What 29 CFR 1910.137 requires (plain English)
29 CFR 1910.137 sets the design, electrical test, and in-service care requirements for electrical protective equipment: the rubber insulating gloves, sleeves, blankets, matting, line hose, and covers that protect workers from electric shock. It classifies this equipment by voltage rating (classes 00, 0, 1, 2, 3, and 4) and specifies the manufacturing and dielectric-strength requirements each class must meet.
Because insulating rubber degrades with use, ozone, and time, the standard is built around inspection and periodic electrical testing. Insulating equipment must be inspected for damage before each day's use and immediately after any incident that could have damaged it; rubber insulating gloves must be electrically retested at regular intervals, at least every six months in service, and blankets and other items on their own schedules. Leather protector gloves must be worn over rubber insulating gloves to shield them from mechanical damage.
1910.137 is about the equipment itself; the duty to actually use it comes from the electrical safe-work-practice standards: 1910.335 requires PPE and insulating equipment where employees work near energized parts, and 1910.333 sets the work practices (de-energize by default). For construction, the parallel requirements sit in Subpart K and Subpart V. Treat 1910.137 as the specification and testing rulebook for the rubber goods that those standards require.