Construction (29 CFR 1926)

Wiring Design and Protection (Construction)

Verified vs OSHA sources · 2026-10-19

29 CFR 1926.404

29 CFR 1926.404 governs wiring design and protection on construction sites: employers must protect workers using electricity through either ground-fault circuit interrupters (GFCIs) on receptacles or a written assured equipment grounding conductor program, in addition to the other equipment grounding conductor requirements. Receptacles on a small portable generator (two-wire, single-phase, not more than 5 kW, with conductors insulated from the frame) are excepted from the GFCI rule. The section also covers other wiring-design topics such as outlet devices and outside conductors.

29 CFR 1926.404 at a glance

What it covers
Conductor identification and polarity (a), branch circuits and ground-fault protection (b), outside conductors and lamps (c), services (d), overcurrent protection (e), grounding (f)
GFCI rule
All 120-volt, single-phase, 15- and 20-amp receptacles not part of the permanent wiring and used by employees must have GFCIs; receptacles on a two-wire, single-phase portable or vehicle-mounted generator of not more than 5 kW with circuit conductors insulated from the frame are excepted (1926.404(b)(1)(ii))
The alternative
A written Assured Equipment Grounding Conductor Program may be used instead: competent person designated, daily inspections, tests before first use, after repair or suspected damage and every 3 months (6 for fixed items not exposed to damage), records kept (1926.404(b)(1)(iii))
Other parts of the section
Identification and polarity of conductors (a), outlet devices (b)(2), outside conductors, services, overcurrent protection and grounding in the other paragraphs; the program does not replace the other equipment grounding conductor requirements
Max penalty (2026)
$16,550 per serious violation; $165,514 per willful
Common confusion
The restriction of (b)(1)(ii) to receptacles not part of the permanent wiring does not exclude the other parts of 1926.404

What 29 CFR 1926.404 requires (plain English)

29 CFR 1926.404 governs wiring design and protection for construction: identification and polarity of conductors, branch circuits and ground-fault protection, outside conductors and lamps, services, overcurrent protection and grounding.

The core requirement gives the employer two options. Under the first, all 120-volt, single-phase, 15- and 20-ampere receptacle outlets on the site that are not part of the permanent wiring and are in use by employees must have approved ground-fault circuit interrupters (GFCIs) for personnel protection. The OSHA eTool describes the GFCI as comparing the current going to and returning from equipment along the circuit conductors and interrupting the current when the two differ by approximately 5 milliamperes, within as little as 1/40 of a second, if it is properly installed and maintained; it does not protect from line contact hazards, such as a person holding two "hot" wires, a hot and a neutral wire in each hand, or contacting an overhead power line. Receptacles on a two-wire, single-phase portable or vehicle-mounted generator rated not more than 5 kW, whose circuit conductors are insulated from the generator frame and all other grounded surfaces, need not have GFCIs. Under the second option, the employer may instead establish and implement a written Assured Equipment Grounding Conductor Program. The program has a written description, including the specific procedures adopted by the employer, available at the jobsite for inspection and copying, with one or more competent persons designated to implement it ((b)(1)(iii)(A)-(B)); a program is not a document alone: the controls and the tests must actually be performed. Each cord set, attachment cap, plug and receptacle of cord sets, and any equipment connected by cord and plug (except cord sets and receptacles that are fixed and not exposed to damage) is visually inspected before each day's use, and equipment found damaged or defective is not used until repaired ((C)); equipment grounding conductors are tested for continuity and each receptacle and plug is tested for correct attachment ((D)); tests are made before first use, before return to service after repair, after any incident that could reasonably be suspected of causing damage, and at intervals not exceeding 3 months (6 months for cord sets and receptacles that are fixed and not exposed to damage) ((E)); and a record of the tests is kept by logs, color coding or other effective means and available at the jobsite ((G)).

Beyond ground-fault protection, 1926.404 covers wiring design more broadly: identification and polarity of conductors, branch-circuit outlet devices rated for the load ((b)(2)), outside conductors and lamps ((c)), services, overcurrent protection and grounding in its other paragraphs. Equipment grounding conductors must be properly connected, and this section's ground-fault rules are in addition to the other equipment grounding conductor requirements ((b)(1)(i)). Grounding has exceptions with conditions: the frame of a portable generator need not be grounded and may serve as the grounding electrode for a system supplied by the generator when it supplies only equipment mounted on it or cord- and plug-connected equipment through receptacles mounted on it, with the metal parts and grounding terminals bonded to its frame ((f)(3)(i)); tools likely to be used in wet or conductive locations need not be grounded if supplied through an isolating transformer with an ungrounded secondary of not over 50 volts, and listed or labeled portable tools protected by a system of double insulation, or its equivalent, need not be grounded and are distinctively marked ((f)(7)(iv)(C)(6)). Conductors and equipment are protected from overcurrent in accordance with their ability to safely conduct current ((e)(1)(i)); means are provided to disconnect all conductors in a building or other structure from the service-entrance conductors ((d)(1)(i)); open outside conductors keep the clearances of (c)(1)(ii), such as 10 feet above finished grade; no grounded conductor is attached to any terminal or lead so as to reverse designated polarity ((a)(2)). 1926.405, 1926.416, 1926.417 and 1926.302 have their own requirements, and general industry provisions do not replace them.

The regulatory text

“All 120-volt, single-phase, 15- and 20-ampere receptacle outlets on construction sites, which are not a part of the permanent wiring of the building or structure and which are in use by employees, shall have approved ground-fault circuit interrupters for personnel protection.”
29 CFR 1926.404(b)(1)(ii)

Key facts about 29 CFR 1926.404

  • All 120V, single-phase, 15- and 20-amp receptacles that are not part of the permanent wiring and are in use by employees must have GFCIs (1926.404(b)(1)(ii)), except receptacles on a two-wire, single-phase portable or vehicle-mounted generator of not more than 5 kW whose circuit conductors are insulated from the frame and other grounded surfaces.
  • The OSHA eTool describes a GFCI interrupting the current when the current going and returning differ by approximately 5 milliamperes, within as little as 1/40 of a second, if properly installed and maintained; it does not protect from line contact hazards, and its test button does not replace the tests of the assured equipment grounding conductor program.
  • Alternative: a written Assured Equipment Grounding Conductor Program, available at the jobsite, with one or more competent persons designated to implement it, visual inspection before each day's use, and tests logged by log, color coding or another effective means (1926.404(b)(1)(iii)(A)-(C), (G)).
  • Program tests: before first use, before return to service after repair, after any incident that could reasonably be suspected of causing damage (for example, a cord set run over), and at intervals not exceeding 3 months (6 months for cord sets and receptacles that are fixed and not exposed to damage) (1926.404(b)(1)(iii)(E)).
  • Equipment grounding conductors must be tested for continuity, and each receptacle and attachment cap or plug tested for correct attachment of the grounding conductor (1926.404(b)(1)(iii)(D)); the employer may not make available any equipment that has not met the program (F).
  • The GFCI rule covers receptacles that are not part of the permanent wiring of the building or structure and are in use by employees; the section as a whole also covers other wiring-design topics (1926.404).
  • The program does not replace all grounding: it is in addition to any other requirements for equipment grounding conductors (1926.404(b)(1)(i)).

Scope: who 29 CFR 1926.404 applies to

Regulatory framework
Construction (29 CFR 1926)
Citation reference
29 CFR 1926.404
Enforcement status
In force and enforced
Jurisdiction
Federal OSHA (29 State-Plan jurisdictions may be stricter)

State-Plan states (e.g. California, Washington, Michigan) operate OSHA-approved programs that must be at least as effective as federal OSHA and frequently impose higher penalties or additional requirements.

Key requirements of 29 CFR 1926.404

#What the section requires or covers
1Use GFCI on all 120V, 15A/20A receptacles
2Or implement assured equipment grounding conductor program
3Ground all electrical systems per requirements
4Protect wiring from physical damage

Summarized from the text of 29 CFR 1926.404.

Common Wiring Design (Construction) violations

Deficiencies OSHA cites under 29 CFR 1926.404 include the ones below, in no particular order. Each serious item carries up to $16,550 (2026).

  • Temporary 120V 15-/20-amp receptacles used by employees without GFCI protection (1926.404(b)(1)(ii)).
  • No written Assured Equipment Grounding Conductor Program where GFCIs are not used, or a program without designated competent persons, daily inspection, the required tests and intervals, or the test record (1926.404(b)(1)(iii)).
  • Equipment grounding conductors not continuous or not properly connected (1926.404(f)).
  • Equipment or cord sets that have not met the assured equipment grounding conductor program made available or used by employees (1926.404(b)(1)(iii)(F)); equipment found damaged or defective used before it is repaired ((C)).

Ground-fault protection, breakers and the rest of the section

An ordinary breaker or fuse protects the wiring from overload and short circuit; a ground-fault circuit interrupter detects a small imbalance of about 5 milliamps between the current leaving and returning. The GFCI rule of (b)(1)(ii) concerns 120-volt, single-phase, 15- and 20-ampere receptacle outlets that are not part of the permanent wiring and are in use by employees, with a reservation for a two-wire, single-phase portable or vehicle-mounted generator of not more than 5 kW whose circuit conductors are insulated from the frame. The restriction of the receptacles in (b)(1)(ii) does not exclude the other parts of 1926.404: polarity and conductors, outside conductors, services, overcurrent protection and grounding. The test button of a GFCI is a useful practice at the manufacturer's frequency, and it does not replace the tests of the assured equipment grounding conductor program.

What OSHA inspectors look for

A compliance officer checks whether temporary receptacles have GFCI protection or the site runs an assured grounding program with documented tests, looks for missing grounds and improper overcurrent protection, and inspects extension cords. The GFCI rule of (b)(1)(ii) and the program of (b)(1)(iii) concern the receptacles and the cord sets they name, not all of 1926.404.

Example: how a violation is cited

Hypothetical case: a crew runs power tools from 120-volt, single-phase, 15-ampere receptacle outlets that are not part of the permanent wiring and are in use by employees, with neither GFCIs nor an assured equipment grounding conductor program. 1926.404(b)(1)(i) has the employer use either GFCIs or the program to protect employees on construction sites. A serious violation carries a penalty of up to $16,550.

Illustrative example, not a specific OSHA case.

Wiring Design (Construction) compliance checklist

Each item is a requirement of 29 CFR 1926.404 that OSHA may verify during an inspection.

  • Provide approved GFCIs on all 120V, single-phase, 15-/20-amp receptacles that are not part of the permanent wiring and are in use by employees; receptacles on a two-wire, single-phase portable or vehicle-mounted generator rated not more than 5 kW, with circuit conductors insulated from the frame and all other grounded surfaces, need not be protected (1926.404(b)(1)(ii)); or
  • Implement a written Assured Equipment Grounding Conductor Program: designate competent persons, inspect before each day's use, test before first use, after repairs, after suspected damage and at least every 3 months (6 for fixed items not exposed to damage), and keep the test record at the jobsite (1926.404(b)(1)(iii)).
  • Test equipment grounding conductors for continuity and each receptacle and attachment cap or plug for correct attachment of the equipment grounding conductor (1926.404(b)(1)(iii)(D)).
  • Test GFCIs with their test button at the frequency the manufacturer gives; 1926.404 sets no test interval for GFCIs, and the button test does not replace the tests of the assured equipment grounding conductor program.
  • Protect conductors and equipment from overcurrent in accordance with their ability to safely conduct current (1926.404(e)(1)(i)).
  • Do not attach a grounded conductor to any terminal or lead so as to reverse designated polarity (1926.404(a)(2)).

2026 penalties for 29 CFR 1926.404

Maximums set by 29 CFR 1903.15(d). 2026 maximums unchanged from 2025 (no CPI adjustment; OMB M-26-11), so not an increase; the serious and repeat policy minimums were revised with FOM chapter 6 (OSHA memo of May 21, 2026). The 2025 OSHA penalty levels remain in effect for 2026; OSHA made no inflation adjustment for 2026. 29 CFR 1903.15 identifies January 15, 2025 as the effective reference for these amounts, while OSHA's public penalties page currently references penalties assessed after Jan. 15, 2026.

Violation typeMinimumMaximumWhen it applies
Serious$1,085$16,550Death or serious physical harm could result, and the employer knew or could have known (29 U.S.C. 666(k)).
Other-Than-Serious$0$16,550Relates to safety/health but unlikely to cause death or serious harm.
Willful$11,823$165,514Intentional, knowing, or voluntary disregard of the requirement.
Repeated$4,256$165,514A substantially similar violation cited within the last 5 years.
Failure to AbateNone$16,550/dayup to $16,550 per day; the total is normally capped at 30 times the daily amount (FOM Ch.6)

Serious violations reach $16,550 and willful or repeat violations $165,514.

Maximums and the willful minimum are set by 29 CFR 1903.15(d); the serious and repeated minimums are OSHA policy floors from its annual penalty adjustment memo. OSHA applies gravity-based and size, good-faith and history reductions (FOM CPL 02-00-164 Ch.6). Estimates only, not legal advice.

The business case for Wiring Design (Construction) compliance

1926.404(b)(1)(i) has the employer use either ground fault circuit interrupters as specified in (b)(1)(ii) or an assured equipment grounding conductor program as specified in (b)(1)(iii) to protect employees on construction sites; these requirements are in addition to any other requirements for equipment grounding conductors.

Free compliance tools for 29 CFR 1926.404

State plans and their penalty rules

States listed by the volume of their federal construction citations, not by this standard. Penalties and enforcement vary by state. State-Plan states may impose higher penalties and additional requirements beyond federal 29 CFR 1926.404.

State pages for 29 CFR 1926.404

Frequently asked questions about 29 CFR 1926.404

Are GFCIs required on construction sites?

Under 1926.404(b)(1)(i), the employer uses either GFCIs or an assured equipment grounding conductor program. Under 1926.404(b)(1)(ii), all 120-volt, single-phase, 15- and 20-ampere receptacle outlets that are not part of the permanent wiring and are in use by employees must have approved ground-fault circuit interrupters (GFCIs) for personnel protection. Receptacles on a two-wire, single-phase portable or vehicle-mounted generator rated not more than 5 kW, with circuit conductors insulated from the generator frame and all other grounded surfaces, are excepted. The alternative (1926.404(b)(1)(iii)) is a written Assured Equipment Grounding Conductor Program with competent persons designated to implement it, visual inspection before each day's use, and periodic electrical tests.

What is the difference between a GFCI and a circuit breaker?

A circuit breaker or fuse is an overcurrent device: under 1926.404(e)(1)(i), conductors and equipment are protected from overcurrent in accordance with their ability to safely conduct current. A GFCI compares the current going to and returning from equipment along the circuit conductors and interrupts the current when the two differ by approximately 5 milliamperes, within as little as 1/40 of a second, if properly installed and maintained (OSHA eTool). The eTool adds that a GFCI does not protect from line contact hazards, such as a person holding two "hot" wires or a hot and a neutral wire in each hand.

What is an Assured Equipment Grounding Conductor Program?

It is the alternative to GFCIs allowed under 1926.404(b)(1)(iii). The employer establishes a written program, available at the jobsite, and designates one or more competent persons to implement it. Cords and equipment are visually inspected before each day's use, and continuity and terminal-connection tests are made before first use, before return to service after repair, after any incident that could reasonably be suspected of causing damage, and at intervals not exceeding three months (six months for cord sets and receptacles that are fixed and not exposed to damage). The test record identifies each item that passed and the last test date or interval, and may be kept by logs, color coding or other effective means; no individual tag is required. Equipment that has not met the program may not be made available or used.

Does a dry environment make a ground fault harmless?

A ground fault of a small current can be dangerous depending on the path, the voltage, the duration and the contact; a dry environment does not establish that it is harmless. 1926.404(b)(1) has the employer use either GFCIs or an assured equipment grounding conductor program to protect employees on construction sites.

Regulatory history of 29 CFR 1926.404

1926.404 is in Subpart K (Electrical). Its source note lists 51 FR 25318 (July 11, 1986), 54 FR 24334 (June 7, 1989) and 61 FR 5510 (February 13, 1996).

Related glossary terms

Key terms that appear in 29 CFR 1926.404, each with a full plain-English explainer.

Get the Binder in Order Before the Inspector Arrives. Are You Ready?

OSHA inspections come unannounced, apart from the few exceptions listed in 29 CFR 1903.6. Get the binder in order before the opening conference, not during it.