What 29 CFR 1910.160 requires (plain English)
29 CFR 1910.160 sets the general requirements that apply to all fixed extinguishing systems installed to meet a particular OSHA standard, except for automatic sprinkler systems, which are covered separately by 1910.159. It also reaches fixed systems not installed to meet an OSHA standard but whose operation may expose employees to injury, death or adverse health effects from the extinguishing agent, though only paragraphs (b)(4) through (b)(7) and (c) apply to them, and those in areas with no employee exposure are exempt ((a)(2)-(3)). Fixed extinguishing systems are the built-in suppression systems (carbon dioxide, dry chemical, gaseous (clean) agent, water spray, and foam) that protect a specific hazard or total-flood an enclosed area.
Because some of these agents are themselves dangerous to people, the standard's central protections address employee safety around discharge. Where discharge of a total-flooding agent can produce a hazardous atmosphere (for example, CO2 or other oxygen-displacing agents), a total flooding system must provide a pre-discharge employee alarm that gives employees time to exit before discharge, with automatic actuation by an approved detection device interconnected with that alarm ((c)(3)-(4)), along with other safeguards. The standard also requires that systems be designed for the hazard, be inspected and maintained, have their container weight and pressure checked at least semi-annually, and that employees designated to inspect, maintain, operate or repair the systems be trained.
1910.160 is the general fixed-system rule; the agent-specific sections follow it: dry chemical (1910.161), gaseous agent (1910.162), and water spray and foam (1910.163).