29 CFR 1910.305

29 CFR 1910.305 governs wiring methods, components, and equipment in general industry: flexible cords may be used only for the purposes listed in (g)(1)(ii), and unless a use in (g)(1)(ii) permits it they are not used as a substitute for the fixed wiring of a structure, conductors entering boxes must be protected and unused openings closed, and metal raceways and enclosures that serve as grounding conductors must be effectively bonded.

29 CFR 1910.305 at a glance

What it requires
Safe wiring methods, components, and equipment for general electrical use
Flexible cords
Only for the uses listed in (g)(1)(ii); never a substitute for fixed wiring, and not through walls, doorways or windows, on building surfaces or concealed, unless (g)(1)(ii) permits
Boxes & fittings
Pull and junction boxes and fittings must have covers identified for the purpose (metal covers grounded); unused openings closed (1910.305(b))
Bonding
Metal raceways, enclosures and other metal parts that serve as grounding conductors must be effectively bonded where necessary for continuity and fault-current capacity (1910.305(a)(1)(i))
Max penalty (2026)
$16,550 per serious violation; $165,514 per willful
Common confusion
Flexible cords are used for the purposes (g)(1)(ii) lists; the prohibitions of (g)(1)(iv) apply unless (g)(1)(ii) permits the use

What 29 CFR 1910.305 requires (plain English)

29 CFR 1910.305 sets the requirements for wiring methods, components, and equipment for general electrical use in general industry, alongside the general requirements of 1910.303. It covers permanent and temporary wiring methods (raceways, cable, boxes, and cabinets), the use and limits of flexible cords and cables, and bonding. Temporary power and lighting of 600 volts or less is used only during remodeling, maintenance or repair and similar activities, for no more than 90 days for Christmas decorative lighting, carnivals and similar purposes, or for experimental or development work and emergencies, and is removed immediately on completion ((a)(2)(i)-(ii)).

Paragraph (g) concerns flexible cords and cables (extension cords and equipment cords). Flexible cords may be used only for the purposes listed in 1910.305(g)(1)(ii): pendants, wiring of fixtures, connection of portable lamps or appliances, portable and mobile signs, elevator cables, wiring of cranes and hoists, connection of stationary equipment to facilitate its frequent interchange, prevention of the transmission of noise or vibration, appliances designed to be removed for maintenance and repair, data processing cables, connection of moving parts, and temporary wiring. Unless one of those uses specifically permits it, a flexible cord may not be used as a substitute for the fixed wiring of a structure, run through holes in walls, ceilings, or floors, run through doorways, windows, or similar openings, attached to building surfaces, concealed behind building walls, ceilings, or floors, or installed in raceways (g)(1)(iv). OSHA's letter of July 2, 2015 refers to the permitted and prohibited uses and gives no general limit in days; the function, the route, the equipment and the protective means are examined.

The standard also requires that boxes and fittings be sound and closed: pull boxes, junction boxes, and fittings must be provided with covers identified for the purpose, unused openings in boxes and cabinets must be effectively closed, and conductors entering boxes must be protected from abrasion. Metal raceways, cable trays, cable armor, enclosures and other metal parts that serve as grounding conductors must be effectively bonded where necessary to ensure electrical continuity and the capacity to conduct safely any fault current likely to be imposed on them (1910.305(a)(1)(i)), and metal covers on boxes must be grounded (1910.305(b)(2)(i)). Together with 1910.303 (general requirements) and the grounding rules of 1910.304(g), these installation rules form the design side of Subpart S.

The regulatory text

“Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used: (A) As a substitute for the fixed wiring of a structure;”
29 CFR 1910.305(g)(1)(iv)(A)

Key facts about 29 CFR 1910.305

  • Governs wiring methods, components, and equipment for general use: the installation companion to 1910.303.
  • Flexible cords may be used only for the purposes listed in (g)(1)(ii) (pendants, fixtures, portable lamps and appliances, elevator cables, cranes and hoists, frequent interchange of stationary equipment, and others).
  • Unless (g)(1)(ii) permits the use, flexible cords are not used as a substitute for fixed wiring, or run through walls, ceilings, floors, doorways, or windows.
  • Unless (g)(1)(ii) permits the use, flexible cords are not attached to building surfaces, concealed behind walls, ceilings, or floors, or installed in raceways.
  • Pull and junction boxes and fittings must have covers identified for the purpose (metal covers grounded), and each outlet box a cover, faceplate or fixture canopy in a completed installation (1910.305(b)(2)(i)).
  • Unused openings in boxes, cabinets, and fittings must be effectively closed.
  • Metal raceways, enclosures and other metal parts that serve as grounding conductors must be effectively bonded where necessary to conduct fault current safely (1910.305(a)(1)(i)).
  • Conductors entering boxes, cabinets and fittings must be protected from abrasion and the openings effectively closed (1910.305(b)(1)(i)).
  • Flexible cords and cables are connected to devices and fittings with strain relief, so pull is not transmitted directly to joints or terminal screws (1910.305(g)(2)(iii)).
  • Temporary wiring of 600 volts or less is limited to remodeling, maintenance, repair and similar activities, 90 days for decorative lighting, carnivals and similar purposes, and experimental work or emergencies, and is removed on completion (1910.305(a)(2)).

Scope: who 29 CFR 1910.305 applies to

Regulatory framework
General Industry (29 CFR 1910)
Citation reference
29 CFR 1910.305
Enforcement status
In force and enforced
Jurisdiction
Federal OSHA (29 State-Plan jurisdictions may be stricter)

State-Plan states (e.g. California, Washington, Michigan) operate OSHA-approved programs that must be at least as effective as federal OSHA and frequently impose higher penalties or additional requirements.

Key requirements of 29 CFR 1910.305

#What the section requires or covers
1Use appropriate wiring methods for location
2Protect wiring from physical damage
3Properly support and secure conductors
4Use approved electrical fittings and boxes
5Maintain covers on junction boxes

Summarized from the text of 29 CFR 1910.305.

Common Electrical Wiring Methods violations

Deficiencies OSHA cites under 29 CFR 1910.305 include the ones below, in no particular order. Each serious item carries up to $16,550 (2026).

  • Flexible cords used as a substitute for fixed wiring, run through walls, doorways or windows, attached to building surfaces or concealed, where (g)(1)(ii) does not permit the use (1910.305(g)(1)(iv)).
  • Pull and junction boxes or fittings without covers identified for the purpose, an outlet box without a cover, faceplate or canopy, or unused openings not closed (1910.305(b)(1)(ii), (b)(2)(i)).
  • Flexible cord used in a way (g)(1) does not permit, or without the identification, splice and termination requirements of 1910.305(g)(2); a cord with a cut sheath or a missing grounding pin falls under the inspection and removal rules of 1910.334(a)(2)-(3).
  • Metal raceways or enclosures serving as grounding conductors not effectively bonded (1910.305(a)(1)(i)); metal box cover not grounded (1910.305(b)(2)(i)); equipment grounding under 1910.304(g).
  • Conductors entering boxes, cabinets or fittings not protected from abrasion or the opening not closed (1910.305(b)(1)(i)); cable not secured to the box (b)(1)(iii).

Cords: permitted uses and prohibited uses

Flexible cords are permitted for the uses 1910.305(g)(1)(ii) lists (pendants, portable lamps and appliances, cranes and hoists, equipment that is frequently interchanged, and others). Unless (g)(1)(ii) permits the use, (g)(1)(iv)(A) does not allow a cord as a substitute for the fixed wiring of a structure. The duration of a connection alone does not decide compliance; OSHA's letter of July 2, 2015 refers to the permitted and prohibited uses and gives no general limit in days.

What OSHA inspectors look for

A compliance officer checks flexible cords against the uses listed in (g)(1)(ii) and the prohibitions of (g)(1)(iv), open junction boxes and unused openings, damaged cord insulation, and the bonding of metal parts that serve as grounding conductors.

Example: how a violation is cited

Hypothetical case: a shop powers a machine through a chain of extension cords attached to the building as permanent wiring, for no use that (g)(1)(ii) lists. 1910.305(g)(1)(iv)(A) has flexible cords not used as a substitute for the fixed wiring of a structure unless (g)(1)(ii) specifically permits it. A serious violation carries a penalty of up to $16,550.

Illustrative example, not a specific OSHA case.

Electrical Wiring Methods compliance checklist

Each item is a requirement of 29 CFR 1910.305 that OSHA may verify during an inspection.

  • Use fixed wiring methods (raceway, cable) for the building's power; keep flexible cords to the uses (g)(1)(ii) lists, and do not use one as a substitute for fixed wiring unless (g)(1)(ii) permits it.
  • Do not run flexible cords through walls, ceilings, floors, doorways, or windows, attach them to building surfaces, or conceal them in the structure, unless a use in (g)(1)(ii) permits it.
  • Provide covers identified for the purpose on pull and junction boxes and fittings (a cover, faceplate or canopy on every outlet box), ground metal covers, and close every unused opening.
  • Effectively bond metal raceways, enclosures and other metal parts that serve as grounding conductors (1910.305(a)(1)(i)), and ground equipment as 1910.304(g) requires.
  • Protect conductors from abrasion where they enter boxes and close the openings; remove damaged cords from service under the cord-inspection practice of 1910.334(a)(2).
  • Where a cord does the work of the fixed wiring of a structure and (g)(1)(ii) does not permit it, install fixed wiring.
  • Inspect cords before use on each shift under 1910.334(a)(2), with the exception for equipment left connected and not exposed to damage; a cord with a dangerous defect is removed from use until repairs and tests are made.

2026 penalties for 29 CFR 1910.305

Maximums set by 29 CFR 1903.15(d). 2026 maximums unchanged from 2025 (no CPI adjustment; OMB M-26-11), so not an increase; the serious and repeat policy minimums were revised with FOM chapter 6 (OSHA memo of May 21, 2026). The 2025 OSHA penalty levels remain in effect for 2026; OSHA made no inflation adjustment for 2026. 29 CFR 1903.15 identifies January 15, 2025 as the effective reference for these amounts, while OSHA's public penalties page currently references penalties assessed after Jan. 15, 2026.

Violation typeMinimumMaximumWhen it applies
Serious$1,085$16,550Death or serious physical harm could result, and the employer knew or could have known (29 U.S.C. 666(k)).
Other-Than-Serious$0$16,550Relates to safety/health but unlikely to cause death or serious harm.
Willful$11,823$165,514Intentional, knowing, or voluntary disregard of the requirement.
Repeated$4,256$165,514A substantially similar violation cited within the last 5 years.
Failure to AbateNone$16,550/dayup to $16,550 per day; the total is normally capped at 30 times the daily amount (FOM Ch.6)

Serious violations reach $16,550 and willful or repeat violations $165,514.

Maximums and the willful minimum are set by 29 CFR 1903.15(d); the serious and repeated minimums are OSHA policy floors from its annual penalty adjustment memo. OSHA applies gravity-based and size, good-faith and history reductions (FOM CPL 02-00-164 Ch.6). Estimates only, not legal advice.

The business case for Electrical Wiring Methods compliance

1910.305(g)(1)(iv)(A) has flexible cords and cables not used as a substitute for the fixed wiring of a structure unless (g)(1)(ii) specifically permits it, and (b) has pull boxes, junction boxes and fittings provided with covers identified for the purpose and unused openings effectively closed.

Free compliance tools for 29 CFR 1910.305

State plans and their penalty rules

States listed by the volume of their federal construction citations, not by this standard. Penalties and enforcement vary by state. State-Plan states may impose higher penalties and additional requirements beyond federal 29 CFR 1910.305.

State pages for 29 CFR 1910.305

Frequently asked questions about 29 CFR 1910.305

Can extension cords be used as permanent wiring?

Not as a substitute for the fixed wiring of a structure. Under 1910.305(g)(1)(iv), unless a use in (g)(1)(ii) specifically permits it, flexible cords and cables may not be used as a substitute for the fixed wiring of a structure, run through holes in walls, ceilings, or floors, run through doorways, windows or similar openings, attached to building surfaces, concealed behind building walls, ceilings, or floors, or installed in raceways. Section (g)(1)(ii) does allow cords for pendants, portable lamps and appliances, cranes and hoists, equipment that is frequently interchanged and a few other uses. OSHA's letter of July 2, 2015 gives no general limit in days; the permitted and prohibited uses decide.

Do all junction boxes need covers?

Yes. Under 1910.305(b)(2)(i), all pull boxes, junction boxes, and fittings must be provided with covers identified for the purpose (metal covers must be grounded), and in completed installations each outlet box must have a cover, faceplate, or fixture canopy. Under (b)(1)(ii), unused openings in cabinets, boxes, and fittings must be effectively closed.

What does 'effectively bonded' mean for electrical wiring?

Under 1910.305(a)(1)(i), metal raceways, cable trays, cable armor, cable sheath, enclosures, frames, fittings and other metal noncurrent-carrying parts that serve as grounding conductors must be effectively bonded where necessary to ensure electrical continuity and the capacity to conduct safely any fault current likely to be imposed on them; grounding of equipment is covered by 1910.304(g).

Which cord uses does 1910.305(g)(1)(iv) prohibit?

Unless a use in (g)(1)(ii) specifically permits it, flexible cords and cables are not used as a substitute for the fixed wiring of a structure, run through holes in walls, ceilings, or floors, run through doorways, windows or similar openings, attached to building surfaces, concealed behind building walls, ceilings, or floors, or installed in raceways ((g)(1)(iv)).

Regulatory history of 29 CFR 1910.305

1910.305 is part of Subpart S, which separates the design safety standards for electrical systems (1910.302 to 1910.308) from the safety-related work practices (1910.331 to 1910.335); 1910.302 sets the installations covered, the exclusions, and the dates from which some requirements apply.

Related glossary terms

Key terms that appear in 29 CFR 1910.305, each with a full plain-English explainer.

Get the Binder in Order Before the Inspector Arrives. Are You Ready?

OSHA inspections come unannounced, apart from the few exceptions listed in 29 CFR 1903.6. Get the binder in order before the opening conference, not during it.