Skip to content

Approaching: Feb 1, 2027 — 300A Posting Begins. Get ready →

General Industry (29 CFR 1910)

Selection and Use of Work Practices

Verified vs OSHA sources · 2026-10-19

29 CFR 1910.333

29 CFR 1910.333 sets the safety-related work practices for electrical work: live parts must be de-energized before work unless de-energizing introduces additional or increased hazards or is infeasible (parts below 50 volts to ground need not be de-energized if there is no increased exposure to electrical burns or arc explosion), and de-energized fixed equipment must be locked out or tagged or both and verified de-energized by a qualified person.

29 CFR 1910.333 at a glance

What it requires
Safe electrical work practices: de-energize before working on or near live parts
The default rule
Live parts an employee may be exposed to must be de-energized before work (parts under 50 V to ground excepted if no added burn or arc-explosion exposure)
The exceptions
Energized work only if de-energizing adds hazards or is infeasible, and then by a qualified person
Approach distance
Unqualified persons and the longest conductive object they may contact stay at least 10 feet from unguarded, energized overhead lines of 50 kV or below to ground, plus 4 inches for every 10 kV over 50 kV (1910.333(c)(3)(i))
Max penalty (2026)
$16,550 per serious violation; $165,514 per willful
Common confusion
A qualified person tests the circuit to verify it is deenergized ((b)(2)(iv)), and the lock-and-tag default has the exceptions of (b)(2)(iii)

What 29 CFR 1910.333 requires (plain English)

29 CFR 1910.333 governs the safety-related work practices for electrical work in general industry: how workers must interact with electrical circuits to avoid shock, arc flash, arc blast, and electrocution. Where 1910.303 and 1910.305 address how systems are installed, 1910.333 addresses how people work on and around them.

The core requirement is that live parts to which an employee may be exposed must be de-energized before the employee works on or near them, unless the employer can demonstrate that de-energizing introduces additional or increased hazards (for example, interrupting life-support equipment) or is infeasible due to equipment design or operational limitations. Live parts that operate at less than 50 volts to ground need not be de-energized if there will be no increased exposure to electrical burns or to explosion due to electric arcs. Under 1910.333(b)(2) the circuits that energize fixed equipment must be locked out or tagged or both. The default is a lock and a tag on each disconnecting means ((b)(2)(iii)(A)). A tag may be used without a lock only where a lock cannot be applied or the employer can demonstrate that tagging gives an equivalent level of safety, and then it must be supplemented by at least one additional safety measure, such as removing an isolating circuit element, blocking a controlling switch or opening an extra disconnecting device ((C)-(D)). A lock may be used without a tag only when just one circuit or piece of equipment is de-energized, the lockout period does not extend beyond the work shift, and the employees exposed to re-energizing know the procedure ((E)). The employer must keep a written copy of these procedures available for inspection by employees and by OSHA (b)(2)(i); it may be a copy of paragraph (b). A qualified person then tests the circuit elements and parts employees will be exposed to with test equipment, verify that they are de-energized, and check for energized conditions from inadvertently induced voltage or backfeed ((b)(2)(iv)). If the circuit to be tested is over 600 volts nominal, the test equipment must be checked for proper operation immediately before and immediately after the test. Checking a tester on a known live source before and after every test ("live-dead-live") is a sound practice at any voltage, but the section makes it mandatory only above 600 volts. OSHA's letter of August 17, 2026 accepts a lock bearing a permanent, legible tag that prohibits unauthorized operation and unauthorized removal of the lock as meeting (b)(2)(iii)(A)-(B).

The standard distinguishes qualified and unqualified persons. Only qualified persons may work on or near exposed energized parts when energized work is justified ((c)(2)); under 1910.399, a qualified person has received training in and has demonstrated skills and knowledge in the construction and operation of the equipment and the hazards involved. Near overhead lines, an unqualified person working in an elevated position, with the longest conductive object the person may contact, stays at least 10 feet from any unguarded, energized overhead line of 50 kV or below to ground, plus 4 inches for every 10 kV over 50 kV, and on the ground brings no conductive object closer than those distances ((c)(3)(i)).

The regulatory text

“Live parts to which an employee may be exposed shall be deenergized before the employee works on or near them, unless the employer can demonstrate that deenergizing introduces additional or increased hazards or is infeasible due to equipment design or operational limitations.”
29 CFR 1910.333(a)(1)

Key facts about 29 CFR 1910.333

  • Default rule: de-energize live parts before working on or near them (1910.333(a)(1)).
  • Energized work is permitted only if the employer demonstrates that de-energizing adds hazards or is infeasible. Parts under 50 volts to ground need not be de-energized if there is no increased exposure to burns or arc explosion.
  • The employer must keep a written copy of the lockout and tagging procedures of (b)(2) available for inspection (it may be a copy of paragraph (b)).
  • De-energized fixed equipment must be locked out or tagged or both (lock and tag by default; tag alone or lock alone only under the (b)(2)(iii) conditions), and a qualified person tests to verify it is deenergized before work.
  • Only qualified persons may work on or near exposed energized parts when energized work is justified.
  • Unqualified persons, and the longest conductive object they may contact, stay at least 10 feet from unguarded, energized overhead lines of 50 kV or below to ground, plus 4 inches for every 10 kV over 50 kV (1910.333(c)(3)(i)).
  • Qualified persons must use appropriate insulated tools, PPE, and shielding for energized work.

Scope: who 29 CFR 1910.333 applies to

Regulatory framework
General Industry (29 CFR 1910)
Citation reference
29 CFR 1910.333
Enforcement status
In force and enforced
Jurisdiction
Federal OSHA (29 State-Plan jurisdictions may be stricter)

State-Plan states (e.g. California, Washington, Michigan) operate OSHA-approved programs that must be at least as effective as federal OSHA and frequently impose higher penalties or additional requirements.

Key requirements of 29 CFR 1910.333

#What the section requires or covers
1De-energize equipment before working on it when possible
2Use lockout/tagout for de-energized work
3Maintain safe approach distances for energized work
4Use appropriate insulated tools and PPE
5Test circuits before touching

Summarized from the text of 29 CFR 1910.333.

Common Electrical Work Practice Selection violations

Deficiencies OSHA cites under 29 CFR 1910.333 include the ones below, in no particular order. Each serious item carries up to $16,550 (2026).

  • Working on or near live parts without de-energizing, absent a demonstrable justification (1910.333(a)(1)).
  • De-energized fixed equipment not locked out or tagged, a lock-only or tag-only practice outside the (b)(2)(iii) conditions, no verification by a qualified person with test equipment, or no written procedure available (1910.333(b)(2)(i), (iii), (iv)).
  • Unqualified persons working on or too close to exposed energized parts (1910.333(c)(2)/(3)).
  • Failure to maintain minimum approach distances from overhead power lines (1910.333(c)(3)).
  • Energized work performed without the protective means the section calls for (1910.333(c)(2)).

Deenergized is verified by a qualified person

1910.333(b)(2) has circuits locked out or tagged or both (a lock and a tag by default, with the (b)(2)(iii) exceptions), and (b)(2)(iv) has a qualified person test the circuit elements and parts with test equipment, verify that they are deenergized, and check for energized conditions from inadvertently induced voltage or backfeed. (b)(2)(iv)(B) makes the check of the test equipment immediately before and after the test mandatory only when the circuit tested is over 600 volts nominal; at lower voltages the live-dead-live sequence is a practice, not a text requirement. Only qualified persons work on or near exposed energized parts; unqualified persons keep the distances of (c)(3).

What OSHA inspectors look for

A compliance officer checks whether workers de-energize and verify circuits before working on them (test-before-touch), whether lockout/tagout is applied, and whether any justified live work uses insulated tools, PPE, and trained qualified persons.

Example: how a violation is cited

Hypothetical case: an electrician opens a panel to replace a breaker without locking out the circuit or verifying that it is deenergized. 1910.333(b)(2) has the circuits locked out or tagged or both, and (b)(2)(iv) has a qualified person verify with test equipment that they are deenergized. A serious violation carries a penalty of up to $16,550.

Illustrative example, not a specific OSHA case.

Electrical Work Practice Selection compliance checklist

Each item is a requirement of 29 CFR 1910.333 that OSHA may verify during an inspection.

  • De-energize live parts before work unless energized work is demonstrably justified.
  • Keep a written copy of the lockout and tagging procedures available for inspection (1910.333(b)(2)(i)); lock and tag each disconnecting means (or use the tag-only or lock-only exception only on its conditions), then have a qualified person test to verify the circuit is dead; check the tester before and after if the circuit is over 600 V, and as good practice at any voltage.
  • Assign only qualified persons to work on or near exposed energized parts.
  • Keep unqualified persons and their conductive objects at least 10 feet from unguarded, energized overhead lines of 50 kV or below to ground, plus 4 inches for every 10 kV over 50 kV (1910.333(c)(3)(i)).
  • Provide insulated tools, appropriate PPE, and shielding for any justified energized work.
  • Where work stays on energized parts, the employer demonstrates the additional or increased hazards or the infeasibility ((a)(1)); the text sets no universal justification form.

2026 penalties for 29 CFR 1910.333

Maximums set by 29 CFR 1903.15(d). 2026 maximums unchanged from 2025 (no CPI adjustment; OMB M-26-11), so not an increase; the serious and repeat policy minimums were revised with FOM chapter 6 (OSHA memo of May 21, 2026). The 2025 OSHA penalty levels remain in effect for 2026; OSHA made no inflation adjustment for 2026. 29 CFR 1903.15 identifies January 15, 2025 as the effective reference for these amounts, while OSHA's public penalties page currently references penalties assessed after Jan. 15, 2026.

Violation typeMinimumMaximumWhen it applies
Serious$1,085$16,550Death or serious physical harm could result, and the employer knew or could have known (29 U.S.C. 666(k)).
Other-Than-Serious$0$16,550Relates to safety/health but unlikely to cause death or serious harm.
Willful$11,823$165,514Intentional, knowing, or voluntary disregard of the requirement.
Repeated$4,256$165,514A substantially similar violation cited within the last 5 years.
Failure to AbateNone$16,550/dayup to $16,550 per day; the total is normally capped at 30 times the daily amount (FOM Ch.6)

Serious violations reach $16,550 and willful or repeat violations $165,514.

Maximums and the willful minimum are set by 29 CFR 1903.15(d); the serious and repeated minimums are OSHA policy floors from its annual penalty adjustment memo. OSHA applies gravity-based and size, good-faith and history reductions (FOM CPL 02-00-164 Ch.6). Estimates only, not legal advice.

The business case for Electrical Work Practice Selection compliance

1910.333(a)(1) has live parts to which an employee may be exposed deenergized before the employee works on or near them, unless the employer can demonstrate that deenergizing introduces additional or increased hazards or is infeasible due to equipment design or operational limitations; (b)(2)(iv) has a qualified person test the circuit elements and parts and verify that they are deenergized.

Free compliance tools for 29 CFR 1910.333

State plans and their penalty rules

States listed by the volume of their federal construction citations, not by this standard. Penalties and enforcement vary by state. State-Plan states may impose higher penalties and additional requirements beyond federal 29 CFR 1910.333.

Frequently asked questions about 29 CFR 1910.333

Does OSHA require electrical circuits to be de-energized before work?

Yes, as the default. Under 1910.333(a)(1), live parts to which an employee may be exposed must be de-energized before the employee works on or near them, unless the employer can demonstrate that de-energizing would introduce additional or increased hazards or is infeasible due to equipment design or operational limitations. Live parts that operate at less than 50 volts to ground need not be de-energized if there will be no increased exposure to electrical burns or to explosion due to electric arcs. When fixed equipment is de-energized, its circuits must also be locked out or tagged or both under (b)(2) (a lock and a tag unless the tag-only or lock-only conditions are met), and a qualified person must test them to verify they are de-energized before work begins.

When is it acceptable to work on energized electrical equipment?

When the employer can demonstrate that de-energizing would introduce additional or increased hazards (such as cutting power to life-support equipment) or is infeasible due to equipment design or operational limitations (1910.333(a)(1)). Only a qualified person then performs the work, with the insulated tools, personal protective equipment and precautionary techniques of (c)(2) and 1910.335.

What is the difference between a qualified and unqualified person?

Under 1910.399, a qualified person has received training in and has demonstrated skills and knowledge in the construction and operation of electric equipment and installations and the hazards involved, and can be qualified for some equipment and not for other equipment. Only qualified persons may work on or near exposed energized parts. An unqualified person near unguarded, energized overhead lines keeps at least 10 feet from lines of 50 kV or below to ground, plus 4 inches for every 10 kV over 50 kV (1910.333(c)(3)(i)).

What is a live-dead-live test?

It is a common way to verify a circuit is truly de-energized. You first confirm your voltage tester works on a known live (energized) source, then test the circuit you have locked out (it should read dead), then confirm your tester still works on the known live source again. The sequence shows the tester was working when it read dead. Section 1910.333(b)(2)(iv)(B) requires a qualified person to test the circuit elements and parts, including for induced voltage and backfeed, and makes the before-and-after check of the test equipment mandatory when the circuit tested is over 600 volts nominal; at lower voltages the full live-dead-live sequence is good practice rather than a text requirement.

Regulatory history of 29 CFR 1910.333

1910.333 was published with the electrical safety-related work practices rule at 55 FR 32016 (August 6, 1990), according to the eCFR source note.

Related glossary terms

Key terms that appear in 29 CFR 1910.333, each with a full plain-English explainer.

Get the Binder in Order Before the Inspector Arrives. Are You Ready?

OSHA inspections come unannounced, apart from the few exceptions listed in 29 CFR 1903.6. Get the binder in order before the opening conference, not during it.

Serious Violation

$16,550

per violation (max)

HazComFast Pro

$199/mo

10 jobsites, unlimited chemicals, unlimited workers

New sign-ups are paused. The free tools below need no account, and customers can log in as usual.

Your account keeps working as usual. Cancel anytime.