Arc Flash
Verified vs OSHA sources · 2026-10-27
An arc flash is the sudden release of thermal energy from an electrical arc fault, a short circuit that jumps through the air between energized parts. The arc can reach temperatures over 35,000°F (nearly four times the surface of the sun), causing severe burns, igniting clothing, and driving an explosive pressure wave known as the arc blast. OSHA has no single “arc-flash standard”. Its electrical rules apply instead: 29 CFR 1910.333 and 1910.335 for work practices and PPE, and 1910.269 for electric power work. The analysis method (arc-flash boundary, incident energy, arc-rated PPE) comes from NFPA 70E, a consensus standard that OSHA has not adopted; OSHA and employers can use it as a guide for hazard analysis and controls (OSHA interpretation 2006-11-14).
Also known as: arc blast, electric arc-flash, flashover
On this page
Arc Flash at a glance
- An electric arc can exceed 35,000°F, nearly four times the temperature of the sun's surface (OSHA).
- The arc-flash boundary is the distance at which the incident energy reaches 1.2 cal/cm², the onset of a second-degree burn on bare skin (NFPA 70E).
- There is no single OSHA “arc-flash standard”. OSHA covers the hazard through its electrical rules: PPE and work practices in 29 CFR 1910.333 and 1910.335 (general industry) and 1926 Subpart K (construction), and arc-flash protection for power work in 1910.269(l)(8). OSHA has not adopted NFPA 70E; it and employers can use it as a guide (OSHA interpretation 2006-11-14).
- Arc-rated (AR) clothing must carry an arc rating (ATPV or EBT, in cal/cm²) at least equal to the calculated incident energy at the working distance.
- In May 2024 OSHA cited a tool manufacturer for one willful and four serious violations, with $222,392 in proposed penalties, after a maintenance electrician suffered severe burns in an electrical arc blast (U.S. Department of Labor news release 24-960-CHI).
- PPE Category 1: 4 cal/cm² (minimum arc rating)
- PPE Category 2: 8 cal/cm² (minimum arc rating)
- PPE Category 3: 25 cal/cm² (minimum arc rating)
- PPE Category 4: 40 cal/cm² (minimum arc rating)
Scale: 0–40 cal/cm² (minimum arc rating) (the minimum arc rating of each NFPA 70E PPE category; choosing PPE from a calculated incident energy is a separate method)
In plain English
A violent electrical explosion. When electricity jumps across a gap (from a dropped tool, a loose connection, or dust and moisture), it creates an arc hotter than the sun that can burn a worker severely from feet away, without any contact. The defense is de-energizing first, and, when live work is truly unavoidable, wearing clothing rated to survive the heat.
What the rule says
“Employees shall wear protective equipment for the eyes or face wherever there is danger of injury to the eyes or face from electric arcs or flashes or from flying objects resulting from electrical explosion.”
In context
An industrial-hygiene, exposure-control, or program-management concept that applies across OSHA standards and workplaces.
Where this is written in OSHA's rules
- 29 CFR 1910.335(a)(1)(v)Read on eCFR / OSHA.gov
- 29 CFR 1910.333Read on eCFR / OSHA.gov
- 29 CFR 1910.269Read on eCFR / OSHA.gov
Example
A panel with a calculated incident energy of 8 cal/cm² at an 18-inch working distance calls for arc-rated clothing and equipment whose arc rating matches or exceeds that 8 cal/cm² estimate (the incident-energy method that NFPA 70E and 29 CFR 1910.269 use). The NFPA 70E PPE category tables are a separate method: they assign a category to the task, and each category sets a minimum arc rating (Category 2 is 8 cal/cm²). A worker in ordinary cotton coveralls at that panel would face a second-degree burn well past the 1.2 cal/cm² threshold, and untreated fabric can ignite and keep burning.
Why it matters
Arc flash is one of the deadliest electrical hazards because the worker never has to touch anything: the heat, the pressure wave, and the molten-metal shrapnel reach out. Because OSHA has no single arc-flash rule, employers sometimes assume the hazard is unregulated. It is covered: 29 CFR 1910.333 and 1910.335 govern electrical work practices and PPE, 1910.269(l)(8) covers power work, and OSHA treats NFPA 70E as a guide because it has not adopted it (OSHA interpretation 2006-11-14). In May 2024 OSHA proposed $222,392 in penalties against a manufacturer after a maintenance electrician was severely burned in an arc blast.
History & background
Arc-flash burns were recognized long before they could be quantified. Ralph Lee's 1982 paper “The Other Electrical Hazard: Electric Arc Blast Burns” gave engineers a way to calculate the burn threshold, and NFPA, which had published the first edition of NFPA 70E in 1979 at OSHA's request, built the arc-flash boundary and incident-energy analysis into later editions. OSHA added explicit arc-flash and incident-energy protection to the power-work standard at 29 CFR 1910.269(l)(8) in its 2014 final rule.
Arc flash vs. arc blast, and vs. shock
The arc FLASH is the intense thermal and light energy (the burn hazard). The arc BLAST is the pressure wave, superheated gases, and vaporized-metal shrapnel that accompany it (the concussion and projectile hazard). Both differ from electric SHOCK, which requires actual contact with an energized part. The arc-flash boundary guards against burns; the shock approach boundaries (limited and restricted) guard against contact. They are calculated differently and rarely coincide.
Arc-flash boundary vs. the shock approach boundaries (NFPA 70E)
| Boundary | Hazard it addresses | What it means |
|---|---|---|
| Arc-flash boundary | Thermal (burns) | Distance where incident energy = 1.2 cal/cm² (second-degree-burn onset); NFPA 70E calls for arc-rated PPE inside it |
| Limited approach | Shock (contact) | Unqualified persons kept outside unless escorted by a qualified person |
| Restricted approach | Shock (increased contact risk) | Only qualified persons, with shock PPE and a documented plan, may cross |
Arc Flash: frequently asked questions
- What is Arc Flash?
- An arc flash is the sudden release of thermal energy from an electrical arc fault, a short circuit that jumps through the air between energized parts. The arc can reach temperatures over 35,000°F (nearly four times the surface of the sun), causing severe burns, igniting clothing, and driving an explosive pressure wave known as the arc blast. OSHA has no single “arc-flash standard”. Its electrical rules apply instead: 29 CFR 1910.333 and 1910.335 for work practices and PPE, and 1910.269 for electric power work. The analysis method (arc-flash boundary, incident energy, arc-rated PPE) comes from NFPA 70E, a consensus standard that OSHA has not adopted; OSHA and employers can use it as a guide for hazard analysis and controls (OSHA interpretation 2006-11-14).
- Is arc flash covered by an OSHA standard?
- Not by a single one. OSHA covers electrical PPE and work practices in 29 CFR 1910.333 and 1910.335 (general industry) and 1926 Subpart K (construction), and arc-flash protection for electric power generation, transmission, and distribution work in 1910.269(l)(8). For most other work OSHA has no arc-flash-specific rule. OSHA has not adopted NFPA 70E, so it does not enforce it, although OSHA and employers can use it as a guide. The General Duty Clause is not used to enforce consensus standards and usually is not used where a specific standard applies (OSHA interpretation 2006-11-14).
- What is the arc-flash boundary?
- The arc-flash boundary is the distance from an exposed energized part at which the incident energy equals 1.2 cal/cm², the level that produces a second-degree burn on bare skin. Under NFPA 70E, anyone inside that boundary wears arc-rated PPE chosen either from the incident energy at the working distance or from the PPE category tables. A calculated incident energy is an estimate, and arc-rated clothing lowers the burn injury without removing all risk: at an arc rating equal to the incident energy, a worker has a 50-percent chance of just barely receiving a second-degree burn (29 CFR 1910.269 Appendix E).
- What is the difference between arc flash and arc blast?
- Arc flash is the thermal and light energy of the arc: the burn hazard. Arc blast is the explosive pressure wave, hot gases, and molten-metal shrapnel thrown by the same event: the concussion and projectile hazard. A single arc-fault event usually produces both.
- How hot is an arc flash?
- An electric arc can exceed 35,000°F, nearly four times the temperature of the surface of the sun (OSHA). At that temperature it vaporizes copper and other metals almost instantly, which is what drives the arc blast's pressure wave and shrapnel.
Related terms
Free tools for this
Governing OSHA standards
More General Safety terms
A workers' compensation insurance multiplier that adjusts an employer's premium to reflect its own payroll and loss record compared with the expected experience of employers in the same classification. A mod of 1.00 leaves the premium unchanged (the unity mod). A mod above 1.00, a debit mod, raises the premium, and one below 1.00, a credit mod, lowers it. The mod multiplies the premium calculated before the modification. It's set by rating bureaus (NCCI or a state bureau) under each state's rules, not by OSHA.
Action LevelAn airborne concentration of a substance, below the exposure limit, at which certain provisions of an OSHA standard begin to apply. Which provisions depend on the standard: they can include exposure assessment or monitoring, training and medical surveillance, each with its own trigger. The action level is set in each standard. For respirable crystalline silica it is 25 µg/m³ as an 8-hour TWA, half the 50 µg/m³ PEL; for lead it is 30 µg/m³ against a PEL of 50 µg/m³ (1910.1025), and for formaldehyde 0.5 ppm against a PEL of 0.75 ppm (1910.1048).
Administrative ControlsChanges to how and when work is done that reduce a worker's exposure without changing the hazard itself. NIOSH places administrative controls fourth in the hierarchy of controls, below elimination, substitution and engineering controls and above personal protective equipment, and gives examples such as work process training, job rotation, adequate rest breaks, limiting access to hazardous areas or machinery, and adjusting line speeds. Housekeeping, written procedures and signage fit the same description. The hierarchy is a preference order. What an OSHA standard calls for is in that standard's own words.
Biological Exposure Index (BEI)An ACGIH guidance value for evaluating biological monitoring results. A BEI generally represents the level of a determinant most likely to be observed in specimens from healthy workers exposed at the TLV-TWA level. The determinant can be the chemical itself, one or more metabolites, or a characteristic, reversible biochemical change induced by the chemical, measured in a specimen such as blood, urine or exhaled breath. BEIs do not indicate a sharp distinction between hazardous and nonhazardous exposures, and they are advisory: an OSHA standard that calls for biological monitoring sets its own terms.
California Proposition 65California's Safe Drinking Water and Toxic Enforcement Act of 1986. As OEHHA describes it, businesses give a “clear and reasonable” warning before knowingly and intentionally exposing anyone to a chemical on the state's list, unless the business can show that the anticipated exposure will not pose a significant risk of cancer or is significantly below levels observed to cause birth defects or other reproductive harm. The list has grown to approximately 900 chemicals. The warning requirement takes effect one year after a chemical is listed, and businesses with less than 10 employees and government agencies are exempt. The law also prohibits knowingly discharging listed chemicals into sources of drinking water. It is a California law, and the test is the exposure a business causes, not the presence of a listed chemical alone.
CAS NumberA numerical identifier assigned by CAS (Chemical Abstracts Service, a division of the American Chemical Society) to a substance registered in the CAS REGISTRY. CAS describes a CAS Registry Number as a unique and unambiguous identifier for a specific substance. Substances are added when they are identified in literature being indexed for the CAS Content Collection or when an entity requests a number for a novel substance. The number has up to 10 digits in three groups separated by hyphens: 2 to 7 digits, 2 digits, and one check digit (for example, 67-64-1 for acetone). CAS is the source and final authority for CAS Registry Numbers, and other resources may associate an incorrect number with a compound.
Ceiling LimitAn exposure limit that may not be exceeded at any instant during the workday. In OSHA's Z-tables it is marked with a “C” before the value. Unlike an 8-hour TWA (an average) or a 15-minute STEL, a Table Z-1 ceiling applies to a single moment; if instantaneous monitoring is not feasible, it is assessed as a 15-minute time-weighted average that may not be exceeded at any time during the working day. Table Z-2 instead uses an acceptable ceiling concentration with a separate acceptable maximum peak allowed for a limited time (1910.1000(a)(1), (b)(2)-(3)).
Chemical CompatibilityWhether two or more chemicals can be stored or used near each other without reacting dangerously, for example by releasing heat, toxic gas or fire. A safety data sheet gives incompatible materials in Section 10 and includes any incompatibilities in the storage conditions of Section 7 (Appendix D, Table D.1). Keeping incompatibles apart in storage is a recognized safety practice: Appendix A to OSHA's laboratory standard, which gives recommendations and sets no duties, advises consulting the SDS and keeping incompatibles separate during transport, storage, use and disposal (1910.1450 App A), and CDC's pool chemical guidance advises storing incompatible chemicals away from each other. What separation a given place needs depends on the products, the quantities, the containers, the manufacturer's instructions and local codes.
Sources & verification
- 29 CFR 1910.335(a)(1)(v) (eCFR / OSHA.gov)
- 29 CFR 1910.333 (eCFR / OSHA.gov)
- 29 CFR 1910.269 (eCFR / OSHA.gov)
- OSHA: Electric-Arc Flash Hazards
- OSHA interpretation 2006-11-14: protection from electric-arc-flash hazards and NFPA 70E-2004
- U.S. Department of Labor news release 24-960-CHI (May 28, 2024)
- OSHA 4472: Protecting Employees from Electric-Arc Flash Hazards (PDF)
- OSHA: 1910.269 App. E (Protection From Flames and Electric Arcs)
- OSHA: 1910.335 (Electrical safeguards for personal protection)
Checked against the eCFR, OSHA.gov and dol.gov. Last reviewed 2026-10-27. This glossary is general information, not legal advice; OSHA State-Plan states (e.g. California, Michigan) may adopt stricter requirements.
A related free tool
The free JSA and Job Hazard Analysis Template covers a task related to Arc Flash. Read the rule above first, then use the tool for your own workplace.
Get the Binder in Order Before the Inspector Arrives. Are You Ready?
OSHA inspections come unannounced, apart from the few exceptions listed in 29 CFR 1903.6. Get the binder in order before the opening conference, not during it.
Serious Violation
$16,550