Construction term · Glossary
GFCI (Ground-Fault Circuit Interrupter)
Verified vs OSHA sources · 2026-10-27
A protective device that compares the current going to and returning from equipment along the circuit conductors and interrupts the current when the difference is approximately 5 milliamperes, which is current leaking to ground, for example through a person. OSHA's construction eTool describes it as a fast-acting circuit breaker designed to shut off power in a ground fault within as little as 1/40 of a second. On construction sites, 1926.404(b)(1)(i) has the employer use either GFCIs, as specified in (b)(1)(ii), or an assured equipment grounding conductor program, as specified in (b)(1)(iii), to protect employees. The GFCI option covers 120-volt, single-phase, 15- and 20-ampere receptacle outlets that are not part of the permanent wiring of the building or structure and are in use by employees, with an exception for certain generator receptacles. OSHA's interpretation letters say the duty to provide ground-fault protection has no voltage limit.
Also known as: ground fault circuit interrupter, ground-fault interrupter
On this page
GFCI (Ground-Fault Circuit Interrupter) at a glance
- A GFCI compares the current going to and returning from equipment, and it interrupts the current when the difference is approximately 5 milliamperes (OSHA construction eTool). OSHA describes it as a fast-acting circuit breaker designed to shut off power in a ground fault within as little as 1/40 of a second.
- Ground-fault protection on construction sites is GFCIs or an assured equipment grounding conductor program (AEGCP): the employer uses either (1926.404(b)(1)(i)). The GFCI option applies to 120-volt, single-phase, 15- and 20-ampere receptacle outlets that are not part of the permanent wiring of the building or structure and are in use by employees ((b)(1)(ii)). The program covers all cord sets, receptacles not part of the building or structure, and equipment connected by cord and plug that are available for use or used by employees ((b)(1)(iii)).
- OSHA's interpretation letters of May 15, 2002 and February 7, 2005 say the duty to provide ground-fault protection in (b)(1)(i) has no voltage limit, so outlets above 120 volts are protected by the program or by a GFCI designed for that voltage.
- A GFCI addresses ground faults. OSHA's eTool says it will not protect from line contact hazards: a person holding two hot wires, a hot and a neutral wire in each hand, or contacting an overhead power line. It also says that if the grounding conductor is not intact or of low impedance, the GFCI may not trip until a person provides a path, and the person will receive a shock that the GFCI should end quickly enough not to be harmful.
- An OSHA interpretation of December 21, 1999 (on a general industry grounding standard) says a GFCI can prevent an electrocution but cannot by itself prevent an initial electric shock before it interrupts the circuit, and that an initial shock could lead to indirect or secondary injuries such as bruises, fractures or death from collisions or falls. For construction, 1926.404(b)(1)(i) says its requirements are in addition to any other requirements for equipment grounding conductors.
In plain English
The device that shuts power off when electricity starts leaking to ground, for example through a person. It reacts in a fraction of a second. It does not protect against touching two live wires or an overhead power line, and an initial shock can still happen.
What the rule says
“All 120-volt, single-phase, 15- and 20-ampere receptacle outlets on construction sites, which are not a part of the permanent wiring of the building or structure and which are in use by employees, shall have approved ground-fault circuit interrupters for personnel protection.”
In context
A concept governed primarily by OSHA's construction standards, 29 CFR Part 1926 — the rules that apply on jobsites rather than the general-industry 1910 set.
Where this is written in OSHA's rules
- 29 CFR 1926.404(b)(1)Read on eCFR / OSHA.gov
- 29 CFR 1926.404(b)(1)(ii)Read on eCFR / OSHA.gov
Example
In this invented illustration, a worker using a drill on a damp slab nicks the cord, and current starts leaking toward ground. A properly installed GFCI on the temporary receptacle senses the imbalance and interrupts the current in a fraction of a second. The worker can still feel a shock before it does, and OSHA notes that an initial shock can lead to secondary injuries such as a fall. The GFCI does not protect against touching two energized conductors or an overhead power line.
Why it matters
OSHA's eTool says a ground fault can send current through the user, resulting in serious injuries or death, and that the GFCI protects against what it calls the most common form of electrical shock hazard, the ground fault, as well as against fires, overheating and destruction of wire insulation. A GFCI is not a complete answer: it does not protect against line contact, and an initial shock can still cause secondary injuries.
GFCI vs. overcurrent circuit breaker
In OSHA's description a GFCI is itself a fast-acting circuit breaker, and it trips on a ground-fault imbalance of approximately 5 milliamperes between the current going and returning. An overcurrent device protects the circuit against current above its setting, usually 15 or 20 amperes (OSHA interpretation of December 21, 1999). The two work at very different currents, and a GFCI is one of the two ground-fault protection options of 1926.404(b)(1).
Ground-fault protection options on construction sites (1926.404(b)(1))
| Option | How it works |
|---|---|
| GFCIs ((b)(1)(ii)) | Approved GFCIs on 120-volt, single-phase, 15- and 20-ampere receptacle outlets that are not part of the permanent wiring and are in use by employees; a GFCI trips on a ground-fault imbalance of approximately 5 milliamperes |
| Assured equipment grounding conductor program ((b)(1)(iii)) | A written program with designated competent persons, a visual inspection of cord sets and cord-and-plug equipment before each day's use, tests of equipment grounding conductors and receptacles on a set schedule, and a test record |
GFCI (Ground-Fault Circuit Interrupter): frequently asked questions
- What is GFCI (Ground-Fault Circuit Interrupter)?
- A protective device that compares the current going to and returning from equipment along the circuit conductors and interrupts the current when the difference is approximately 5 milliamperes, which is current leaking to ground, for example through a person. OSHA's construction eTool describes it as a fast-acting circuit breaker designed to shut off power in a ground fault within as little as 1/40 of a second. On construction sites, 1926.404(b)(1)(i) has the employer use either GFCIs, as specified in (b)(1)(ii), or an assured equipment grounding conductor program, as specified in (b)(1)(iii), to protect employees. The GFCI option covers 120-volt, single-phase, 15- and 20-ampere receptacle outlets that are not part of the permanent wiring of the building or structure and are in use by employees, with an exception for certain generator receptacles. OSHA's interpretation letters say the duty to provide ground-fault protection has no voltage limit.
- What does a GFCI do?
- It compares the current going to and returning from equipment, and when the difference is approximately 5 milliamperes it interrupts the current, in a ground fault within as little as 1/40 of a second according to OSHA's construction eTool. It does not protect against line contact, such as touching two energized conductors or an overhead power line, and an initial shock can still occur before it interrupts the circuit.
- Are GFCIs needed on construction sites?
- The employer uses either GFCIs or an assured equipment grounding conductor program to protect employees on construction sites (29 CFR 1926.404(b)(1)(i)). The GFCI option applies to 120-volt, single-phase, 15- and 20-ampere receptacle outlets that are not part of the permanent wiring of the building or structure and are in use by employees ((b)(1)(ii)), with a narrow exception for receptacles on certain portable or vehicle-mounted generators. The duty to provide ground-fault protection has no voltage limit (OSHA interpretation letters of 2002 and 2005), and it is in addition to any other requirements for equipment grounding conductors.
- What's the difference between a GFCI and a circuit breaker?
- OSHA describes a GFCI as a fast-acting circuit breaker designed to shut off power in a ground fault. It trips on an imbalance of approximately 5 milliamperes between the current going and returning, while an overcurrent device trips when the current exceeds its setting, usually 15 or 20 amperes (OSHA interpretation of December 21, 1999).
Related terms
Governing OSHA standards
More Construction terms
The part of Title 29 of the Code of Federal Regulations that contains OSHA's General Industry standards, the default rulebook for most American workplaces (manufacturing, warehousing, healthcare, etc.) that are not covered by the construction, maritime or agriculture standards. It includes core rules such as Hazard Communication (1910.1200) and the air contaminant limits (1910.1000). Construction work is covered by Part 1926, which 1910.12(a) adopts as standards for every employee engaged in construction work, and some requirements are the same in both parts: 1926.59 says the HazCom requirements for construction are identical to those of 1910.1200.
29 CFR 1926The part of Title 29 of the Code of Federal Regulations that contains OSHA's Construction standards, the “Safety and Health Regulations for Construction.” It applies to construction work, which 1910.12(b) defines as work for construction, alteration, and/or repair, including painting and decorating, with construction-specific rules for fall protection (Subpart M), scaffolds (Subpart L), excavations (Subpart P), electrical (Subpart K) and more. OSHA decides by the activity being performed and not only by the employer's general business. Some general-industry (1910) standards apply to construction because 1926 adopts them (HazCom through 1926.59) or because 1910 identifies them as applicable to construction; OSHA's Field Operations Manual says a hazard in construction work that no specific 1926 standard covers is not normally cited under 1910 unless that standard has been identified as applicable to construction.
Anchor PointThe secure attachment point a personal fall arrest system (PFAS) ties off to. Under 29 CFR 1926.502(d)(15), anchorages used for attachment of personal fall arrest equipment are independent of any anchorage being used to support or suspend platforms and capable of supporting 5,000 pounds or more pounds per employee attached, or are designed, installed and used as part of a complete personal fall arrest system that maintains a safety factor of two or more, under the supervision of a qualified person.
Atmospheric TestingMeasuring the air in a confined space with an instrument before and during entry, as part of the evaluation of a permit space (1926.1204(e)) or of the alternate procedures for a space whose only hazard is atmospheric and is controlled by forced air ventilation, which call for a calibrated direct-reading instrument (1926.1203(e)(2)(iii)). Testing is done in a set order: first oxygen, then combustible gases and vapors, then toxic gases and vapors (1926.1204(e)(3)). Whether an atmosphere is hazardous is defined in 1926.1202: flammable gas, vapor or mist in excess of 10 percent of its lower flammable limit; oxygen below 19.5 percent or above 23.5 percent; a substance above its dose or permissible exposure limit; or any other atmospheric condition that is immediately dangerous to life or health. Readings within those ranges are one condition of an entry and are not enough on their own: the classification of the space, the permit, isolation, ventilation, an attendant and rescue also apply.
BenchingA method of protecting employees from cave-ins by excavating the sides of an excavation to form one or a series of horizontal levels or steps, usually with vertical or near-vertical surfaces between levels (1926.650(b)). Benching is one of the sloping and benching systems whose slopes and configurations are selected under 1926.652(b), by one of four options: a slope not steeper than 1½H:1V (Option 1), Appendices A and B (Option 2), other tabulated data (Option 3), or a design approved by a registered professional engineer (Option 4). Appendix B to Subpart P lists benched configurations for Type A and Type B soil in excavations 20 feet or less in depth, and it lists no benched configuration for Type C soil.
Competent Person (Excavation)In OSHA's excavation standard (Subpart P), a competent person is one who is capable of identifying existing and predictable hazards in the surroundings, or working conditions which are unsanitary, hazardous, or dangerous to employees, and who has authorization to take prompt corrective measures to eliminate them (1926.650(b)). The competent person inspects excavations, the adjacent areas and protective systems before the start of work, as needed throughout the shift (not a continuous watch), and after every rainstorm or other hazard increasing occurrence, when employee exposure can be reasonably anticipated (1926.651(k)(1)). Exposed employees are removed from the hazardous area when the competent person finds evidence of a possible cave-in or another hazardous condition, until the necessary precautions have been taken (1926.651(k)(2)). When Appendix A to Subpart P applies, a competent person also classifies each soil and rock deposit as stable rock, Type A, Type B or Type C, based on a visual and a manual analysis.
Confined SpaceA space that is large enough and so configured that an employee can bodily enter it, has limited or restricted means for entry and exit, and is not designed for continuous employee occupancy (1926.1202). It is a permit space (also called a PRCS) if it has one or more of these characteristics: it contains or has a potential to contain a hazardous atmosphere; it contains a material that has the potential for engulfing an entrant; it has an internal configuration such that an entrant could be trapped or asphyxiated by inwardly converging walls or by a floor that slopes downward and tapers to a smaller cross-section; or it contains any other recognized serious safety or health hazard. A competent person identifies the confined spaces and the permit spaces before work begins (1926.1203(a)). An employer that decides to have employees enter a permit space has a written permit space program (1926.1203(d)), or uses the alternate procedures of 1926.1203(e) when their conditions are met, and a permit space can be reclassified as a non-permit confined space only when a competent person determines that the requirements of 1926.1203(g) are met.
Controlling EmployerUnder OSHA's Multi-Employer Citation Policy (CPL 02-00-124), a controlling employer is an employer who has general supervisory authority over the worksite, including the power to correct safety and health violations itself or to have others correct them. Control can be established by contract or, in the absence of explicit contractual provisions, by the exercise of control in practice. In the policy's examples the controlling employer is a general contractor or a construction manager, and an architect or engineer is one only if the breadth of its involvement is sufficient. The policy works in two steps: first the employer's role (creating, exposing, correcting or controlling), then whether its actions were sufficient for that role. A controlling employer has a duty to exercise reasonable care to prevent and detect violations on the site, and it can be cited for another employer's violation of an OSHA standard even when none of its own employees are exposed, but only when it did not meet that duty.
Sources & verification
- 29 CFR 1926.404(b)(1) (eCFR / OSHA.gov)
- 29 CFR 1926.404(b)(1)(ii) (eCFR / OSHA.gov)
- OSHA: Construction eTool, Ground-Fault Circuit Interrupters (GFCI)
- eCFR: 29 CFR 1926.404, Wiring design and protection
- OSHA: Interpretation letter of May 15, 2002, ground fault protection for 120-volt and 240-volt circuits
- OSHA: Interpretation letter of February 7, 2005, 1926.404(b)(1) and 208-volt branch circuits
- OSHA: Interpretation of December 21, 1999, grounding of equipment connected by cord and plug
Checked against the eCFR and OSHA.gov. Last reviewed 2026-10-27. This glossary is general information, not legal advice; OSHA State-Plan states (e.g. California, Michigan) may adopt stricter requirements.
Free OSHA and HazCom tools
HazComFast offers free OSHA and HazCom tools for related workplace tasks.
Get the Binder in Order Before the Inspector Arrives. Are You Ready?
OSHA inspections come unannounced, apart from the few exceptions listed in 29 CFR 1903.6. Get the binder in order before the opening conference, not during it.