What 29 CFR 1926.416 requires (plain English)
29 CFR 1926.416 sets the general requirements for the protection of employees from electric shock in construction: work near electric power circuits, passageways and open spaces, load ratings, fuses, and cords and cables.
The core requirement is that no employer may permit an employee to work in such proximity to any part of an electric power circuit that the employee could contact it in the course of work, unless the employee is protected against electric shock by de-energizing the circuit and grounding it, or by guarding it effectively with insulation or other means. The two means are alternatives in the text, and a guard by location must actually prevent contact. Under 1926.417, controls that are to be deactivated during the course of work on energized or deenergized equipment or circuits are tagged; equipment or circuits that are deenergized are rendered inoperative and have tags attached at all points where they can be energized; tags identify plainly the equipment or circuits being worked on. 1910.147 does not apply to construction work. The GFCI is in 1926.404(b)(1); it is not a control for all live parts and not a permission to work live. The clearances for cranes and derricks are in 1926.1408, and other activities have their own provisions; 1926.416 sets no single clearance distance.
Paragraph (a) adds two duties. Before work begins, the employer must determine (by inquiry, direct observation, or instruments) whether any part of an energized electric power circuit is so located that work could bring a person, tool, or machine into physical or electrical contact with it, then post and maintain warning signs and advise employees of the location and hazards. The information given to employees includes the protective measures to be taken ((a)(3)). Where the exact location of underground electric powerlines is unknown, employees using jack-hammers, bars or other hand tools which may contact a line are provided with insulated protective gloves ((a)(2)); this does not allow digging without locating, and 1926.651(b) is separate. Barriers or other means of guarding ensure that the workspace for electrical equipment is not used as a passageway when energized parts are exposed ((b)(1)); working spaces and walkways are kept clear of cords ((b)(2)). Worn or frayed electric cords or cables are not used ((e)(1)); extension cords are not fastened with staples, hung from nails or suspended by wire ((e)(2)).