What 29 CFR 1926.404 requires (plain English)
29 CFR 1926.404 governs wiring design and protection for construction: identification and polarity of conductors, branch circuits and ground-fault protection, outside conductors and lamps, services, overcurrent protection and grounding.
The core requirement gives the employer two options. Under the first, all 120-volt, single-phase, 15- and 20-ampere receptacle outlets on the site that are not part of the permanent wiring and are in use by employees must have approved ground-fault circuit interrupters (GFCIs) for personnel protection. The OSHA eTool describes the GFCI as comparing the current going to and returning from equipment along the circuit conductors and interrupting the current when the two differ by approximately 5 milliamperes, within as little as 1/40 of a second, if it is properly installed and maintained; it does not protect from line contact hazards, such as a person holding two "hot" wires, a hot and a neutral wire in each hand, or contacting an overhead power line. Receptacles on a two-wire, single-phase portable or vehicle-mounted generator rated not more than 5 kW, whose circuit conductors are insulated from the generator frame and all other grounded surfaces, need not have GFCIs. Under the second option, the employer may instead establish and implement a written Assured Equipment Grounding Conductor Program. The program has a written description, including the specific procedures adopted by the employer, available at the jobsite for inspection and copying, with one or more competent persons designated to implement it ((b)(1)(iii)(A)-(B)); a program is not a document alone: the controls and the tests must actually be performed. Each cord set, attachment cap, plug and receptacle of cord sets, and any equipment connected by cord and plug (except cord sets and receptacles that are fixed and not exposed to damage) is visually inspected before each day's use, and equipment found damaged or defective is not used until repaired ((C)); equipment grounding conductors are tested for continuity and each receptacle and plug is tested for correct attachment ((D)); tests are made before first use, before return to service after repair, after any incident that could reasonably be suspected of causing damage, and at intervals not exceeding 3 months (6 months for cord sets and receptacles that are fixed and not exposed to damage) ((E)); and a record of the tests is kept by logs, color coding or other effective means and available at the jobsite ((G)).
Beyond ground-fault protection, 1926.404 covers wiring design more broadly: identification and polarity of conductors, branch-circuit outlet devices rated for the load ((b)(2)), outside conductors and lamps ((c)), services, overcurrent protection and grounding in its other paragraphs. Equipment grounding conductors must be properly connected, and this section's ground-fault rules are in addition to the other equipment grounding conductor requirements ((b)(1)(i)). Grounding has exceptions with conditions: the frame of a portable generator need not be grounded and may serve as the grounding electrode for a system supplied by the generator when it supplies only equipment mounted on it or cord- and plug-connected equipment through receptacles mounted on it, with the metal parts and grounding terminals bonded to its frame ((f)(3)(i)); tools likely to be used in wet or conductive locations need not be grounded if supplied through an isolating transformer with an ungrounded secondary of not over 50 volts, and listed or labeled portable tools protected by a system of double insulation, or its equivalent, need not be grounded and are distinctively marked ((f)(7)(iv)(C)(6)). Conductors and equipment are protected from overcurrent in accordance with their ability to safely conduct current ((e)(1)(i)); means are provided to disconnect all conductors in a building or other structure from the service-entrance conductors ((d)(1)(i)); open outside conductors keep the clearances of (c)(1)(ii), such as 10 feet above finished grade; no grounded conductor is attached to any terminal or lead so as to reverse designated polarity ((a)(2)). 1926.405, 1926.416, 1926.417 and 1926.302 have their own requirements, and general industry provisions do not replace them.