At a glance
- Construction: GFCIs or an assured equipment grounding conductor program, 29 CFR 1926.404(b)(1); flexible cords, 29 CFR 1926.405(a)(2)(ii) and (g); worn or frayed cords, 29 CFR 1926.416(e)(1).
- About 5 minutes to read the script out loud, then the three questions. The drill and the tables below add time if you use them.
- FY2025 citations: 29 CFR 1926.404, 142 (139 at construction sites); 29 CFR 1926.405, 387 (368 at construction sites); 29 CFR 1926.416, 394 (374 at construction sites).
- Free PDF and Word file: the script, the questions, the rule and a 20-line sign-in sheet. No account, no email.
Read this to your crew
Today is extension cords. A cord on a jobsite can get dragged over concrete, run over, pinched in a door or left in a puddle, and the damage is not always visible from a few feet away.
Before you plug in, run the cord through your hands from plug to plug. Look for cuts, crushed spots, bare wire, a jacket pulled out of the plug, a missing or bent ground pin, melted or burned plastic, and tape. Tape is not a repair. A cord with any of that comes out of service: unplug it, tag it and bring it to me.
Use a cord made for the job: a three-wire cord rated for hard or extra-hard use, long enough to reach without chaining cords together, and heavy enough for the tool. The marking is printed on the jacket.
Protect the run. Keep cords out of water, off sharp edges and out of doorways unless they are protected there. Do not hang them on nails or staple them. Where trucks or carts cross, run the cord overhead or under a cover.
Plug into GFCI protection, or into the circuits our assured grounding program covers. A GFCI cuts the power in a fraction of a second when current leaks to ground, through a person for example. It does not protect you if you touch two wires at once or an overhead line, and it does not make a damaged cord safe. Test it the way its maker describes before use. If it trips, something is wrong: unplug the tool and the cord and look for the fault. Do not keep resetting it until it holds.
When you are done, unplug by the plug, not the cord, coil it loosely and hang it off the floor.
Three questions for the crew
- What would take a cord out of service today?
Listen for: Cuts, crushed or bare spots, a missing or bent ground pin, a damaged plug, burn marks, or a taped splice. - What do you do when a GFCI trips?
Listen for: Stop, unplug, look for the fault in the tool, the cord or the connection, and report it. No resetting again and again. - Where on this site do cords cross a path, a doorway or water?
Listen for: Specific spots, and how each one is protected: overhead, under a cover, or rerouted.
What are OSHA's rules for extension cords and GFCIs?
In construction, the employer shall use either ground-fault circuit interrupters or an assured equipment grounding conductor program to protect employees (29 CFR 1926.404(b)(1)(i)). All 120-volt, single-phase, 15- and 20-ampere receptacle outlets that are not part of the permanent wiring of the building or structure and are in use by employees shall have approved GFCIs, with an exception for small two-wire generators rated not more than 5kW that meet the rule's conditions (29 CFR 1926.404(b)(1)(ii)).
Under an assured equipment grounding conductor program, cord sets, plugs, receptacles and cord-and-plug equipment are visually inspected before each day's use, and damaged equipment is not used until repaired (29 CFR 1926.404(b)(1)(iii)(C)). The tests are performed before first use, after repairs, after any incident that may have caused damage, and at intervals not to exceed 3 months, or 6 months for fixed cord sets and receptacles not exposed to damage (29 CFR 1926.404(b)(1)(iii)(E)), and they are recorded by logs, color coding or other effective means (29 CFR 1926.404(b)(1)(iii)(G)).
Flexible cords shall be protected from damage, including where they pass through doorways or other pinch points (29 CFR 1926.405(a)(2)(ii)(I)), and extension cord sets used with portable electric tools shall be of three-wire type and designed for hard or extra-hard usage (29 CFR 1926.405(a)(2)(ii)(J)). Worn or frayed cords shall not be used, and extension cords shall not be fastened with staples, hung from nails or suspended by wire (29 CFR 1926.416(e)(1) and (e)(2)).
The paragraphs, word for word:
“(b) Branch circuits—(1) Ground-fault protection—(i) General. The employer shall use either ground fault circuit interrupters as specified in paragraph (b)(1)(ii) of this section or an assured equipment grounding conductor program as specified in paragraph (b)(1)(iii) of this section to protect employees on construction sites. These requirements are in addition to any other requirements for equipment grounding conductors.”
“(e) Cords and cables. (1) Worn or frayed electric cords or cables shall not be used.”
“(iii) Splices. Flexible cords shall be used only in continuous lengths without splice or tap. Hard service flexible cords No. 12 or larger may be repaired if spliced so that the splice retains the insulation, outer sheath properties, and usage characteristics of the cord being spliced.”
How often did OSHA cite these rules in FY2025?
| Standard | Construction sites | Other industries | All FY2025 citations |
|---|---|---|---|
| 29 CFR 1926.404GFCI or assured equipment grounding conductor programParagraph 1926.404(b)(1): 44 of these | 139 | 3 | 142 |
| 29 CFR 1926.405Wiring methods, temporary wiring and flexible cordsParagraph 1926.405(a)(2)(ii): 56 of these | 368 | 19 | 387 |
| 29 CFR 1926.416General requirements, including worn or frayed cordsParagraph 1926.416(e): 148 of these | 374 | 20 | 394 |
Citation items under 29 CFR issued Oct 1, 2024 to Sep 30, 2025, at federal and State Plan inspections, counted by HazComFast on U.S. Department of Labor enforcement data (extracted Oct 13, 2026). Construction means an inspection whose NAICS code starts with 23. The counts describe inspected establishments, not every employer.
Pre-use cord check
| Check | Pass | Take out of service |
|---|---|---|
| Jacket | Intact, no cuts or crushed spots | Cut, crushed, bare wire or inner insulation showing |
| Plug and ground pin | Ground pin present and straight, plug body intact | Pin missing or bent, plug cracked or loose |
| Connector and strain relief | The jacket is held firmly where it enters the plug and the connector | Jacket pulled out of the plug or the connector |
| Splices and tape | No splice, or a proper repair on a hard service cord No. 12 or larger | Tape over damage, or a splice that does not keep the insulation and the jacket |
| Marking | Hard or extra-hard usage, three-wire | A light household cord or a two-wire cord |
| GFCI | Trips on its test and resets | Does not trip on its test, or trips again and again in use |
A cord that fails goes out of service, with a tag, until it is repaired properly or replaced.
When the GFCI trips
- Stop work and let go of the tool.
- Unplug the tool, then the cord.
- Look for the cause: water in a connection, a damaged cord, a damaged tool.
- Take the damaged item out of service and tag it.
- Reset only when the cause has been found and removed.
- Report repeat trips to the supervisor, even when the cause is not clear.
If the site runs an assured grounding program instead
Some sites protect employees with an assured equipment grounding conductor program instead of GFCIs. The program is written and kept at the jobsite, competent persons run it, and every cord set, receptacle and cord-and-plug tool it covers is inspected before each day's use and tested on the schedule the rule sets (29 CFR 1926.404(b)(1)(iii)).
The test record can be a log or a color code, such as a colored tape on each tested cord for the period. If a cord carries an old color, or no color at all, it stays out of use until it is tested.