Skip to content

Approaching: Feb 1, 2027 — 300A Posting Begins. Get ready →

Construction (29 CFR 1926)

Wiring Methods, Components (Construction)

Verified vs OSHA sources · 2026-10-19

29 CFR 1926.405

29 CFR 1926.405 governs wiring methods, components, and equipment on construction sites: flexible cords and cables may not be used as a substitute for the fixed wiring of a structure, conductors entering boxes must be protected and boxes closed and covered, flexible cords may be spliced only in the narrow case of (g)(2)(iii), and temporary wiring has its own rules.

29 CFR 1926.405 at a glance

What it covers
Wiring methods and temporary wiring (a), cabinets, boxes and fittings (b), flexible cords and cables (g), equipment for general use (j)
Who it covers
Construction employers using temporary and permanent electrical systems
Cord rule
Flexible cords may not substitute for the fixed wiring of a structure (1926.405(g)(1)(iii))
Extension cords
Three-wire type designed for hard or extra-hard usage with portable electric tools and appliances (1926.405(a)(2)(ii)(J))
Max penalty (2026)
$16,550 per serious violation; $165,514 per willful
Common confusion
The splice rule of (g)(2)(iii) is not a rule that every splice must be in a box; hard service cord No. 12 or larger may be repaired with a splice that keeps its characteristics

What 29 CFR 1926.405 requires (plain English)

29 CFR 1926.405 governs wiring methods, components, and equipment for general use on construction sites: how conductors are run, spliced and enclosed, temporary wiring, flexible cords and cables, and equipment such as lighting fixtures, motors, transformers and capacitors.

A central prohibition is that flexible cords and cables may not be used as a substitute for the fixed wiring of a structure, run through holes in walls or ceilings, or attached to building surfaces as permanent wiring. The prohibited uses apply unless necessary for a use (g)(1)(i) permits, and the doorway prohibition has an exception: flexible cords and cables may pass through doorways or other pinch points if protection is provided to avoid damage ((g)(1)(iii)(C), (a)(2)(ii)(I)). Beyond that, conductors entering boxes, cabinets and fittings must be protected from abrasion and the openings closed, pull and junction boxes and fittings must have covers (metal covers grounded), and each outlet box in an energized installation needs a cover, faceplate or fixture canopy ((b)(1)-(2)). Flexible cords may be used only in continuous lengths without splice or tap, but hard service flexible cords No. 12 or larger may be repaired by a splice that retains the insulation, outer sheath properties and usage characteristics of the cord ((g)(2)(iii)). For temporary wiring (1926.405(a)(2)(ii)): temporary lights may not be hung by their cords unless the cords and lights are designed for it ((F)); portable lighting in wet or other conductive locations such as drums, tanks and vessels must run at 12 volts or less, though 120-volt lights are allowed if protected by a GFCI ((G)); flexible cords and cables must be protected from damage, sharp corners and projections avoided, and they may pass through doorways or other pinch points if protection is provided to avoid damage ((I)); extension cord sets for portable tools and appliances must be the three-wire type designed for hard or extra-hard usage, and cords for temporary and portable lights hard or extra-hard usage ((J)).

Under 1926.403, all electrical conductors and equipment are approved ((a)), and listed, labeled, or certified equipment is installed and used in accordance with instructions included in the listing, labeling, or certification ((b)(2)); 1926.449 defines acceptable. In its letter of October 4, 2000, OSHA states that 1926.405(a)(2)(ii)(B) permits nonmetallic-sheathed cable (type NM) to be used as temporary wiring, secured by staples, cable ties, straps or similar fittings designed and installed so as not to damage the cable, and run up the outside of walls for both exposed and concealed work in normally dry locations; no branch-circuit conductors are laid on the floor. NM cable and an extension cord are not the same, and that permission does not cover a stapling that damages an extension cord. The letter was edited on April 12, 2004 to strike information that no longer reflects current OSHA policy. The note to 1926.402(a) deems an installation made in accordance with the National Electrical Code ANSI/NFPA 70-1984 in compliance with 1926.403 through 1926.408, except for 1926.404(b)(1) and 1926.405(a)(2)(ii)(E), (F), (G) and (J); a later NEC edition is not presumed adopted. Paragraph (j) covers equipment for general use, including lighting fixtures, lampholders, lamps and receptacles, motors, transformers and capacitors. 1926.404(f) and the particular provisions govern grounding. Temporary wiring is removed immediately upon completion of the construction or of the purpose for which it was installed ((a)(2)(i)).

The regulatory text

“Unless necessary for a use permitted in paragraph (g)(1)(i) of this section, flexible cords and cables shall not be used: (A) As a substitute for the fixed wiring of a structure; …”
29 CFR 1926.405(g)(1)(iii)

Key facts about 29 CFR 1926.405

  • Flexible cords and cables may not be used as a substitute for the fixed wiring of a structure (1926.405(g)(1)(iii)).
  • Cords may not be run through holes in walls, ceilings or floors, attached to building surfaces or concealed in the structure; passing through a doorway or pinch point is allowed if protection avoids damage (1926.405(g)(1)(iii), (a)(2)(ii)(I)).
  • Conductors entering boxes, cabinets and fittings must be protected from abrasion, openings closed, pull and junction boxes covered (metal covers grounded), and outlet boxes covered in energized installations (1926.405(b)(1)-(2)).
  • Flexible cords may be used only in continuous lengths without splice or tap; hard service cords No. 12 or larger may be repaired by a splice that keeps the insulation, outer sheath properties and usage characteristics (1926.405(g)(2)(iii)).
  • Temporary wiring is removed immediately upon completion of construction or of the purpose it served ((a)(2)(i)). Feeders originate in a distribution center and branch circuits in a power outlet or panelboard, with overcurrent devices at the conductors' ampacity; receptacles are the grounding type, with a separate equipment grounding conductor in each branch circuit unless in a complete metallic raceway; each temporary circuit has a switch or plug connector that disconnects all ungrounded conductors; general-illumination lamps are protected from contact or breakage ((a)(2)(ii)(A)-(E)). Lights are not hung by their cords unless designed for it; portable lighting in wet or conductive locations runs at 12 V or less, or 120 V with a GFCI; cords are protected from damage and sharp corners; extension cord sets are three-wire, hard or extra-hard usage ((a)(2)(ii)(F)-(J)).
  • Nonmetallic-sheathed cable (type NM) may be used as temporary wiring, secured by fittings designed and installed so as not to damage the cable (OSHA letter of October 4, 2000); NM cable and an extension cord are not the same.
  • Grounding is covered by 1926.404(f) and the particular provisions.

Scope: who 29 CFR 1926.405 applies to

Regulatory framework
Construction (29 CFR 1926)
Citation reference
29 CFR 1926.405
Enforcement status
In force and enforced
Jurisdiction
Federal OSHA (29 State-Plan jurisdictions may be stricter)

State-Plan states (e.g. California, Washington, Michigan) operate OSHA-approved programs that must be at least as effective as federal OSHA and frequently impose higher penalties or additional requirements.

Key requirements of 29 CFR 1926.405

#What the section requires or covers
1Use listed and labeled electrical equipment
2Install temporary wiring per requirements
3Protect extension cords from damage
4Use proper cord connectors
5Remove temporary wiring when no longer needed

Summarized from the text of 29 CFR 1926.405.

Common Wiring Methods (Construction) violations

Deficiencies OSHA cites under 29 CFR 1926.405 include the ones below, in no particular order. Each serious item carries up to $16,550 (2026).

  • Flexible cords used as a substitute for fixed wiring (1926.405(g)(1)(iii)).
  • Cords run through holes in walls, ceilings or floors, or attached to building surfaces or concealed, where no permitted use applies (1926.405(g)(1)(iii)); a protected temporary cord through a doorway is permitted ((a)(2)(ii)(I)).
  • Open or missing covers on boxes and cabinets (1926.405(b)).
  • A flexible cord spliced or tapped outside the repair allowed for hard service cord No. 12 or larger (1926.405(g)(2)(iii)); conductors entering boxes not protected or openings not closed (1926.405(b)(1)).
  • Temporary wiring left in place after the work or purpose it served ended, or installed without the origin, grounding, disconnect and lamp protection that 1926.405(a)(2)(i)-(ii)(A)-(E) require.
  • Cords not protected from damage, or with sharp corners and projections not avoided (1926.405(a)(2)(ii)(I)); extension cord sets for portable tools not of the three-wire type designed for hard or extra-hard usage ((J)).

Cords, splices and doorways

1926.405(g)(1)(iii) has flexible cords and cables not used, unless necessary for a use permitted in (g)(1)(i), as a substitute for the fixed wiring of a structure, where run through holes in walls, ceilings or floors, attached to building surfaces, or concealed behind walls, ceilings or floors; where run through doorways, windows or similar openings, except as permitted in (a)(2)(ii)(I): flexible cords and cables may pass through doorways or other pinch points if protection is provided to avoid damage. Flexible cords are used only in continuous lengths without splice or tap, except that hard service flexible cords No. 12 or larger may be repaired by a splice that retains the insulation, outer sheath properties and usage characteristics of the cord ((g)(2)(iii)); a splice in a box is not the rule for every conductor. The permitted uses of (g)(1)(i) are pendants, wiring of fixtures, connection of portable lamps or appliances, elevator cables, wiring of cranes and hoists, connection of stationary equipment to facilitate their frequent interchange, prevention of the transmission of noise or vibration, and appliances designed to permit removal for maintenance and repair.

What OSHA inspectors look for

A compliance officer looks for extension cords used as permanent wiring or run through walls, open or missing box covers, damaged cord insulation, and improper cord splices; a temporary cord that passes through a doorway is acceptable when protection prevents damage ((a)(2)(ii)(I)). Flexible cords have permitted uses (g)(1)(i), and the prohibited uses of (g)(1)(iii) apply unless a permitted use is necessary.

Example: how a violation is cited

Hypothetical case: a crew wires temporary lighting into a partially built structure using extension cords stapled along the framing. 1926.405(g)(1)(iii) has flexible cords and cables not used as a substitute for the fixed wiring of a structure, or attached to building surfaces, unless necessary for a use permitted in (g)(1)(i); (a)(2)(ii)(I) has flexible cords and cables protected from damage. A serious violation carries a penalty of up to $16,550.

Illustrative example, not a specific OSHA case.

Wiring Methods (Construction) compliance checklist

Each item is a requirement of 29 CFR 1926.405 that OSHA may verify during an inspection.

  • Do not use flexible cords and cables as a substitute for the fixed wiring of a structure unless necessary for a use permitted in (g)(1)(i) (1926.405(g)(1)(iii)(A)).
  • Do not run flexible cords through holes in walls, ceilings or floors, attach them to building surfaces, or conceal them; a temporary cord through a doorway needs protection against damage (1926.405(g)(1)(iii), (a)(2)(ii)(I)).
  • Protect conductors entering boxes, cabinets, or fittings from abrasion and effectively close the openings, including unused openings; provide covers on all pull boxes, junction boxes, and fittings, grounded if metal (1926.405(b)(1)-(2)).
  • Splice flexible cords only as 1926.405(g)(2)(iii) allows (hard service No. 12 or larger, splice keeping insulation, sheath and usage characteristics).
  • Install temporary wiring as 1926.405(a)(2) provides: feeders from a distribution center, branch circuits from a power outlet or panelboard with overcurrent protection at ampacity, grounding-type receptacles with an equipment grounding conductor, a disconnect for each temporary circuit, protected lamps, no lights hung by their cords unless designed for it, 12 V or 120 V with a GFCI for portable lighting in wet or conductive locations, cords protected from damage and sharp corners, three-wire hard or extra-hard usage cord sets; remove the wiring immediately when the work or its purpose ends.
  • Use extension cord sets of the three-wire type designed for hard or extra-hard usage with portable tools and appliances, protect flexible cords from damage, and use temporary lights hung by their cords only if designed for it (1926.405(a)(2)(ii)(F), (I), (J)).

2026 penalties for 29 CFR 1926.405

Maximums set by 29 CFR 1903.15(d). 2026 maximums unchanged from 2025 (no CPI adjustment; OMB M-26-11), so not an increase; the serious and repeat policy minimums were revised with FOM chapter 6 (OSHA memo of May 21, 2026). The 2025 OSHA penalty levels remain in effect for 2026; OSHA made no inflation adjustment for 2026. 29 CFR 1903.15 identifies January 15, 2025 as the effective reference for these amounts, while OSHA's public penalties page currently references penalties assessed after Jan. 15, 2026.

Violation typeMinimumMaximumWhen it applies
Serious$1,085$16,550Death or serious physical harm could result, and the employer knew or could have known (29 U.S.C. 666(k)).
Other-Than-Serious$0$16,550Relates to safety/health but unlikely to cause death or serious harm.
Willful$11,823$165,514Intentional, knowing, or voluntary disregard of the requirement.
Repeated$4,256$165,514A substantially similar violation cited within the last 5 years.
Failure to AbateNone$16,550/dayup to $16,550 per day; the total is normally capped at 30 times the daily amount (FOM Ch.6)

Serious violations reach $16,550 and willful or repeat violations $165,514.

Maximums and the willful minimum are set by 29 CFR 1903.15(d); the serious and repeated minimums are OSHA policy floors from its annual penalty adjustment memo. OSHA applies gravity-based and size, good-faith and history reductions (FOM CPL 02-00-164 Ch.6). Estimates only, not legal advice.

The business case for Wiring Methods (Construction) compliance

1926.405(g)(1)(iii) has flexible cords and cables not used, unless necessary for a use permitted in (g)(1)(i), as a substitute for the fixed wiring of a structure, or where run through holes in walls, ceilings or floors, run through doorways, windows or similar openings except as (a)(2)(ii)(I) permits, attached to building surfaces, or concealed behind walls, ceilings or floors. The regulation is not a guarantee that temporary power is as safe as permanent wiring.

State plans and their penalty rules

States listed by the volume of their federal construction citations, not by this standard. Penalties and enforcement vary by state. State-Plan states may impose higher penalties and additional requirements beyond federal 29 CFR 1926.405.

State pages for 29 CFR 1926.405

Frequently asked questions about 29 CFR 1926.405

Can extension cords be used as permanent wiring on a construction site?

No. Under 1926.405(g)(1)(iii), flexible cords and cables may not be used as a substitute for the fixed wiring of a structure, run through holes in walls, ceilings or floors, or attached to building surfaces, unless necessary for a permitted use; a temporary cord may pass through a doorway if protection avoids damage ((a)(2)(ii)(I)). The permitted uses of (g)(1)(i) include connection of portable lamps or appliances, elevator cables, wiring of cranes and hoists, connection of stationary equipment to facilitate their frequent interchange, and prevention of the transmission of noise or vibration.

What does 1926.405 require for boxes and splices?

Under 1926.405(b), conductors entering boxes, cabinets and fittings must be protected from abrasion with the openings effectively closed, unused openings closed, pull and junction boxes and fittings provided with covers (metal covers grounded), and outlet boxes in energized installations given a cover, faceplate or fixture canopy. The splice rule is in (g)(2)(iii) and concerns flexible cords: continuous lengths without splice or tap, except that hard service cords No. 12 or larger may be repaired with a splice that keeps the insulation, sheath and usage characteristics.

What is the difference between 1926.405 and 1926.404?

1926.404 covers wiring design and protection: conductor identification and polarity, branch circuits with the choice between GFCIs and an assured equipment grounding conductor program, outside conductors, services, overcurrent protection and grounding. 1926.405 covers wiring methods, components, and equipment for general use, such as temporary wiring, boxes, flexible cords and splices. They are separate sections of Subpart K.

How is 1926.405 different from general industry's 1910.305?

1926.405 applies to construction work and 1910.305 to general industry; the general industry provisions are not applied automatically to construction.

Regulatory history of 29 CFR 1926.405

1926.405 is in Subpart K (Electrical). Its source note lists 51 FR 25318 (July 11, 1986), 61 FR 5510 (February 13, 1996) and 85 FR 8736 (February 18, 2020). The note to 1926.402(a) refers to the 1984 edition of the National Electrical Code.

Related glossary terms

Key terms that appear in 29 CFR 1926.405, each with a full plain-English explainer.

Get the Binder in Order Before the Inspector Arrives. Are You Ready?

OSHA inspections come unannounced, apart from the few exceptions listed in 29 CFR 1903.6. Get the binder in order before the opening conference, not during it.

Serious Violation

$16,550

per violation (max)

HazComFast Pro

$199/mo

10 jobsites, unlimited chemicals, unlimited workers

New sign-ups are paused. The free tools below need no account, and customers can log in as usual.

Your account keeps working as usual. Cancel anytime.