What 29 CFR 1910.334 requires (plain English)
29 CFR 1910.334 governs the use of electrical equipment as part of OSHA's electrical safety-related work practices: how portable tools, cords, and equipment are handled, inspected and tested.
The core requirement is pre-use inspection. Portable cord- and plug-connected equipment and flexible cord sets (extension cords) must be visually inspected before use on any shift for external defects (such as loose parts, deformed or missing pins, or damage to the outer jacket or insulation) and for evidence of possible internal damage. Any equipment or cord found damaged or defective must be removed from service, and no employee may use it until the necessary repairs and tests to render it safe have been made. Equipment and cords that remain connected once they are put in place and are not exposed to damage need not be inspected until they are relocated.
Handling and use rules complete the standard. Portable equipment must be handled in a manner that will not cause damage: flexible cords may not be used to raise or lower equipment, and may not be fastened with staples or otherwise hung in a way that could damage the outer jacket or insulation. Portable equipment and cords used in highly conductive work locations, or where employees are likely to contact water or conductive liquids, must be approved for those locations, and employees' hands may not be wet when plugging and unplugging energized equipment ((a)(4)-(5)). Flexible cords used with grounding-type equipment must contain an equipment grounding conductor, plugs and receptacles may not be altered so the grounding continuity is lost, and adapters that interrupt the grounding connection may not be used ((a)(3)). For circuits, load-rated switches, circuit breakers or other devices designed as disconnecting means must be used to open, reverse or close circuits under load ((b)(1)); after a circuit protective device trips, the circuit may not be manually re-energized until it has been determined that the equipment and circuit can be safely energized, and repetitive manual reclosing of breakers or re-energizing through replaced fuses is prohibited, except that no examination is needed when the design of the circuit and the overcurrent devices shows the trip was an overload, not a fault (b)(2) and its note. Only qualified persons may perform testing work on electric circuits or equipment, with test instruments, leads and probes visually inspected before use and rated for the circuits they are connected to ((c)(1)-(3)). Pulling a plug out by its cord damages cords and is poor practice that the no-damage handling rule of (a)(1) can reach, though that paragraph does not use those words.