Electrical – General Requirements

Verified vs OSHA sources · 2026-10-19

29 CFR 1910.303

29 CFR 1910.303 sets the general electrical requirements for general industry: electrical equipment must be approved (acceptable under 1910.399: accepted, certified, listed or labeled by a nationally recognized testing laboratory, or, for a kind of equipment no laboratory accepts, inspected or tested by another authority, or, for custom-made equipment, determined safe by its manufacturer on test data the employer keeps), installed and used per its listing, and live parts operating at 50 volts or more must be guarded against accidental contact.

29 CFR 1910.303 at a glance

What it requires
Electrical conductors and equipment must be safe, approved, and properly installed and maintained
Approval rule
Conductors and equipment are acceptable only if 'approved' as defined in 1910.399
Working space
Sufficient access and working space must be maintained around electrical equipment
Guarding
Live parts operating at 50 volts or more must be guarded against accidental contact
Max penalty (2026)
$16,550 per serious violation; $165,514 per willful
Common confusion
'Approved' means acceptable as defined in 1910.399, which has three routes

What 29 CFR 1910.303 requires (plain English)

29 CFR 1910.303 sets the general requirements for electrical installations in general industry: the design-and-installation foundation of OSHA's electrical standards (Subpart S). Its requirements cover conductors and equipment that are approved for the use, examined for safety, properly installed, marked, guarded, and accessible for safe operation and maintenance.

Conductors and equipment are acceptable only if "approved": a defined term (1910.399, "acceptable"). The first route is acceptance, certification, listing or labeling by a nationally recognized testing laboratory. Two other routes exist under strict conditions: for equipment of a kind no laboratory accepts, inspection or testing by another Federal agency or a State or local authority that enforces the National Electrical Code; and, for custom-made equipment built for one customer, a manufacturer's determination of safety based on test data the employer keeps and makes available to OSHA. Equipment must be examined for safety considerations including suitability for the use, mechanical strength, insulation, heating and arcing effects, and proper classification by voltage and current. Listed or labeled equipment must be installed and used in accordance with its listing instructions, and equipment must be marked with the manufacturer and ratings needed to judge safe application.

The standard also protects the people who work around electrical equipment. Live parts of equipment operating at 50 volts or more must be guarded against accidental contact, by approved enclosures, location, or barriers. Sufficient access and working space must be provided and maintained around electrical equipment to permit ready and safe operation and maintenance (with minimum clearances that increase with voltage), at least one entrance must give access to the working space, and the space must be illuminated and never used for storage.

The regulatory text

“The conductors and equipment required or permitted by this subpart shall be acceptable only if approved, as defined in § 1910.399.”
29 CFR 1910.303(a)

Key facts about 29 CFR 1910.303

  • Conductors and equipment are acceptable only if 'approved' as defined in 1910.399: NRTL acceptance, certification, listing or labeling; or, for a kind no NRTL accepts, inspection or testing by another authority; or, for custom-made equipment, a manufacturer's safety determination on test data the employer keeps.
  • Equipment must be examined for safety: suitability, mechanical strength, insulation, heating and arcing effects, and classification.
  • Listed or labeled equipment must be installed and used per its listing/labeling instructions (1910.303(b)(2)).
  • Live parts operating at 50 volts or more must be guarded against accidental contact (1910.303(g)(2)).
  • Sufficient access and working space must be maintained around electrical equipment (1910.303(g)(1)).
  • For equipment of 600 V or less, the working space may not be used for storage; indoor service equipment, switchboards, panelboards and motor control centers need illuminated working space, and at least one entrance gives access, with one at each end for equipment rated 1200 A or more and over 6 ft wide (with exceptions); over 600 V has its own rules in (h) (1910.303(g)-(h)).
  • Equipment must be durably marked with manufacturer identification and the ratings needed for safe use.
  • Each disconnecting means for motors and appliances, and each service, feeder and branch circuit at its disconnecting means or overcurrent device, is legibly marked to indicate its purpose, unless located and arranged so the purpose is evident (1910.303(f)(1)-(2)); in installations made after August 13, 2007, disconnecting means are capable of being locked in the open position ((f)(4); 1910.302(b)(4)).
  • 1910.302 sets the installations covered, the exclusions, and the dates of construction or modification from which some requirements apply.

Scope: who 29 CFR 1910.303 applies to

Regulatory framework
General Industry (29 CFR 1910)
Citation reference
29 CFR 1910.303
Enforcement status
In force and enforced
Jurisdiction
Federal OSHA (29 State-Plan jurisdictions may be stricter)

State-Plan states (e.g. California, Washington, Michigan) operate OSHA-approved programs that must be at least as effective as federal OSHA and frequently impose higher penalties or additional requirements.

Key requirements of 29 CFR 1910.303

#What the section requires or covers
1Use only conductors and equipment that are approved, meaning acceptable under the definition in 1910.399: accepted, certified, listed or labeled by a nationally recognized testing laboratory, or one of the other two routes the definition gives (1910.303(a))
2Keep the working space in front of electrical equipment of 600 volts or less to the depth Table S-1 sets for the nominal voltage to ground and the condition (3, 3.5 or 4 feet, 2.5 feet allowed for some installations built before April 16, 1981), at least 30 inches wide, with the headroom 1910.303(g)(1) requires
3For equipment over 600 volts, the working space follows 1910.303(h)(5)
4Legibly mark each disconnecting means for motors and appliances to show its purpose, and mark the other disconnects and circuit breakers as 1910.303(f) requires
5Keep electrical equipment free from recognized hazards, install and use listed or labeled equipment in accordance with the instructions in its listing or labeling, and protect it from physical damage (1910.303(b))

Summarized from the text of 29 CFR 1910.303.

Common Electrical General violations

Deficiencies OSHA cites under 29 CFR 1910.303 include the ones below, in no particular order. Each serious item carries up to $16,550 (2026).

  • Use of conductors or equipment that are not acceptable under any of the three routes of 1910.399 (1910.303(a)).
  • Live parts at 50 volts or more not guarded against accidental contact (1910.303(g)(2)).
  • Insufficient or obstructed working space around electrical equipment (storage in front of panels): 1910.303(g)(1).
  • Equipment not installed/used per its listing or labeling instructions (1910.303(b)(2)).
  • Missing equipment markings (manufacturer, ratings) needed to judge safe application (1910.303(e)).

What 'approved' means in 1910.303

In 1910.303 'approved' is defined in 1910.399 as 'acceptable', which has three routes: acceptance, certification, listing or labeling by a nationally recognized testing laboratory; inspection or testing by another authority for a kind of equipment no laboratory accepts; and, for custom-made equipment, a manufacturer's safety determination on test data the employer keeps and makes available. Absence of a listing is not by itself always the violation; the other two routes apply, and a modified device calls for a conformity evaluation, not a decision based on its appearance. Listed or labeled equipment is installed and used in accordance with its listing or labeling instructions ((b)(2)).

What OSHA inspectors look for

A compliance officer looks for unlisted or field-modified equipment, missing covers on panels and boxes, exposed energized parts, and inadequate working clearance in front of electrical equipment.

Example: how a violation is cited

Hypothetical case: a maintenance shop runs a 480-volt panel with a missing cover, leaving energized busbars exposed in a work area. 1910.303(g)(2) has live parts of electric equipment operating at 50 volts or more guarded against accidental contact. A serious violation carries a penalty of up to $16,550.

Illustrative example, not a specific OSHA case.

Electrical General compliance checklist

Each item is a requirement of 29 CFR 1910.303 that OSHA may verify during an inspection.

  • Use only conductors and equipment that are approved as defined in 1910.399, installed per the listing instructions.
  • Examine equipment for suitability, insulation, mechanical strength, and heating/arcing effects.
  • Guard live parts operating at 50 volts or more against accidental contact.
  • Maintain required working space and clearances around electrical equipment; never store items there.
  • Provide at least one entrance to, and illumination of, the working space.
  • Ensure equipment is durably marked with manufacturer identification and the ratings needed for safe use.

2026 penalties for 29 CFR 1910.303

Maximums set by 29 CFR 1903.15(d). 2026 maximums unchanged from 2025 (no CPI adjustment; OMB M-26-11), so not an increase; the serious and repeat policy minimums were revised with FOM chapter 6 (OSHA memo of May 21, 2026). The 2025 OSHA penalty levels remain in effect for 2026; OSHA made no inflation adjustment for 2026. 29 CFR 1903.15 identifies January 15, 2025 as the effective reference for these amounts, while OSHA's public penalties page currently references penalties assessed after Jan. 15, 2026.

Violation typeMinimumMaximumWhen it applies
Serious$1,085$16,550Death or serious physical harm could result, and the employer knew or could have known (29 U.S.C. 666(k)).
Other-Than-Serious$0$16,550Relates to safety/health but unlikely to cause death or serious harm.
Willful$11,823$165,514Intentional, knowing, or voluntary disregard of the requirement.
Repeated$4,256$165,514A substantially similar violation cited within the last 5 years.
Failure to AbateNone$16,550/dayup to $16,550 per day; the total is normally capped at 30 times the daily amount (FOM Ch.6)

Serious violations reach $16,550 and willful or repeat violations $165,514.

Maximums and the willful minimum are set by 29 CFR 1903.15(d); the serious and repeated minimums are OSHA policy floors from its annual penalty adjustment memo. OSHA applies gravity-based and size, good-faith and history reductions (FOM CPL 02-00-164 Ch.6). Estimates only, not legal advice.

The business case for Electrical General compliance

1910.303(a) has conductors and equipment acceptable only if approved, as defined in 1910.399, and (g)(2) has live parts of electric equipment operating at 50 volts or more guarded against accidental contact.

Free compliance tools for 29 CFR 1910.303

State plans and their penalty rules

States listed by the volume of their federal construction citations, not by this standard. Penalties and enforcement vary by state. State-Plan states may impose higher penalties and additional requirements beyond federal 29 CFR 1910.303.

State pages for 29 CFR 1910.303

Frequently asked questions about 29 CFR 1910.303

What does 'approved' mean in the OSHA electrical standard?

Under 1910.303(a) and the definition of 'acceptable' in 1910.399, equipment is approved if it is accepted, certified, listed or labeled by an NRTL; if, for a kind of equipment no NRTL accepts, another Federal agency or a State or local authority enforcing the National Electrical Code inspected or tested it; or if it is custom-made equipment a manufacturer determined safe on test data the employer keeps. Listed or labeled equipment is installed and used in accordance with its listing or labeling instructions (1910.303(b)(2)).

How much working space is required around electrical equipment?

Under 1910.303(g)(1), sufficient access and working space must be provided and maintained around electrical equipment (600 volts or less) to permit ready and safe operation and maintenance. (g)(1) has the depth of the clear working space set by the voltage and the conditions of Table S-1, a width of at least 30 inches or the width of the equipment if greater, doors that open to at least 90 degrees, and exceptions; over 600 volts follows (h) and Table S-2. The space is not used for storage, is illuminated and has at least one entrance.

When must live electrical parts be guarded?

Under 1910.303(g)(2), live parts of electric equipment operating at 50 volts or more must be guarded against accidental contact, by use of approved enclosures or cabinets, by location in a room or area accessible only to qualified persons, by suitable permanent partitions or screens, or by elevation of 8 feet or more above the working surface.

What is the difference between the electrical design standards and the work-practice standards?

The design and installation standards (1910.302–308, including 1910.303) govern how electrical systems must be built: approved equipment, guarding, working space, wiring methods. The safety-related work practice standards (1910.331–335) govern how workers interact with electrical systems: de-energizing and lockout/tagout of circuits, using qualified persons, and applying appropriate protective equipment. Compliance requires both a safe installation and safe work practices.

Regulatory history of 29 CFR 1910.303

1910.303 is part of Subpart S, the design safety standards for electrical systems (1910.302 to 1910.308); the safety-related work practices are in 1910.331 to 1910.335.

Related glossary terms

Key terms that appear in 29 CFR 1910.303, each with a full plain-English explainer.

Get the Binder in Order Before the Inspector Arrives. Are You Ready?

OSHA inspections come unannounced, apart from the few exceptions listed in 29 CFR 1903.6. Get the binder in order before the opening conference, not during it.

Serious Violation

$16,550

per violation (max)