What 29 CFR 1910.137 requires (plain English)
29 CFR 1910.137 sets the design, electrical test, and in-service care requirements for electrical protective equipment: the rubber insulating gloves, sleeves, blankets, matting, line hose, and covers that protect workers from electric shock. It classifies this equipment by voltage rating (classes 00, 0, 1, 2, 3, and 4) and specifies the manufacturing and dielectric-strength requirements each class must meet.
Each class has a maximum use voltage in Table I-4: 500 volts ac for Class 00, 1,000 for Class 0, 7,500 for Class 1, 17,000 for Class 2, 26,500 for Class 3 and 36,000 for Class 4, with the notes of the table for particular configurations ((c)(2)(i)). Insulating equipment must be inspected for damage before each day's use and immediately after any incident that could have damaged it; insulating gloves must also be given an air test along with the inspection ((c)(2)(ii)). Rubber insulating gloves are tested before first issue and every 6 months thereafter, when their insulating value is suspect, after repair, and after use without protectors; blankets and sleeves before first issue and every 12 months, line hose and covers when the value is suspect and after repair (Table I-5); equipment tested but not issued may not be placed in service unless it was tested within the previous 12 months (1910.137(c)(2)(viii)). Protector gloves must be worn over insulating gloves, except under limited-use conditions where small equipment and parts manipulation needs unusually high finger dexterity: Class 0 gloves; Class 00 gloves if the voltage does not exceed 250 volts ac or 375 volts dc; and any other class only if the employer can demonstrate that the possibility of physical damage to the gloves is small and the glove is one class higher than the voltage requires. Gloves used without protectors may not be reused until electrically tested (1910.137(c)(2)(vii)). The employer must certify that equipment has been tested, identifying the equipment that passed and the test date; marking the equipment or keeping logs are acceptable means ((c)(2)(xii)).
1910.137 is about the equipment itself; the duty to actually use it comes from the electrical safe-work-practice standards: 1910.335 requires PPE and insulating equipment where employees work near energized parts, and 1910.333 sets the work practices (de-energize by default). For construction, the parallel requirements sit in Subpart K and Subpart V.