What 29 CFR 1926.150 requires (plain English)
29 CFR 1926.150 sets the fire protection requirements for construction and demolition. It has the employer develop a fire protection program followed throughout all phases of the work, and to provide firefighting equipment as fire hazards arise, without delay.
The standard sets measurable extinguisher rules. A fire extinguisher rated not less than 2A is needed for each 3,000 square feet of protected building area or major fraction thereof, with travel distance from any point to the nearest extinguisher not over 100 feet; at least one 2A extinguisher on each floor, and in a multistory building one adjacent to a stairway; a 10B extinguisher within 50 feet of wherever more than 5 gallons of flammable or combustible liquids or 5 pounds of flammable gas are being used (not integral vehicle fuel tanks); and listed or approved extinguishers, periodically inspected and maintained to NFPA 10A, protected from freezing (1926.150(c)(1)). A 55-gallon open drum of water with two fire pails, or a garden-type hose line of 1/2 inch, up to 100 feet, discharging at least 5 gallons per minute with a 30-foot stream, mounted on racks or reels so one stream reaches all points, may substitute for a 2A extinguisher, and 100 feet or less of 1 1/2 inch hose with a nozzle of 25 gallons per minute or more may substitute where it reaches all points ((c)(1)(ii)-(iii), (c)(2)(i)). A temporary or permanent water supply of sufficient volume, duration and pressure must be made available as soon as combustible materials accumulate ((b)(1)). Standpipes are addressed in (d)(2): in structures in which standpipes are required, or where they exist in structures being altered, they are brought up as soon as applicable laws permit and maintained ready for use as construction progresses; whether a given building needs one is a question of the applicable laws, not simply of the number of stories. An alarm system must be established so employees on the site and the local fire department can be alerted, with the alarm code and reporting instructions conspicuously posted at phones and employee entrances ((e)(1)-(2)). As fire hazards occur, there is no delay in providing the necessary equipment ((a)(1)). Access to all available firefighting equipment is maintained at all times, it is conspicuously located, periodically inspected and maintained in operating condition, and defective equipment is immediately replaced ((a)(2)-(4)). As warranted by the project, the employer provides a trained and equipped firefighting organization (fire brigade) to assure adequate protection to life ((a)(5)); this does not make every employee a firefighter. Where underground water mains are to be provided, they are installed, completed and made available as soon as practicable ((b)(2)). Carbon tetrachloride and other toxic vaporizing liquid fire extinguishers are prohibited ((c)(1)(vii)). If the facility includes automatic sprinkler protection, the installation closely follows the construction and is placed in service as soon as applicable laws permit following completion of each story; during demolition or alterations, existing automatic sprinkler installations are retained in service as long as reasonable, sprinkler control valves are operated only by properly authorized persons and are checked daily at close of work ((d)(1)). Fire walls and exit stairways required for the completed buildings are given construction priority, and fire doors with automatic closing devices are hung as soon as practicable ((f)(1)). The employer's emergency action plan and the fire protection program of 1926.150 are different documents; the 1910.39 requirements are not imported.
1926.150 is in Subpart F (fire protection and prevention); the flammable-liquid (1926.152), LP-gas, 1926.151 (fire prevention) and 1926.153 and 1926.352 provisions have their own requirements.