General safety term · Glossary
Combustible Liquid
Verified vs OSHA sources · 2026-10-27
A liquid that can burn but has a higher flash point than a flammable liquid. Three rulebooks use the word and draw the line differently. In 29 CFR 1910.106, the paragraph that formerly defined it, (a)(18), now reads only “[Reserved]”, and (a)(19) defines a flammable liquid as any liquid with a flashpoint at or below 199.4 °F (93 °C), in four categories. The 100 °F line still appears inside that section: a Category 3 liquid with a flashpoint at or above 100 °F that is heated for use to within 30 °F of its flashpoint is handled as a Category 3 liquid with a flashpoint below 100 °F (1910.106(a)(19)(iii)), and other provisions of 1910.106, such as tank vents and inside storage room wiring, treat Category 3 liquids below 100 °F and at or above 100 °F differently. NFPA 30, a consensus fire code, keeps the Class II, IIIA and IIIB scheme with limits at 100, 140 and 200 °F. DOT's hazardous materials rules define a combustible liquid for transport in 49 CFR 173.120(b): a liquid that meets no other hazard class definition and has a flash point above 60 °C (140 °F) and below 93 °C (200 °F). So the word has no single meaning, and the rulebook behind the question decides what it covers.
Also known as: combustible liquids
On this page
Combustible Liquid at a glance
- In 29 CFR 1910.106, paragraph (a)(18) now reads only “[Reserved]”. What (a)(19) defines is a flammable liquid, any liquid with a flashpoint at or below 199.4 °F, in four categories: Category 3 from 73.4 °F up to and including 140 °F, and Category 4 above 140 °F up to and including 199.4 °F.
- The 100 °F line has not left 1910.106. A Category 3 liquid with a flashpoint at or above 100 °F that is heated for use to within 30 °F of its flashpoint is handled as a Category 3 liquid with a flashpoint below 100 °F, and a Category 4 liquid heated the same way is handled as a Category 3 liquid with a flashpoint at or above 100 °F (1910.106(a)(19)(iii) and (iv)). A liquid above 199.4 °F heated for use to within 30 °F of its flashpoint is handled as a Category 4 liquid (1910.106(a)(19)(v)).
- NFPA 30 uses its own classes: Class II from 100 °F up to 140 °F, Class IIIA from 140 °F up to 200 °F and Class IIIB at 200 °F and above. These are NFPA's limits, not OSHA's, and they sit on different boundaries than the OSHA categories.
- DOT's hazardous materials rules treat a liquid with a flash point of 60 °C (140 °F) or less as a Class 3 flammable liquid, and a liquid that meets no other hazard class with a flash point above 60 °C (140 °F) and below 93 °C (200 °F) as a combustible liquid (49 CFR 173.120(a) and (b)). Under 173.120(b)(2), a flammable liquid with a flash point at or above 38 °C (100 °F) that meets no other hazard class may be reclassed as a combustible liquid, except for transport by vessel or aircraft.
- A flash point is the lowest temperature at which a liquid gives off vapor in a test vessel in enough concentration to form an ignitable mixture with air near the surface (1910.106(a)(14)). It is measured by a specified test method, so it describes the test and not every real condition. Flash points differ between fuel grades and formulations, and Section 9 of the SDS gives the figure for the product on site.
In plain English
A liquid that can burn but has a higher flash point than a flammable liquid. NFPA 30, OSHA 1910.106 and DOT each draw the line differently. The flash point on the SDS and the rulebook you are working under decide which label applies.
What the rule says
“Flammable liquid means any liquid having a flashpoint at or below 199.4 °F (93 °C). Flammable liquids are divided into four categories as follows: ... (iii) Category 3 shall include liquids having flashpoints at or above 73.4 °F (23 °C) and at or below 140 °F (60 °C). ... (iv) Category 4 shall include liquids having flashpoints above 140 °F (60 °C) and at or below 199.4 °F (93 °C).”
In context
An industrial-hygiene, exposure-control, or program-management concept that applies across OSHA standards and workplaces.
Where this is written in OSHA's rules
- 29 CFR 1910.106(a)(19)Read on eCFR / OSHA.gov
- 29 CFR 1910.106Read on eCFR / OSHA.gov
- 29 CFR 1910.106(a)(19)(iii)Read on eCFR / OSHA.gov
Example
In this invented illustration, the SDS of a liquid gives a flash point of 130 °F (54 °C). Under 29 CFR 1910.106(a)(19)(iii) it is a Category 3 flammable liquid, because 130 °F falls between 73.4 °F and 140 °F. Under NFPA 30 it is a Class II combustible liquid, because 130 °F falls between 100 °F and 140 °F. In DOT's transport rules it is a Class 3 flammable liquid under 49 CFR 173.120(a), because its flash point is not more than 140 °F, although 173.120(b)(2) lets a shipper reclass it as combustible when it meets no other hazard class, except by vessel or aircraft. Which of these labels applies depends on the rulebook behind the question.
Why it matters
The same liquid can carry different names in different rulebooks, so a storage plan, a label or a shipping paper has to name the rulebook it follows. Heat matters too: 1910.106(a)(19) itself handles a liquid heated for use close to its flashpoint under the requirements for a more flammable category, so a high flash point alone does not settle how a liquid is handled. Whether a particular room or area is a classified location depends on the conditions of the rule that applies.
Combustible vs. flammable depends on the rulebook
“Flammable below 100 °F, combustible at or above 100 °F” is the NFPA 30 split. It is not how 29 CFR 1910.106 sorts liquids, which defines flammable liquids up to 199.4 °F in four categories, and it is not the DOT split at 140 °F. Name the rulebook whenever you quote a cut-off. Both flammable and combustible liquids can burn.
How the three rulebooks cut the flash-point scale (the lines do not match, so the rows are not equivalents)
| Rulebook and class | Flash point | Boundary notes |
|---|---|---|
| OSHA 1910.106(a)(19)(iii), Category 3 | 73.4 °F up to and including 140 °F | Flammable liquid; includes 140 °F, which NFPA 30 places in Class IIIA |
| OSHA 1910.106(a)(19)(iv), Category 4 | Above 140 °F up to and including 199.4 °F | Flammable liquid; the upper limit is 199.4 °F, not 200 °F |
| NFPA 30, Class II | 100 °F up to 140 °F | Combustible liquid in NFPA 30 |
| NFPA 30, Class IIIA | 140 °F up to 200 °F | Combustible liquid in NFPA 30 |
| NFPA 30, Class IIIB | 200 °F and above | Above the OSHA Category 4 limit of 199.4 °F |
| DOT 49 CFR 173.120(b) | Above 140 °F and below 200 °F | Combustible liquid for transport if it meets no other hazard class; 173.120(b)(2) allows some reclassing |
Combustible Liquid: frequently asked questions
- What is Combustible Liquid?
- A liquid that can burn but has a higher flash point than a flammable liquid. Three rulebooks use the word and draw the line differently. In 29 CFR 1910.106, the paragraph that formerly defined it, (a)(18), now reads only “[Reserved]”, and (a)(19) defines a flammable liquid as any liquid with a flashpoint at or below 199.4 °F (93 °C), in four categories. The 100 °F line still appears inside that section: a Category 3 liquid with a flashpoint at or above 100 °F that is heated for use to within 30 °F of its flashpoint is handled as a Category 3 liquid with a flashpoint below 100 °F (1910.106(a)(19)(iii)), and other provisions of 1910.106, such as tank vents and inside storage room wiring, treat Category 3 liquids below 100 °F and at or above 100 °F differently. NFPA 30, a consensus fire code, keeps the Class II, IIIA and IIIB scheme with limits at 100, 140 and 200 °F. DOT's hazardous materials rules define a combustible liquid for transport in 49 CFR 173.120(b): a liquid that meets no other hazard class definition and has a flash point above 60 °C (140 °F) and below 93 °C (200 °F). So the word has no single meaning, and the rulebook behind the question decides what it covers.
- What is the difference between a flammable and a combustible liquid?
- It depends on the rulebook. In NFPA 30, a flammable liquid has a flash point below 100 °F and a combustible liquid has a flash point at or above 100 °F. In 29 CFR 1910.106, the word combustible no longer has its own definition, and flammable liquids run up to a flashpoint of 199.4 °F. In DOT's transport rules, a flammable liquid has a flash point of 140 °F or less and a combustible liquid is above 140 °F and below 200 °F.
- Is diesel flammable or combustible?
- It depends on the product's flash point and on the rulebook. Flash points differ between diesel grades and formulations, so Section 9 of the product's SDS gives the figure to use. If that figure is from 100 °F up to 140 °F, NFPA 30 calls it a Class II combustible liquid and OSHA's HCS classifies it as a Category 3 flammable liquid. If it is above 140 °F and up to 199.4 °F, NFPA 30 puts it in Class IIIA and the HCS in Category 4.
- How do combustible liquids map to GHS?
- Only partly. The OSHA and GHS categories in 1910.106(a)(19) and 1910.1200 Appendix B.6 run up to a flashpoint of 199.4 °F: Category 3 from 73.4 °F up to and including 140 °F and Category 4 above 140 °F up to and including 199.4 °F. The lines do not match NFPA 30: Category 3 includes 140 °F, which NFPA places in Class IIIA, and Category 4 ends at 199.4 °F, not 200 °F. A liquid above 199.4 °F falls outside those categories, although 1910.106(a)(19)(v) handles it as a Category 4 liquid when it is heated for use to within 30 °F of its flashpoint.
Related terms
Free tools for this
Governing OSHA standards
More General Safety terms
An arc flash is the sudden release of thermal energy from an electrical arc fault, a short circuit that jumps through the air between energized parts. The arc can reach temperatures over 35,000°F (nearly four times the surface of the sun), causing severe burns, igniting clothing, and driving an explosive pressure wave known as the arc blast. OSHA has no single “arc-flash standard”. Its electrical rules apply instead: 29 CFR 1910.333 and 1910.335 for work practices and PPE, and 1910.269 for electric power work. The analysis method (arc-flash boundary, incident energy, arc-rated PPE) comes from NFPA 70E, a consensus standard that OSHA has not adopted; OSHA and employers can use it as a guide for hazard analysis and controls (OSHA interpretation 2006-11-14).
Experience Modification Rate (EMR)A workers' compensation insurance multiplier that adjusts an employer's premium to reflect its own payroll and loss record compared with the expected experience of employers in the same classification. A mod of 1.00 leaves the premium unchanged (the unity mod). A mod above 1.00, a debit mod, raises the premium, and one below 1.00, a credit mod, lowers it. The mod multiplies the premium calculated before the modification. It's set by rating bureaus (NCCI or a state bureau) under each state's rules, not by OSHA.
Action LevelAn airborne concentration of a substance, below the exposure limit, at which certain provisions of an OSHA standard begin to apply. Which provisions depend on the standard: they can include exposure assessment or monitoring, training and medical surveillance, each with its own trigger. The action level is set in each standard. For respirable crystalline silica it is 25 µg/m³ as an 8-hour TWA, half the 50 µg/m³ PEL; for lead it is 30 µg/m³ against a PEL of 50 µg/m³ (1910.1025), and for formaldehyde 0.5 ppm against a PEL of 0.75 ppm (1910.1048).
Administrative ControlsChanges to how and when work is done that reduce a worker's exposure without changing the hazard itself. NIOSH places administrative controls fourth in the hierarchy of controls, below elimination, substitution and engineering controls and above personal protective equipment, and gives examples such as work process training, job rotation, adequate rest breaks, limiting access to hazardous areas or machinery, and adjusting line speeds. Housekeeping, written procedures and signage fit the same description. The hierarchy is a preference order. What an OSHA standard calls for is in that standard's own words.
Biological Exposure Index (BEI)An ACGIH guidance value for evaluating biological monitoring results. A BEI generally represents the level of a determinant most likely to be observed in specimens from healthy workers exposed at the TLV-TWA level. The determinant can be the chemical itself, one or more metabolites, or a characteristic, reversible biochemical change induced by the chemical, measured in a specimen such as blood, urine or exhaled breath. BEIs do not indicate a sharp distinction between hazardous and nonhazardous exposures, and they are advisory: an OSHA standard that calls for biological monitoring sets its own terms.
California Proposition 65California's Safe Drinking Water and Toxic Enforcement Act of 1986. As OEHHA describes it, businesses give a “clear and reasonable” warning before knowingly and intentionally exposing anyone to a chemical on the state's list, unless the business can show that the anticipated exposure will not pose a significant risk of cancer or is significantly below levels observed to cause birth defects or other reproductive harm. The list has grown to approximately 900 chemicals. The warning requirement takes effect one year after a chemical is listed, and businesses with less than 10 employees and government agencies are exempt. The law also prohibits knowingly discharging listed chemicals into sources of drinking water. It is a California law, and the test is the exposure a business causes, not the presence of a listed chemical alone.
CAS NumberA numerical identifier assigned by CAS (Chemical Abstracts Service, a division of the American Chemical Society) to a substance registered in the CAS REGISTRY. CAS describes a CAS Registry Number as a unique and unambiguous identifier for a specific substance. Substances are added when they are identified in literature being indexed for the CAS Content Collection or when an entity requests a number for a novel substance. The number has up to 10 digits in three groups separated by hyphens: 2 to 7 digits, 2 digits, and one check digit (for example, 67-64-1 for acetone). CAS is the source and final authority for CAS Registry Numbers, and other resources may associate an incorrect number with a compound.
Ceiling LimitAn exposure limit that may not be exceeded at any instant during the workday. In OSHA's Z-tables it is marked with a “C” before the value. Unlike an 8-hour TWA (an average) or a 15-minute STEL, a Table Z-1 ceiling applies to a single moment; if instantaneous monitoring is not feasible, it is assessed as a 15-minute time-weighted average that may not be exceeded at any time during the working day. Table Z-2 instead uses an acceptable ceiling concentration with a separate acceptable maximum peak allowed for a limited time (1910.1000(a)(1), (b)(2)-(3)).
Sources & verification
- 29 CFR 1910.106(a)(19) (eCFR / OSHA.gov)
- 29 CFR 1910.106 (eCFR / OSHA.gov)
- 29 CFR 1910.106(a)(19)(iii) (eCFR / OSHA.gov)
- eCFR: 29 CFR 1910.106, Flammable liquids (including (a)(18) and (a)(19))
- eCFR: 49 CFR 173.120, Class 3, Definitions (DOT flammable and combustible liquids)
- OSHA: Appendix B to §1910.1200, Physical hazard criteria (B.6 Flammable liquids)
- NFPA: NFPA 30 fact sheet (Class II, IIIA and IIIB limits)
Checked against the eCFR, OSHA.gov and NFPA. Last reviewed 2026-10-27. This glossary is general information, not legal advice; OSHA State-Plan states (e.g. California, Michigan) may adopt stricter requirements.
A related free tool
The free Flammable Liquid GHS Category Classifier covers a task related to Combustible Liquid. Read the rule above first, then use the tool for your own workplace.
Get the Binder in Order Before the Inspector Arrives. Are You Ready?
OSHA inspections come unannounced, apart from the few exceptions listed in 29 CFR 1903.6. Get the binder in order before the opening conference, not during it.
Serious Violation
$16,550
per violation (max)
HazComFast Pro
$199/mo
10 jobsites, unlimited chemicals, unlimited workers
New sign-ups are paused. The free tools below need no account, and customers can log in as usual.
Your account keeps working as usual. Cancel anytime.