Skip to content

Approaching: Feb 1, 2027 — 300A Posting Begins. Get ready →

General Industry (29 CFR 1910)

Use of Equipment

Verified vs OSHA sources · 2026-10-19

29 CFR 1910.334

29 CFR 1910.334 sets safe work practices for using electrical equipment: portable cord-and-plug equipment must be visually inspected for damage before use on any shift (equipment left connected in place and not exposed to damage is inspected when relocated), defective equipment must be removed from service, a tripped circuit may not be re-energized until it is determined safe, and workers may not plug or unplug energized equipment with wet hands.

29 CFR 1910.334 at a glance

What it requires
Safe use of electrical equipment: inspect cords and tools before use, remove defects
Inspection
Portable cord- and plug-connected equipment inspected before use on any shift; items left connected in place and not exposed to damage only when relocated (1910.334(a)(2)(i))
Damaged equipment
Defective or damaged items must be removed from service until repaired and tested
Handling
Equipment handled so as not to cause damage; cords not used to raise/lower equipment
Max penalty (2026)
$16,550 per serious violation; $165,514 per willful
Common confusion
The inspection is before use on any shift, with an exception for equipment left connected in place and not exposed to damage; 1910.334 does not prescribe a new inspection by each user at each exchange

What 29 CFR 1910.334 requires (plain English)

29 CFR 1910.334 governs the use of electrical equipment as part of OSHA's electrical safety-related work practices: how portable tools, cords, and equipment are handled, inspected and tested.

The core requirement is pre-use inspection. Portable cord- and plug-connected equipment and flexible cord sets (extension cords) must be visually inspected before use on any shift for external defects (such as loose parts, deformed or missing pins, or damage to the outer jacket or insulation) and for evidence of possible internal damage. Any equipment or cord found damaged or defective must be removed from service, and no employee may use it until the necessary repairs and tests to render it safe have been made. Equipment and cords that remain connected once they are put in place and are not exposed to damage need not be inspected until they are relocated.

Handling and use rules complete the standard. Portable equipment must be handled in a manner that will not cause damage: flexible cords may not be used to raise or lower equipment, and may not be fastened with staples or otherwise hung in a way that could damage the outer jacket or insulation. Portable equipment and cords used in highly conductive work locations, or where employees are likely to contact water or conductive liquids, must be approved for those locations, and employees' hands may not be wet when plugging and unplugging energized equipment ((a)(4)-(5)). Flexible cords used with grounding-type equipment must contain an equipment grounding conductor, plugs and receptacles may not be altered so the grounding continuity is lost, and adapters that interrupt the grounding connection may not be used ((a)(3)). For circuits, load-rated switches, circuit breakers or other devices designed as disconnecting means must be used to open, reverse or close circuits under load ((b)(1)); after a circuit protective device trips, the circuit may not be manually re-energized until it has been determined that the equipment and circuit can be safely energized, and repetitive manual reclosing of breakers or re-energizing through replaced fuses is prohibited, except that no examination is needed when the design of the circuit and the overcurrent devices shows the trip was an overload, not a fault (b)(2) and its note. Only qualified persons may perform testing work on electric circuits or equipment, with test instruments, leads and probes visually inspected before use and rated for the circuits they are connected to ((c)(1)-(3)). Pulling a plug out by its cord damages cords and is poor practice that the no-damage handling rule of (a)(1) can reach, though that paragraph does not use those words.

The regulatory text

“Portable cord- and plug-connected equipment and flexible cord sets (extension cords) shall be visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket).”
29 CFR 1910.334(a)(2)(i)

Key facts about 29 CFR 1910.334

  • Portable cord- and plug-connected equipment and extension cords must be visually inspected before use on any shift; items that remain connected once put in place and are not exposed to damage need inspection only when relocated (1910.334(a)(2)(i)).
  • Inspection looks for external defects (loose parts, deformed/missing pins, jacket/insulation damage) and evidence of internal damage.
  • Damaged or defective equipment/cords must be removed from service until repaired and tested safe (1910.334(a)(2)(ii)).
  • Portable equipment must be handled so as not to cause damage.
  • Flexible cords may not be used to raise or lower equipment, or fastened with staples.
  • Portable equipment and cords in highly conductive or wet work locations must be approved for them, and hands may not be wet when plugging or unplugging energized equipment (1910.334(a)(4)-(5)).
  • A circuit tripped by a protective device may not be manually re-energized until it is determined safe; repetitive manual reclosing of breakers or re-energizing through replaced fuses is prohibited (1910.334(b)(2)); no examination is needed when the design shows the trip was an overload (note).
  • Grounding-type equipment needs a cord with an equipment grounding conductor, and no adapter or alteration may interrupt grounding continuity (1910.334(a)(3)).
  • Only qualified persons may do testing work on circuits and equipment, with inspected, correctly rated test instruments and leads (1910.334(c)).
  • Works with the wiring standard (1910.305) and the de-energization work practices (1910.333).

Scope: who 29 CFR 1910.334 applies to

Regulatory framework
General Industry (29 CFR 1910)
Citation reference
29 CFR 1910.334
Enforcement status
In force and enforced
Jurisdiction
Federal OSHA (29 State-Plan jurisdictions may be stricter)

State-Plan states (e.g. California, Washington, Michigan) operate OSHA-approved programs that must be at least as effective as federal OSHA and frequently impose higher penalties or additional requirements.

Key requirements of 29 CFR 1910.334

#What the section requires or covers
1Inspect portable equipment before use
2Do not use damaged extension cords
3Remove from service equipment with defects
4Use proper test equipment rated for circuit voltage
5Protect cord connections from strain

Summarized from the text of 29 CFR 1910.334.

Common Electrical Equipment Use violations

Deficiencies OSHA cites under 29 CFR 1910.334 include the ones below, in no particular order. Each serious item carries up to $16,550 (2026).

  • Portable equipment/cords not visually inspected before use on any shift, other than items left connected in place and not exposed to damage (1910.334(a)(2)(i)).
  • Damaged or defective cords/tools kept in service instead of being removed (1910.334(a)(2)(ii)).
  • Flexible cords used to raise/lower equipment or fastened with staples (1910.334(a)(1)).
  • Cords damaged by being pulled, or otherwise handled in a way that damages them (1910.334(a)(1)).
  • Portable equipment or cords not approved for a highly conductive or wet work location (1910.334(a)(4)); hands wet when plugging or unplugging energized equipment ((a)(5)); circuit manually re-energized after a trip without determining it is safe, or repetitive reclosing of a breaker or replaced fuses (1910.334(b)(2)); testing work by a person who is not qualified ((c)(1)).

Inspection before use on any shift, with one exception

1910.334(a)(2)(i) has portable cord- and plug-connected equipment and flexible cord sets visually inspected before use on any shift for external defects and for evidence of possible internal damage; equipment and cords that remain connected once put in place and are not exposed to damage need not be inspected until they are relocated. The paragraph does not prescribe a new inspection by each user at each exchange, and it sets no periodic test. If the inspection shows damage, (a)(2)(ii) has the item removed from service until the repairs and tests necessary to render it safe have been made.

What OSHA inspectors look for

A compliance officer looks for damaged cords and tools still in service, missing ground prongs, equipment used in wet conditions without protection, and overloaded circuits.

Example: how a violation is cited

Hypothetical case: a worker uses a drill whose cord is cut through to the conductors. 1910.334(a)(2)(ii) has damaged or defective equipment removed from service until the repairs and tests necessary to render it safe have been made. A serious violation carries a penalty of up to $16,550.

Illustrative example, not a specific OSHA case.

Electrical Equipment Use compliance checklist

Each item is a requirement of 29 CFR 1910.334 that OSHA may verify during an inspection.

  • Visually inspect portable equipment and extension cords before use on any shift (items left connected in place and not exposed to damage need it only when relocated) (1910.334(a)(2)(i)).
  • Check for external defects (loose parts, deformed/missing pins, jacket/insulation damage) and internal damage.
  • Remove any damaged or defective item from service until it is repaired and tested safe.
  • Handle equipment so as not to damage it; never use a cord to raise/lower a tool or staple it in place.
  • Do not pull a plug out by its cord (good practice; the no-damage handling rule of 1910.334(a)(1) reaches the damage it causes). Do not reset a tripped breaker or replace a fuse again and again before the cause is determined (1910.334(b)(2)).
  • Use equipment and cords approved for conductive or wet locations ((a)(4)), keep hands dry when plugging or unplugging energized equipment ((a)(5)), keep grounding continuity ((a)(3)), have only qualified persons test circuits with inspected, rated instruments ((c)), and provide GFCI protection where 1910.304(b)(3) calls for it.

A lockout can't go active until every point has its zero-energy check recorded, and on an electrical point, only a meter test counts. Lockout/tagout in HazComFast

2026 penalties for 29 CFR 1910.334

Maximums set by 29 CFR 1903.15(d). 2026 maximums unchanged from 2025 (no CPI adjustment; OMB M-26-11), so not an increase; the serious and repeat policy minimums were revised with FOM chapter 6 (OSHA memo of May 21, 2026). The 2025 OSHA penalty levels remain in effect for 2026; OSHA made no inflation adjustment for 2026. 29 CFR 1903.15 identifies January 15, 2025 as the effective reference for these amounts, while OSHA's public penalties page currently references penalties assessed after Jan. 15, 2026.

Violation typeMinimumMaximumWhen it applies
Serious$1,085$16,550Death or serious physical harm could result, and the employer knew or could have known (29 U.S.C. 666(k)).
Other-Than-Serious$0$16,550Relates to safety/health but unlikely to cause death or serious harm.
Willful$11,823$165,514Intentional, knowing, or voluntary disregard of the requirement.
Repeated$4,256$165,514A substantially similar violation cited within the last 5 years.
Failure to AbateNone$16,550/dayup to $16,550 per day; the total is normally capped at 30 times the daily amount (FOM Ch.6)

Serious violations reach $16,550 and willful or repeat violations $165,514.

Maximums and the willful minimum are set by 29 CFR 1903.15(d); the serious and repeated minimums are OSHA policy floors from its annual penalty adjustment memo. OSHA applies gravity-based and size, good-faith and history reductions (FOM CPL 02-00-164 Ch.6). Estimates only, not legal advice.

The business case for Electrical Equipment Use compliance

1910.334(a)(2)(i) has portable cord- and plug-connected equipment and flexible cord sets visually inspected before use on any shift for external defects and for evidence of possible internal damage, and (a)(2)(ii) has damaged or defective equipment removed from service until the necessary repairs and tests have been made.

Free compliance tools for 29 CFR 1910.334

State plans and their penalty rules

States listed by the volume of their federal construction citations, not by this standard. Penalties and enforcement vary by state. State-Plan states may impose higher penalties and additional requirements beyond federal 29 CFR 1910.334.

State pages for 29 CFR 1910.334

Frequently asked questions about 29 CFR 1910.334

How often must electrical cords and tools be inspected?

Before use on any shift. Under 1910.334(a)(2)(i), portable cord- and plug-connected equipment and flexible cord sets (extension cords) must be visually inspected before use on any shift for external defects (loose parts, deformed or missing pins, damage to the outer jacket or insulation) and for evidence of possible internal damage such as a pinched or crushed jacket. Equipment and cords that remain connected once they are put in place and are not exposed to damage need not be inspected until they are relocated.

What must be done with a damaged extension cord or power tool?

It must be removed from service. Under 1910.334(a)(2)(ii), any portable equipment or cord found to be damaged or defective must be removed from service, and no employee may use it until the repairs and tests necessary to render it safe have been made.

Can you use an extension cord to hoist a tool?

No. Under 1910.334(a)(1), flexible cords may not be used to raise or lower equipment. Cords also may not be fastened with staples or hung in a way that could damage the outer jacket or insulation. Pulling a plug out by its cord is poor practice that the no-damage handling rule can reach, though paragraph (a)(1) does not state it in those words.

How does 1910.334 relate to GFCI protection?

1910.334 has portable electrical equipment inspected and damaged equipment removed from service; the GFCI obligations are in 1910.304(b)(3). A GFCI monitors an imbalance between the current going out and coming back; it does not protect against every contact between conductors.

Regulatory history of 29 CFR 1910.334

1910.334 was published with the electrical safety-related work practices rule at 55 FR 32016 (August 6, 1990), according to the eCFR source note.

Related glossary terms

Key terms that appear in 29 CFR 1910.334, each with a full plain-English explainer.

Get the Binder in Order Before the Inspector Arrives. Are You Ready?

OSHA inspections come unannounced, apart from the few exceptions listed in 29 CFR 1903.6. Get the binder in order before the opening conference, not during it.