Flammable Liquid

Verified vs OSHA sources · 2026-10-27

Under OSHA's HazCom standard, a liquid with a flash point of not more than 93 °C (199.4 °F) (Appendix B.6.1). The HCS sorts flammable liquids into four categories by flash point (FP) and, for Categories 1 and 2, initial boiling point (IBP). Category 1 (FP below 23 °C and IBP of 35 °C or less) is the highest flammability hazard in this class and Category 4 the lowest. The ranking compares only the flammable-liquid hazard within the class; it says nothing about a product's toxicity or its overall risk. At a lower flash point, a liquid gives off an ignitable mixture of vapor and air at a lower temperature.

29 CFR 1910.1200 App B.6

Flammable Liquid at a glance

  • Definition ceiling: flash point not more than 93 °C (199.4 °F) (Appendix B.6.1). Aerosols and chemicals under pressure should not be classified as flammable liquids (note to Appendix B.6.2; see Appendix B.3).
  • Category 1: FP below 23 °C (73.4 °F) and IBP of 35 °C (95 °F) or less. Category 2: FP below 23 °C and IBP above 35 °C. The initial boiling point separates these two categories only (Appendix B.6.2).
  • Category 3: FP at or above 23 °C and up to and including 60 °C (140 °F). Category 4: FP above 60 °C up to and including 93 °C (199.4 °F). A flash point of exactly 60 °C falls in Category 3.
  • The label elements follow the category (Appendix C.4.19): Categories 1 and 2 carry the signal word Danger, Category 3 carries Warning, all with the flame pictogram. Category 4 carries Warning and the hazard statement “Combustible liquid” with no pictogram. A product's label also reflects its other hazard classes.
  • The category is read from the product's SDS: the flash point (and, below 23 °C, the initial boiling point) for the actual product decides it, not the name of the liquid.

In plain English

A liquid with a flash point of 93 °C (199.4 °F) or lower, sorted into four flammability categories. The SDS gives the category for the product. Category 1 is the highest flammability hazard in the class and Category 4 the lowest.

What the rule says

“Flammable liquid means a liquid having a flash point of not more than 93 °C (199.4 °F).”
29 CFR 1910.1200 App B.6.1

In context

An industrial-hygiene, exposure-control, or program-management concept that applies across OSHA standards and workplaces.

29 CFR 1910 / 1926

Where this is written in OSHA's rules

Example

In this invented illustration, an SDS gives a flash point of 10 °C and an initial boiling point of 30 °C, so the liquid is Category 1 (flash point below 23 °C and initial boiling point of 35 °C or less). A liquid with the same flash point and an initial boiling point of 60 °C is Category 2. A liquid whose SDS reports a flash point of 60 °C is Category 3, because the Category 3 range includes 60 °C, and one at 61 °C is Category 4. In each case the values on the SDS of the actual product decide the category.

Why it matters

The category sets the signal word and hazard statement on the label, with the flame pictogram for Categories 1 to 3 (Appendix C.4.19). 1910.106 also uses categories in its storage and handling provisions, which depend as well on the place, the operation, the quantity and the container. Reading the category from the wrong flash point value puts a liquid in the wrong label group and can point to the wrong provisions.

Flammable vs. combustible liquid

In the HCS and in 1910.106(a)(19), every liquid with a flash point up to 93 °C is a flammable liquid, in Categories 1 to 4. “Combustible liquid” is not defined in 1910.106 anymore, since paragraph (a)(18) now reads only “[Reserved]”, and NFPA 30 and DOT use the term with their own limits (see the Combustible Liquid entry). The HCS label for Category 4 does use the words “Combustible liquid” as its hazard statement (Appendix C.4.19), while the flame pictogram goes with Categories 1 to 3 only.

HCS flammable liquid categories by flash point (FP) and initial boiling point (IBP) (Appendix B.6.2), with the hazard statement the HCS assigns

CategoryFlash pointInitial boiling pointHazard statement
1< 23 °C (73.4 °F)≤ 35 °C (95 °F)Extremely flammable liquid and vapor
2< 23 °C (73.4 °F)> 35 °C (95 °F)Highly flammable liquid and vapor
3≥ 23 °C and ≤ 60 °C (140 °F)Not usedFlammable liquid and vapor
4> 60 °C and ≤ 93 °C (199.4 °F)Not usedCombustible liquid

Flammable Liquid: frequently asked questions

What is Flammable Liquid?
Under OSHA's HazCom standard, a liquid with a flash point of not more than 93 °C (199.4 °F) (Appendix B.6.1). The HCS sorts flammable liquids into four categories by flash point (FP) and, for Categories 1 and 2, initial boiling point (IBP). Category 1 (FP below 23 °C and IBP of 35 °C or less) is the highest flammability hazard in this class and Category 4 the lowest. The ranking compares only the flammable-liquid hazard within the class; it says nothing about a product's toxicity or its overall risk. At a lower flash point, a liquid gives off an ignitable mixture of vapor and air at a lower temperature.
What is a flammable liquid under OSHA?
A liquid with a flash point of not more than 93 °C (199.4 °F), per 1910.1200 Appendix B.6.1; 1910.106(a)(19) uses the same limit. The HCS divides flammable liquids into four categories by flash point, and by initial boiling point for Categories 1 and 2.
What's the difference between the flammable liquid categories?
Category 1 has the lowest flash point (below 23 °C) with an initial boiling point of 35 °C or less and is the highest flammability hazard in the class. Categories 2 to 4 have progressively higher flash points, and Category 4 tops out at 93 °C. The ranking covers the flammable-liquid hazard only, not a product's toxicity or overall risk.
Is diesel a flammable liquid?
It depends on the flash point reported on the product's SDS, which differs between grades. A product with a flash point from 23 °C up to and including 60 °C is Category 3, and one above 60 °C and up to 93 °C is Category 4. Both are flammable liquids under the HCS, and the label for Category 4 reads “Combustible liquid” with no pictogram.

Related terms

Free tools for this

Governing OSHA standards

More General Safety terms

Arc Flash

An arc flash is the sudden release of thermal energy from an electrical arc fault, a short circuit that jumps through the air between energized parts. The arc can reach temperatures over 35,000°F (nearly four times the surface of the sun), causing severe burns, igniting clothing, and driving an explosive pressure wave known as the arc blast. OSHA has no single “arc-flash standard”. Its electrical rules apply instead: 29 CFR 1910.333 and 1910.335 for work practices and PPE, and 1910.269 for electric power work. The analysis method (arc-flash boundary, incident energy, arc-rated PPE) comes from NFPA 70E, a consensus standard that OSHA has not adopted; OSHA and employers can use it as a guide for hazard analysis and controls (OSHA interpretation 2006-11-14).

Experience Modification Rate (EMR)

A workers' compensation insurance multiplier that adjusts an employer's premium to reflect its own payroll and loss record compared with the expected experience of employers in the same classification. A mod of 1.00 leaves the premium unchanged (the unity mod). A mod above 1.00, a debit mod, raises the premium, and one below 1.00, a credit mod, lowers it. The mod multiplies the premium calculated before the modification. It's set by rating bureaus (NCCI or a state bureau) under each state's rules, not by OSHA.

Action Level

An airborne concentration of a substance, below the exposure limit, at which certain provisions of an OSHA standard begin to apply. Which provisions depend on the standard: they can include exposure assessment or monitoring, training and medical surveillance, each with its own trigger. The action level is set in each standard. For respirable crystalline silica it is 25 µg/m³ as an 8-hour TWA, half the 50 µg/m³ PEL; for lead it is 30 µg/m³ against a PEL of 50 µg/m³ (1910.1025), and for formaldehyde 0.5 ppm against a PEL of 0.75 ppm (1910.1048).

Administrative Controls

Changes to how and when work is done that reduce a worker's exposure without changing the hazard itself. NIOSH places administrative controls fourth in the hierarchy of controls, below elimination, substitution and engineering controls and above personal protective equipment, and gives examples such as work process training, job rotation, adequate rest breaks, limiting access to hazardous areas or machinery, and adjusting line speeds. Housekeeping, written procedures and signage fit the same description. The hierarchy is a preference order. What an OSHA standard calls for is in that standard's own words.

Biological Exposure Index (BEI)

An ACGIH guidance value for evaluating biological monitoring results. A BEI generally represents the level of a determinant most likely to be observed in specimens from healthy workers exposed at the TLV-TWA level. The determinant can be the chemical itself, one or more metabolites, or a characteristic, reversible biochemical change induced by the chemical, measured in a specimen such as blood, urine or exhaled breath. BEIs do not indicate a sharp distinction between hazardous and nonhazardous exposures, and they are advisory: an OSHA standard that calls for biological monitoring sets its own terms.

California Proposition 65

California's Safe Drinking Water and Toxic Enforcement Act of 1986. As OEHHA describes it, businesses give a “clear and reasonable” warning before knowingly and intentionally exposing anyone to a chemical on the state's list, unless the business can show that the anticipated exposure will not pose a significant risk of cancer or is significantly below levels observed to cause birth defects or other reproductive harm. The list has grown to approximately 900 chemicals. The warning requirement takes effect one year after a chemical is listed, and businesses with less than 10 employees and government agencies are exempt. The law also prohibits knowingly discharging listed chemicals into sources of drinking water. It is a California law, and the test is the exposure a business causes, not the presence of a listed chemical alone.

CAS Number

A numerical identifier assigned by CAS (Chemical Abstracts Service, a division of the American Chemical Society) to a substance registered in the CAS REGISTRY. CAS describes a CAS Registry Number as a unique and unambiguous identifier for a specific substance. Substances are added when they are identified in literature being indexed for the CAS Content Collection or when an entity requests a number for a novel substance. The number has up to 10 digits in three groups separated by hyphens: 2 to 7 digits, 2 digits, and one check digit (for example, 67-64-1 for acetone). CAS is the source and final authority for CAS Registry Numbers, and other resources may associate an incorrect number with a compound.

Ceiling Limit

An exposure limit that may not be exceeded at any instant during the workday. In OSHA's Z-tables it is marked with a “C” before the value. Unlike an 8-hour TWA (an average) or a 15-minute STEL, a Table Z-1 ceiling applies to a single moment; if instantaneous monitoring is not feasible, it is assessed as a 15-minute time-weighted average that may not be exceeded at any time during the working day. Table Z-2 instead uses an acceptable ceiling concentration with a separate acceptable maximum peak allowed for a limited time (1910.1000(a)(1), (b)(2)-(3)).

Sources & verification

Checked against the eCFR and OSHA.gov. Last reviewed 2026-10-27. This glossary is general information, not legal advice; OSHA State-Plan states (e.g. California, Michigan) may adopt stricter requirements.

A related free tool

The free HazCom Audit Checklist (2026) covers a task related to Flammable Liquid. Read the rule above first, then use the tool for your own workplace.

Get the Binder in Order Before the Inspector Arrives. Are You Ready?

OSHA inspections come unannounced, apart from the few exceptions listed in 29 CFR 1903.6. Get the binder in order before the opening conference, not during it.

Serious Violation

$16,550

per violation (max)

HazComFast Pro

$199/mo

10 jobsites, unlimited chemicals, unlimited workers

New sign-ups are paused. The free tools below need no account, and customers can log in as usual.

Your account keeps working as usual. Cancel anytime.