What 29 CFR 1926.405 requires (plain English)
29 CFR 1926.405 governs wiring methods, components, and equipment for general use on construction sites: how conductors are run, spliced and enclosed, temporary wiring, flexible cords and cables, and equipment such as lighting fixtures, motors, transformers and capacitors.
A central prohibition is that flexible cords and cables may not be used as a substitute for the fixed wiring of a structure, run through holes in walls or ceilings, or attached to building surfaces as permanent wiring. The prohibited uses apply unless necessary for a use (g)(1)(i) permits, and the doorway prohibition has an exception: flexible cords and cables may pass through doorways or other pinch points if protection is provided to avoid damage ((g)(1)(iii)(C), (a)(2)(ii)(I)). Beyond that, conductors entering boxes, cabinets and fittings must be protected from abrasion and the openings closed, pull and junction boxes and fittings must have covers (metal covers grounded), and each outlet box in an energized installation needs a cover, faceplate or fixture canopy ((b)(1)-(2)). Flexible cords may be used only in continuous lengths without splice or tap, but hard service flexible cords No. 12 or larger may be repaired by a splice that retains the insulation, outer sheath properties and usage characteristics of the cord ((g)(2)(iii)). For temporary wiring (1926.405(a)(2)(ii)): temporary lights may not be hung by their cords unless the cords and lights are designed for it ((F)); portable lighting in wet or other conductive locations such as drums, tanks and vessels must run at 12 volts or less, though 120-volt lights are allowed if protected by a GFCI ((G)); flexible cords and cables must be protected from damage, sharp corners and projections avoided, and they may pass through doorways or other pinch points if protection is provided to avoid damage ((I)); extension cord sets for portable tools and appliances must be the three-wire type designed for hard or extra-hard usage, and cords for temporary and portable lights hard or extra-hard usage ((J)).
Under 1926.403, all electrical conductors and equipment are approved ((a)), and listed, labeled, or certified equipment is installed and used in accordance with instructions included in the listing, labeling, or certification ((b)(2)); 1926.449 defines acceptable. In its letter of October 4, 2000, OSHA states that 1926.405(a)(2)(ii)(B) permits nonmetallic-sheathed cable (type NM) to be used as temporary wiring, secured by staples, cable ties, straps or similar fittings designed and installed so as not to damage the cable, and run up the outside of walls for both exposed and concealed work in normally dry locations; no branch-circuit conductors are laid on the floor. NM cable and an extension cord are not the same, and that permission does not cover a stapling that damages an extension cord. The letter was edited on April 12, 2004 to strike information that no longer reflects current OSHA policy. The note to 1926.402(a) deems an installation made in accordance with the National Electrical Code ANSI/NFPA 70-1984 in compliance with 1926.403 through 1926.408, except for 1926.404(b)(1) and 1926.405(a)(2)(ii)(E), (F), (G) and (J); a later NEC edition is not presumed adopted. Paragraph (j) covers equipment for general use, including lighting fixtures, lampholders, lamps and receptacles, motors, transformers and capacitors. 1926.404(f) and the particular provisions govern grounding. Temporary wiring is removed immediately upon completion of the construction or of the purpose for which it was installed ((a)(2)(i)).