What 29 CFR 1910.36 requires (plain English)
29 CFR 1910.36 sets the design and construction requirements for exit routes: the permanent, continuous, and unobstructed paths of travel from any point in a workplace to a place of safety. It answers how many exit routes a workplace must have, how they must be arranged and separated, and how big they must be, so that employees can evacuate promptly during a fire or other emergency. It works with 1910.37 (maintenance and operational features) and the emergency action plan requirements of 1910.38.
The core design rule is redundancy: at least two exit routes must be available in a workplace to permit prompt evacuation, located as far apart as practical so that if one is blocked by fire or smoke the other remains usable. More than two are required when the number of employees, the size of the building, or the arrangement of the workplace means two would not allow everyone to evacuate safely. (A single exit route is allowed only where the number of employees, the size of the building, its occupancy, and the arrangement allow all employees to evacuate safely during an emergency.) Exit routes must be separated from other workplace areas by fire-resistant construction: generally a one-hour fire-resistance rating for buildings of three or fewer stories and two hours for four or more.
The standard also fixes the physical dimensions and features that make a route usable: an exit route must be at least 28 inches wide at all points (wider where the occupant load requires), with headroom of at least 7 feet 6 inches, and free of anything that could reduce its clear width. An exit door must be side-hinged, swing out in the direction of travel where serving high-hazard areas or 50+ occupants, and connect directly to the outside or to a safe area. These design requirements set the stage that 1910.37 then requires be kept unobstructed, lighted, and marked.