Skip to content

Approaching: Feb 1, 2027 — 300A Posting Begins. Get ready →

General Industry (29 CFR 1910)

Storage and Handling of Liquefied Petroleum Gases

Verified vs OSHA sources · 2026-10-19

29 CFR 1910.110

29 CFR 1910.110 governs the storage and handling of liquefied petroleum gases (propane and similar fuels): LP-gas is effectively odorized so that its presence is indicated by distinct odor down to one-fifth of the lower limit of flammability (unless odorizing is harmful in the use or further processing, or serves no useful warning purpose), and containers, valves, regulators, and piping are approved or listed for the system, located at the distances of Table H-23, and tested after assembly.

29 CFR 1910.110 at a glance

What it requires
Safe storage and handling of LP-gas: odorization, approved containers, proper location, and leak/ignition protection
Who it covers
General-industry employers storing or using LP-gas (propane)
Odorization rule
LP-gas is odorized so its presence is indicated by distinct odor down to one-fifth of the lower limit of flammability, except where odorizing is harmful in the use or further processing or serves no useful warning purpose (1910.110(b)(1)(i))
Key duty
Use approved containers and valves, locate them safely, and protect against leaks and ignition
Max penalty (2026)
$16,550 per serious violation; $165,514 per willful
Common confusion
LP-gas odorization has exceptions (1910.110(b)(1)(i))

What 29 CFR 1910.110 requires (plain English)

29 CFR 1910.110 sets requirements for the storage and handling of liquefied petroleum gases: propane, butane, and similar fuels used for heating, forklifts, and equipment. It covers containers, valves, regulators, piping, and their location. It does not apply to marine and pipeline terminals, natural gas processing plants, refineries, or tank farms other than those at industrial sites; to LP-gas refrigerated storage systems; to LP-gas used with oxygen, which falls under 1910.253; to utility gas plants; or to certain low-pressure piping systems and the appliances they supply ((i)(2)).

LP-gas must be effectively odorized by an approved agent so that its presence is indicated by distinct odor down to one-fifth of the lower limit of flammability. Odorization is not required if it is harmful in the use or further processing of the gas, or serves no useful purpose as a warning agent in that use or processing (1910.110(b)(1)(i)). Containers and appliances are approved, and containers are located at the distances Table H-23 sets from the nearest important building or group of buildings ((b)(6)(ii)). All piping, tubing, or hose is tested after assembly and proved free from leaks at not less than normal operating pressures, and the test is not made with a flame ((b)(8)(ix)). Portable containers of not more than 1,000 pounds water capacity awaiting use or resale follow paragraph (f): outlet valves closed, valves protected, and, inside buildings, empty containers that have been in LP-gas service counted as full for the maximum quantity; in buildings not frequented by the public, such as industrial buildings, stored LP-gas does not exceed 300 pounds except in special buildings or rooms, which have walls, floors and ceilings with at least a 2-hour fire resistance rating where they are within or adjacent to other parts of the building ((f)(4)-(5)).

1910.110 sits in Subpart H (hazardous materials) with the other gas standards. It incorporates specific NFPA consensus standards for certain installations (for example NFPA 54 for appliance installations and NFPA 505 for LP-gas fueled industrial trucks) and recognizes containers built to the NFPA 58 edition in effect at their fabrication (1910.110(b)(3)(iv)); other containers meet the 1968 ASME code ((b)(3)(i)).

The regulatory text

“All liquefied petroleum gases shall be effectively odorized by an approved agent of such character as to indicate positively, by distinct odor, the presence of gas down to concentration in air of not over one-fifth the lower limit of flammability. Odorization, however, is not required if harmful in the use of further processing of the liquefied petroleum gas, or if odorization will serve no useful purpose as a warning agent in such use or further processing.”
29 CFR 1910.110(b)(1)(i)

Key facts about 29 CFR 1910.110

  • LP-gas must be effectively odorized so its presence is indicated by distinct odor down to one-fifth of the lower limit of flammability (1910.110(b)(1)(i)). NIOSH publication 2021-106 says the odorant can fade, and the NIOSH Pocket Guide lists propane as an odorless gas in pure form with a relative gas density of 1.55.
  • Approval depends on the system: DOT containers (49 CFR part 178) need approved valves, connectors, manifold valve assemblies and regulators; domestic or commercial systems of 2,000 gallons or less need the container assembly or whole system and the regulators individually listed; containers over 2,000 gallons need each regulator, container valve, excess flow valve, gaging device and relief valve listed by a nationally recognized testing laboratory (1910.110(b)(2)(i)-(iii)).
  • Containers are located by Table H-23 with respect to the nearest important building or group of buildings (by water capacity, with notes for aggregate capacity and conditional reductions), and between aboveground containers; the table does not use property lines as its reference (1910.110(b)(6)(ii)).
  • Table H-23 minimum distances to the nearest important building or group of buildings (underground / aboveground), then between aboveground containers: under 125 gal, 10 ft / none / none; 125 to 250 gal, 10 / 10 / none; 251 to 500 gal, 10 / 10 / 3 ft; 501 to 2,000 gal, 25 / 25 / 3 ft; 2,001 to 30,000 gal, 50 / 50 / 5 ft; 30,001 to 70,000 gal, 50 / 75 / one quarter of the sum of the diameters of adjacent containers; 70,001 to 90,000 gal, 50 / 100 / the same quarter-sum rule. At a consumer site with several containers totalling 501 gal or more, apply the aggregate capacity and keep each installation at least 25 ft from another; the 25 ft for 501 to 2,000 gal can be reduced to 10 ft for a single container of 1,200 gal or less that is at least 25 ft from any other container over 125 gal (1910.110(b)(6)(ii), Table H-23 notes).
  • Containers awaiting use or resale: the outlet valves of containers in storage are closed (1910.110(f)(2)(iv)), and empty containers that have been in LP-gas service count as full containers when stored inside ((f)(2)(v)).
  • Storage within buildings not frequented by the public (such as industrial buildings): the quantity of LP-Gas stored does not exceed 300 pounds, except in special buildings or rooms (1910.110(f)(4)(i)).
  • The standard incorporates specific NFPA standards for named uses, accepts containers built to the NFPA 58 edition in effect at fabrication (1910.110(b)(3)(iv)), and requires others to meet the ASME code (b)(3)(i); it does not adopt the current NFPA 58 as a whole.
  • It is part of Subpart H alongside the other compressed-gas standards.

Scope: who 29 CFR 1910.110 applies to

Regulatory framework
General Industry (29 CFR 1910)
Citation reference
29 CFR 1910.110
Enforcement status
In force and enforced
Jurisdiction
Federal OSHA (29 State-Plan jurisdictions may be stricter)

State-Plan states (e.g. California, Washington, Michigan) operate OSHA-approved programs that must be at least as effective as federal OSHA and frequently impose higher penalties or additional requirements.

Key requirements of 29 CFR 1910.110

#What the section requires or covers
1Use containers that meet the DOT or ASME specifications 1910.110 sets for LP-gas containers
2Install the pressure relief devices 1910.110 requires on containers and systems
3Keep the separation distances 1910.110 sets between containers, buildings, property lines and sources of ignition
4Test piping and hose for leaks after assembly and before the system is put in service, as 1910.110 requires
5At LP-gas service stations: no smoking on the driveway in dispensing areas or transport truck unloading areas, and conspicuous no-smoking signs within sight of the customer being served, with letters not less than 4 inches high (1910.110(h)(12))

Summarized from the text of 29 CFR 1910.110.

Common LP-Gas Storage violations

Deficiencies OSHA cites under 29 CFR 1910.110 include the ones below, in no particular order. Each serious item carries up to $16,550 (2026).

  • LP-gas not effectively odorized where odorization is required (1910.110(b)(1)(i)).
  • Container closer than Table H-23 allows to the nearest important building or group of buildings for its water capacity and installation (1910.110(b)(6)(ii)).
  • Outlet valves of containers in storage not closed (1910.110(f)(2)(iv)).
  • More than 300 pounds of LP-gas stored in a building not frequented by the public (1910.110(f)(4)(i)).
  • System components not approved or listed as the system class requires: DOT container valves and regulators; listed assembly and regulators of 2,000 gallons or less; laboratory-listed fittings on containers over 2,000 gallons (1910.110(b)(2)(i)-(iii)).

Odorization of LP-gas

1910.110(b)(1)(i): all liquefied petroleum gases are effectively odorized by an approved agent of such character as to indicate positively, by distinct odor, the presence of gas down to concentration in air of not over one-fifth the lower limit of flammability. Odorization, however, is not required if harmful in the use or further processing of the liquefied petroleum gas, or if odorization will serve no useful purpose as a warning agent in such use or further processing.

What OSHA inspectors look for

A compliance officer checks that LP-gas containers and components are approved or listed as the system class requires, located at the Table H-23 distances from the nearest important building or group of buildings (by the container's water capacity), kept away from ignition sources and fitted with proper relief valves, that stored containers follow paragraph (f), and that the gas is odorized where required.

Example: how a violation is cited

Hypothetical case: a 1,500-gallon aboveground propane container is installed 15 feet from the nearest important building. Table H-23 sets 25 feet for 501 to 2,000 gallons of water capacity (1910.110(b)(6)(ii)). A serious violation carries a penalty of up to $16,550.

Illustrative example, not a specific OSHA case.

LP-Gas Storage compliance checklist

Each item is a requirement of 29 CFR 1910.110 that OSHA may verify during an inspection.

  • Ensure LP-gas is effectively odorized by an approved agent, unless odorizing is harmful in the use or further processing or serves no useful warning purpose (1910.110(b)(1)(i)).
  • Use containers, valves, regulators, and appliances approved or listed as the system class requires (1910.110(b)(2)), and test piping, tubing and hose after assembly at not less than normal operating pressure, never with a flame ((b)(8)(ix)).
  • Record each container's water capacity, number of containers and aggregate capacity, then locate it per Table H-23 from the nearest important building or group of buildings and from other aboveground containers, and keep it away from ignition sources.
  • Close the outlet valves of containers in storage (1910.110(f)(2)(iv)).
  • Keep stored LP-gas within 300 pounds in buildings not frequented by the public, counting empty containers that have been in service as full, except in special buildings or rooms (1910.110(f)(2)(v), (f)(4)-(5)).
  • Uses outside the section include LP-gas refrigerated storage systems and LP-gas used with oxygen, which falls under 1910.253 (1910.110(i)(2)).

Import your chemical list from a spreadsheet, with hazard words or GHS codes, and each product lands with its pictograms, in the flammables total and the hazard filters. Export it and re-import it, and nothing is lost. Chemical inventory in HazComFast

2026 penalties for 29 CFR 1910.110

Maximums set by 29 CFR 1903.15(d). 2026 maximums unchanged from 2025 (no CPI adjustment; OMB M-26-11), so not an increase; the serious and repeat policy minimums were revised with FOM chapter 6 (OSHA memo of May 21, 2026). The 2025 OSHA penalty levels remain in effect for 2026; OSHA made no inflation adjustment for 2026. 29 CFR 1903.15 identifies January 15, 2025 as the effective reference for these amounts, while OSHA's public penalties page currently references penalties assessed after Jan. 15, 2026.

Violation typeMinimumMaximumWhen it applies
Serious$1,085$16,550Death or serious physical harm could result, and the employer knew or could have known (29 U.S.C. 666(k)).
Other-Than-Serious$0$16,550Relates to safety/health but unlikely to cause death or serious harm.
Willful$11,823$165,514Intentional, knowing, or voluntary disregard of the requirement.
Repeated$4,256$165,514A substantially similar violation cited within the last 5 years.
Failure to AbateNone$16,550/dayup to $16,550 per day; the total is normally capped at 30 times the daily amount (FOM Ch.6)

Serious violations reach $16,550 and willful or repeat violations $165,514.

Maximums and the willful minimum are set by 29 CFR 1903.15(d); the serious and repeated minimums are OSHA policy floors from its annual penalty adjustment memo. OSHA applies gravity-based and size, good-faith and history reductions (FOM CPL 02-00-164 Ch.6). Estimates only, not legal advice.

The business case for LP-Gas Storage compliance

1910.110(b)(1)(i) has LP-gas odorized so that its presence is indicated by distinct odor down to a concentration in air of not over one-fifth the lower limit of flammability, except where odorization is harmful in the use or further processing of the gas or serves no useful purpose as a warning agent.

State plans and their penalty rules

States listed by the volume of their federal construction citations, not by this standard. Penalties and enforcement vary by state. State-Plan states may impose higher penalties and additional requirements beyond federal 29 CFR 1910.110.

Frequently asked questions about 29 CFR 1910.110

Does LP-gas have to be odorized?

Yes, with an exception. Under 1910.110(b)(1)(i), liquefied petroleum gases must be effectively odorized by an approved agent so their presence is indicated by distinct odor down to one-fifth of the lower limit of flammability. Odorization is not required if it is harmful in the use or further processing of the gas or serves no useful purpose as a warning agent in that use or processing.

Why does NIOSH say not to rely on smell for propane?

NIOSH publication 2021-106 says the odorant in propane can fade, including when the gas contacts soil, concrete, and a wide variety of building materials, and recommends that responders use gas detection equipment and not rely on their sense of smell.

Where can LP-gas containers be located?

Under 1910.110(b)(6), LP-gas containers are generally located outside buildings, each the Table H-23 distance or more from the nearest important building or group of buildings (depending on the container's water capacity, with notes for multi-container aggregate capacity and conditional reductions) and from other aboveground containers, and away from ignition sources. The distances come from Table H-23 and its notes.

Which LP-gas equipment is approved?

Under 1910.110(b)(2), approval depends on the system class: DOT containers need approved valves, connectors, manifold valve assemblies and regulators; systems of 2,000 gallons or less need the container assembly or system and the regulators listed; containers over 2,000 gallons need each regulator, container valve, excess flow valve, gaging device and relief valve listed by a nationally recognized testing laboratory.

Regulatory history of 29 CFR 1910.110

1910.110 was published at 39 FR 23502 (June 27, 1974) and last amended at 72 FR 71069 (December 14, 2007), according to the eCFR source note.

Related glossary terms

Key terms that appear in 29 CFR 1910.110, each with a full plain-English explainer.

Get the Binder in Order Before the Inspector Arrives. Are You Ready?

OSHA inspections come unannounced, apart from the few exceptions listed in 29 CFR 1903.6. Get the binder in order before the opening conference, not during it.

Serious Violation

$16,550

per violation (max)

HazComFast Pro

$199/mo

10 jobsites, unlimited chemicals, unlimited workers

New sign-ups are paused. The free tools below need no account, and customers can log in as usual.

Your account keeps working as usual. Cancel anytime.