), and 1910.333 (work practices).
  • Construction's parallel is 1926.404; 1910.304(b)(3)(ii) also carries the assured grounding program for temporary wiring on construction-like work in general industry (written program, competent persons, daily inspection, tests every 3 months or 6 for fixed items, records).
  • Replacing a receptacle where no grounding means exists: nongrounding replacement, GFCI receptacle marked "No Equipment Ground", or grounding-type receptacle on a GFCI marked "GFCI Protected" and "No Equipment Ground" are all allowed (1910.304(b)(2)(iv)(C)).

Scope: who 29 CFR 1910.304 applies to

Regulatory framework
General Industry (29 CFR 1910)
Citation reference
29 CFR 1910.304
Enforcement status
In force and enforced
Jurisdiction
Federal OSHA (29 State-Plan jurisdictions may be stricter)

State-Plan states (e.g. California, Washington, Michigan) operate OSHA-approved programs that must be at least as effective as federal OSHA and frequently impose higher penalties or additional requirements.

Key requirements of 29 CFR 1910.304

#What the section requires or covers
1Use GFCI protection for wet/damp locations
2Properly ground all electrical circuits
3Provide overcurrent protection
4Install wiring per NEC standards
5Protect flexible cords from damage

Summarized from the text of 29 CFR 1910.304.

Common Wiring Design violations

Deficiencies OSHA cites under 29 CFR 1910.304 include the ones below, in no particular order. Each serious item carries up to $16,550 (2026).

  • Equipment ground path broken, bypassed, or not continuous (1910.304(g)(5)).
  • Missing GFCI protection on required 125-V, single-phase, 15/20-A receptacles in bathrooms or on rooftops (1910.304(b)(3)(i)); on construction-like temporary wiring, non-permanent receptacles in use without GFCI protection or, for those not covered by GFCIs, no assured equipment grounding conductor program (1910.304(b)(3)(ii)).
  • Conductors and equipment not protected from overcurrent in line with their ability to carry current safely, for example an oversized or defeated breaker or fuse (1910.304(f)(1)(i)).
  • Metal enclosures and equipment not grounded where 1910.304(g) requires it, outside its exceptions (1910.304(g)).
  • Reversed polarity or improper circuit identification (1910.304(a)).

The path to ground and GFCI protection are separate requirements

1910.304(g)(5) has the path to ground from circuits, equipment, and enclosures permanent, continuous, and effective, and (b)(3) has GFCI protection for the receptacles it lists. A GFCI monitors an imbalance between outgoing and returning current; it does not protect against every contact between conductors. A receptacle without a ground can be a permitted replacement under (b)(2)(iv)(C), which does not create an equipment grounding conductor.

What OSHA inspectors look for

A compliance officer checks that equipment grounding is continuous and effective (not relying on a broken or bypassed ground), that GFCI protection is present on required receptacles (125-volt, single-phase, 15/20-ampere in bathrooms and on rooftops, and non-permanent receptacles in use on construction-like temporary wiring), that overcurrent devices are sized and not defeated, and that circuit identification is correct.

Example: how a violation is cited

Hypothetical case: a worker uses a grounded tool through an adapter with the ground pin broken off. 1910.304(g)(5) has the path to ground from circuits, equipment, and enclosures permanent, continuous, and effective. A serious violation carries a penalty of up to $16,550.

Illustrative example, not a specific OSHA case.

Wiring Design compliance checklist

Each item is a requirement of 29 CFR 1910.304 that OSHA may verify during an inspection.

  • Verify the equipment grounding path is permanent, continuous, and effective throughout circuits and enclosures.
  • Provide GFCI protection on 125-V, single-phase, 15/20-A receptacles in bathrooms and on rooftops, and on non-permanent receptacles in use on construction-like temporary wiring (125-V, single-phase, 15/20/30-A; others by GFCI or an assured equipment grounding conductor program) (1910.304(b)(3)).
  • Size overcurrent protection to the conductors and equipment and never defeat or oversize breakers or fuses (1910.304(f)).
  • Test receptacles for correct grounding and polarity, and repair broken grounds; a receptacle without a ground may be a permitted replacement under (b)(2)(iv)(C) (nongrounding type, GFCI marked "No Equipment Ground", or grounding type on a GFCI marked "GFCI Protected" and "No Equipment Ground").
  • Bond and ground metal enclosures and equipment as required.
  • Apply 1910.305 to wiring methods and flexible cords, and 1910.333 to work practices; check 1910.302 for the date from which a requirement applies to the installation.

2026 penalties for 29 CFR 1910.304

Maximums set by 29 CFR 1903.15(d). 2026 maximums unchanged from 2025 (no CPI adjustment; OMB M-26-11), so not an increase; the serious and repeat policy minimums were revised with FOM chapter 6 (OSHA memo of May 21, 2026). The 2025 OSHA penalty levels remain in effect for 2026; OSHA made no inflation adjustment for 2026. 29 CFR 1903.15 identifies January 15, 2025 as the effective reference for these amounts, while OSHA's public penalties page currently references penalties assessed after Jan. 15, 2026.

Violation typeMinimumMaximumWhen it applies
Serious$1,085$16,550Death or serious physical harm could result, and the employer knew or could have known (29 U.S.C. 666(k)).
Other-Than-Serious$0$16,550Relates to safety/health but unlikely to cause death or serious harm.
Willful$11,823$165,514Intentional, knowing, or voluntary disregard of the requirement.
Repeated$4,256$165,514A substantially similar violation cited within the last 5 years.
Failure to AbateNone$16,550/dayup to $16,550 per day; the total is normally capped at 30 times the daily amount (FOM Ch.6)

Serious violations reach $16,550 and willful or repeat violations $165,514.

Maximums and the willful minimum are set by 29 CFR 1903.15(d); the serious and repeated minimums are OSHA policy floors from its annual penalty adjustment memo. OSHA applies gravity-based and size, good-faith and history reductions (FOM CPL 02-00-164 Ch.6). Estimates only, not legal advice.

The business case for Wiring Design compliance

1910.304(g)(5) has the path to ground from circuits, equipment, and enclosures permanent, continuous, and effective, and (b)(3)(i) has ground-fault circuit interrupter protection on 125-volt, single-phase, 15- and 20-ampere receptacles installed in bathrooms and on rooftops.

State plans and their penalty rules

States listed by the volume of their federal construction citations, not by this standard. Penalties and enforcement vary by state. State-Plan states may impose higher penalties and additional requirements beyond federal 29 CFR 1910.304.

State pages for 29 CFR 1910.304

Frequently asked questions about 29 CFR 1910.304

What does 1910.304 require for grounding?

Under 1910.304(g)(5), the path to ground from circuits, equipment, and enclosures must be permanent, continuous, and effective.

Where does OSHA require GFCI protection in general industry?

Under 1910.304(b)(3), ground-fault circuit interrupter protection is required on 125-volt, single-phase, 15- and 20-ampere receptacles installed in bathrooms and on rooftops, and, on temporary wiring used during construction-like activities, on non-permanent 125-volt, single-phase, 15-, 20- and 30-ampere receptacles in use by personnel (others by GFCI or an assured equipment grounding conductor program) (1910.304(b)(3)(ii)). A GFCI monitors an imbalance between the current going out and coming back; it does not protect against every contact between conductors.

What does a broken equipment ground affect?

1910.304(g)(5) has the path to ground from circuits, equipment, and enclosures permanent, continuous, and effective. A broken path compromises one means of protection; it does not by itself show that every other protective device is inoperative.

What is the difference between 1910.304 and 1926.404?

1910.304 is the general-industry wiring-design and protection standard, and 1926.404 is its construction counterpart. Both require effective grounding and overcurrent protection, but construction's 1926.404 sets the rule for construction temporary power: GFCI protection or a written assured equipment grounding conductor program. The program is not exclusive to construction: 1910.304(b)(3)(ii) applies a similar GFCI and assured-grounding rule to temporary wiring used during construction-like activities (certain maintenance, remodeling or repair) in general industry.

Regulatory history of 29 CFR 1910.304

1910.304 is part of Subpart S, the design safety standards for electrical systems; 1910.302 sets the installations covered, the exclusions, and the dates of construction or modification from which some requirements apply.

Related glossary terms

Key terms that appear in 29 CFR 1910.304, each with a full plain-English explainer.

Get the Binder in Order Before the Inspector Arrives. Are You Ready?

OSHA inspections come unannounced, apart from the few exceptions listed in 29 CFR 1903.6. Get the binder in order before the opening conference, not during it.

Serious Violation

$16,550

per violation (max)

HazComFast Pro

$199/mo

10 jobsites, unlimited chemicals, unlimited workers

New sign-ups are paused. The free tools below need no account, and customers can log in as usual.

Your account keeps working as usual. Cancel anytime.