General Industry (29 CFR 1910)

Design and Construction Requirements for Exit Routes

Verified vs OSHA sources · 2026-10-19

29 CFR 1910.36

29 CFR 1910.36 sets the design and construction requirements for exit routes: each exit route is a permanent part of the workplace; at least two exit routes are available, located as far away as practical from each other, except where a single exit route lets all employees evacuate safely; an exit is separated by fire resistant materials; exit route doors open from the inside at all times without keys, tools, or special knowledge; and each exit discharge leads directly outside or to a street, walkway, refuge area, public way, or open space with access to the outside.

29 CFR 1910.36 at a glance

What it requires
Enough properly designed, separated exit routes to evacuate everyone safely
Number
At least two exit routes (more if the number of employees, building size, occupancy or arrangement requires); a single route where all employees can evacuate safely (1910.36(b))
Minimum size
Exit access at least 28 inches wide at all points (exit and discharge at least as wide when there is a single exit access); ceiling at least 7 ft 6 in, with projections no lower than 6 ft 8 in; capacity for the occupant load and not decreasing toward the discharge (1910.36(g)(1) and (g)(2))
Fire resistance
An exit is separated by materials with a one-hour fire resistance-rating if it connects three or fewer stories and a two-hour rating if it connects four or more (1910.36(a)(2))
Max penalty (2026)
$16,550 per serious violation; $165,514 per willful
Common confusion
Design (1910.36) is how routes are built; maintenance (1910.37) is keeping them usable

What 29 CFR 1910.36 requires (plain English)

29 CFR 1910.36 sets the design and construction requirements for exit routes: the permanent, continuous, and unobstructed paths of travel from any point in a workplace to a place of safety. It sets the number, arrangement, separation and dimensions of exit routes. It works with 1910.37 (maintenance and operational features) and the emergency action plan requirements of 1910.38. An employer demonstrating compliance with the exit-route provisions of NFPA 101 or the International Fire Code, 2009 editions, is deemed to comply with the corresponding requirements (1910.35).

At least two exit routes must be available in a workplace to permit prompt evacuation, located as far away as practical from each other so that if one is blocked by fire or smoke, employees can use the second ((b)(1)). More than two are required when the number of employees, the size of the building, its occupancy, or the arrangement of the workplace is such that all employees would not be able to evacuate safely ((b)(2)); a single exit route is permitted where all employees would be able to evacuate safely ((b)(3)). An exit is separated from other parts of the workplace by construction materials with a one-hour fire resistance-rating if the exit connects three or fewer stories and a two-hour rating if it connects four or more stories (1910.36(a)(2)). Openings into an exit are limited to those needed for access, and each is protected by a self-closing fire door, listed or approved by a nationally recognized testing laboratory, that remains closed or closes automatically on an alarm ((a)(3)).

The standard also fixes the physical dimensions of a route: the exit access must be at least 28 inches wide at all points (and the exit and exit discharge at least as wide when there is only one exit access), the ceiling at least 7 feet 6 inches high with any projection no lower than 6 feet 8 inches, the width sufficient for the maximum permitted occupant load of each floor, with the capacity never decreasing toward the exit discharge, and free of objects that reduce the width below the minimum (1910.36(g)(1) and (g)(2)). A door connecting a room to an exit route must be side-hinged, and must swing out in the direction of exit travel if the room is designed for more than 50 people or is a high hazard area (1910.36(e)). Employees must be able to open an exit route door from the inside at all times without keys, tools, or special knowledge, and exit route doors are free of any device or alarm that could restrict emergency use if it fails; a door may be locked from the inside only in mental, penal, or correctional facilities with supervisory personnel continuously on duty and a plan to remove occupants ((d)). Each exit discharge must lead directly outside or to a street, walkway, refuge area, public way or open space with access to the outside, large enough for the occupants likely to use it, and exit stairs that continue beyond the discharge level are interrupted at that level (1910.36(c)). An outdoor exit route has guardrails where a fall hazard exists, is covered where snow or ice is likely to accumulate unless it is removed before it presents a slipping hazard, is reasonably straight with smooth, solid, substantially level walkways, and has no dead-end longer than 20 feet ((h)).

The regulatory text

“At least two exit routes must be available in a workplace to permit prompt evacuation of employees and other building occupants during an emergency, except as allowed in paragraph (b)(3) of this section. The exit routes must be located as far away as practical from each other so that if one exit route is blocked by fire or smoke, employees can evacuate using the second exit route.”
29 CFR 1910.36(b)(1)

Key facts about 29 CFR 1910.36

  • At least two exit routes must be available, located as far apart as practical (1910.36(b)(1)).
  • More than two exit routes are required when the number of employees, the size of the building, its occupancy, or the arrangement of the workplace demands it (1910.36(b)(2)).
  • A single exit route is permitted where the number of employees, the size of the building, its occupancy, or the arrangement of the workplace lets all employees evacuate safely (1910.36(b)(3)).
  • An exit is separated by construction materials with a one-hour fire resistance-rating if it connects three or fewer stories and a two-hour rating if it connects four or more stories (1910.36(a)(2)).
  • The exit access must be at least 28 inches wide at all points and the ceiling at least 7 ft 6 in high, with projections no lower than 6 ft 8 in (1910.36(g)(1) and (g)(2)); the exit and discharge must be at least as wide as a single exit access; capacity may not decrease toward the discharge (1910.36(f)(2)).
  • Each exit route is a permanent part of the workplace (1910.36(a)(1)), and each exit discharge leads directly outside or to a street, walkway, refuge area, public way, or open space with access to the outside (1910.36(c)(1)).
  • An employer demonstrating compliance with the exit-route provisions of NFPA 101 or the International Fire Code, 2009 editions, is deemed to comply with the corresponding requirements of 1910.34, 1910.36 and 1910.37 (1910.35).
  • 1910.36 covers design; 1910.37 covers maintenance, safeguards and operational features.

Scope: who 29 CFR 1910.36 applies to

Regulatory framework
General Industry (29 CFR 1910)
Citation reference
29 CFR 1910.36
Enforcement status
In force and enforced
Jurisdiction
Federal OSHA (29 State-Plan jurisdictions may be stricter)

State-Plan states (e.g. California, Washington, Michigan) operate OSHA-approved programs that must be at least as effective as federal OSHA and frequently impose higher penalties or additional requirements.

Key requirements of 29 CFR 1910.36

#What the section requires or covers
1Exit routes must be permanent
2Exit access must be at least 28 inches wide
3Exits must be fire-resistant rated
4Exits must discharge outside the building

Summarized from the text of 29 CFR 1910.36.

Common Exit Route Design violations

Deficiencies OSHA cites under 29 CFR 1910.36 include the ones below, in no particular order. Each serious item carries up to $16,550 (2026).

  • Fewer exit routes than required for the number of employees, building size, occupancy or arrangement (1910.36(b)(1)-(2)).
  • Exit not separated by fire-resistant materials rated 1 hour (three stories or fewer) or 2 hours (four or more) (1910.36(a)(2)); exit route not permanent (a)(1); openings into the exit not limited or not protected by self-closing fire doors (a)(3).
  • Exit access narrower than 28 inches, ceiling under 7 ft 6 in or a projection below 6 ft 8 in, or a width or capacity that does not fit the occupant load or decreases toward the discharge (1910.36(g)(1) and (g)(2)). Exit discharge that does not lead directly outside or to a safe area (1910.36(c)).
  • Door connecting a room designed to be occupied by more than 50 people, or a high hazard area, to an exit route that does not swing out in the direction of exit travel (1910.36(e)(2)).
  • Exit route door that cannot be opened from the inside without keys, tools, or special knowledge, or that has a device or alarm that could restrict emergency use if it fails (1910.36(d)(1)-(2)).

Design (1910.36) vs. maintenance (1910.37)

1910.36 governs the design and construction of exit routes: their number and arrangement, the fire resistant separation of exits, their minimum dimensions (28 inches wide at the exit access, 7 ft 6 in ceiling; 1910.36(g)(1) and (g)(2)), and, at 1910.36(d), exit route doors that employees can open from the inside at all times without keys, tools, or special knowledge. 1910.37 governs maintenance, safeguards and operational features: routes kept free and unobstructed, adequately lighted, and marked with exit signs. The emergency action plan (1910.38) and fire prevention plan (1910.39) apply when another OSHA standard requires them.

What OSHA inspectors look for

A compliance officer checks that the building has enough exits for its occupancy, adequately separated, that a door connecting a room designed for more than 50 people, or a high hazard area, to an exit route swings out in the direction of exit travel (1910.36(e)(2)), that the exit access is at least 28 inches wide at all points, and the ceiling at least 7 ft 6 in high (a projection may come down to 6 ft 8 in) (1910.36(g)(1) and (g)(2)), and that exits carry the fire resistance-rating of (a)(2).

Example: how a violation is cited

Hypothetical case: a workspace whose number of employees, size and layout do not allow all employees to evacuate safely through one route is served by a single exit route. 1910.36(b)(1) has at least two exit routes available, except as allowed in (b)(3). A serious violation carries a penalty of up to $16,550.

Illustrative example, not a specific OSHA case.

Exit Route Design compliance checklist

Each item is a requirement of 29 CFR 1910.36 that OSHA may verify during an inspection.

  • Provide at least two exit routes (more if the number of employees, size, occupancy or arrangement requires), located as far apart as practical; a single route only where all employees can evacuate safely (1910.36(b)).
  • Separate each exit from other parts of the workplace with construction materials rated one hour (three or fewer stories connected) or two hours (four or more) (1910.36(a)(2)); limit openings into the exit and protect them with listed self-closing fire doors ((a)(3)).
  • Measure by segment: exit access at least 28 inches wide at all points, ceiling at least 7 ft 6 in (projections no lower than 6 ft 8 in), width and capacity for the floor's occupant load and not decreasing toward the discharge (1910.36(g)(1) and (g)(2)).
  • Confirm each exit route leads to a place of safety (outside, or a street/walkway/open space with outside access).
  • Use a side-hinged door to connect any room to an exit route, swinging out in the direction of exit travel if the room is designed to be occupied by more than 50 people or is a high hazard area (1910.36(e)); make exit route doors openable from the inside at all times without keys, tools, or special knowledge (1910.36(d)).
  • Coordinate the design with 1910.37 maintenance and the 1910.38 emergency action plan.

2026 penalties for 29 CFR 1910.36

Maximums set by 29 CFR 1903.15(d). 2026 maximums unchanged from 2025 (no CPI adjustment; OMB M-26-11), so not an increase; the serious and repeat policy minimums were revised with FOM chapter 6 (OSHA memo of May 21, 2026). The 2025 OSHA penalty levels remain in effect for 2026; OSHA made no inflation adjustment for 2026. 29 CFR 1903.15 identifies January 15, 2025 as the effective reference for these amounts, while OSHA's public penalties page currently references penalties assessed after Jan. 15, 2026.

Violation typeMinimumMaximumWhen it applies
Serious$1,085$16,550Death or serious physical harm could result, and the employer knew or could have known (29 U.S.C. 666(k)).
Other-Than-Serious$0$16,550Relates to safety/health but unlikely to cause death or serious harm.
Willful$11,823$165,514Intentional, knowing, or voluntary disregard of the requirement.
Repeated$4,256$165,514A substantially similar violation cited within the last 5 years.
Failure to AbateNone$16,550/dayup to $16,550 per day; the total is normally capped at 30 times the daily amount (FOM Ch.6)

Serious violations reach $16,550 and willful or repeat violations $165,514.

Maximums and the willful minimum are set by 29 CFR 1903.15(d); the serious and repeated minimums are OSHA policy floors from its annual penalty adjustment memo. OSHA applies gravity-based and size, good-faith and history reductions (FOM CPL 02-00-164 Ch.6). Estimates only, not legal advice.

The business case for Exit Route Design compliance

1910.36(b)(1) has the exit routes located as far away as practical from each other so that if one exit route is blocked by fire or smoke, employees can evacuate using the second exit route.

Free compliance tools for 29 CFR 1910.36

State plans and their penalty rules

States listed by the volume of their federal construction citations, not by this standard. Penalties and enforcement vary by state. State-Plan states may impose higher penalties and additional requirements beyond federal 29 CFR 1910.36.

State pages for 29 CFR 1910.36

Frequently asked questions about 29 CFR 1910.36

How many exit routes does a workplace need?

At least two, under 1910.36(b)(1): located as far apart as practical so that if one is blocked by fire or smoke, employees can use the other. More than two are required when the number of employees, the size of the building, or its arrangement means two would not allow everyone to evacuate safely. A single exit route is permitted where the number of employees, the size of the building, its occupancy, or the arrangement of the workplace is such that all employees would be able to evacuate safely during an emergency (1910.36(b)(3)).

What are the minimum size requirements for an exit route?

Under 1910.36(g), the exit access must be at least 28 inches wide at all points (the exit and exit discharge at least as wide when there is only one exit access), wide enough for the maximum permitted occupant load of each floor, and the ceiling must be at least 7 feet 6 inches high, with any projection no lower than 6 feet 8 inches. Objects that project into the exit route must not reduce its required width, and the route must be a permanent part of the workplace.

How must exit routes be separated from the rest of the building?

Under 1910.36(a)(2), construction materials that separate an exit from other parts of the workplace have a one-hour fire resistance-rating if the exit connects three or fewer stories and a two-hour rating if it connects four or more stories. Openings into an exit are limited to those necessary for access, and each is protected by a self-closing fire door listed or approved by a nationally recognized testing laboratory (1910.36(a)(3)).

Where does an exit route lead?

Under 1910.34, an exit route is a continuous and unobstructed path of exit travel from any point within a workplace to a place of safety (including refuge areas), made of three parts: the exit access, the exit, and the exit discharge. Each exit discharge leads directly outside or to a street, walkway, refuge area, public way, or open space with access to the outside, large enough to accommodate the building occupants likely to use the exit route (1910.36(c)(1)-(2)).

Regulatory history of 29 CFR 1910.36

1910.36 was published at 67 FR 67961 (November 7, 2002) and amended at 76 FR 33606 (June 8, 2011). 1910.36 covers the design and construction of exit routes; 1910.37 covers their ongoing maintenance and operational features; and 1910.38/1910.39 cover emergency action and fire prevention plans.

Related glossary terms

Key terms that appear in 29 CFR 1910.36, each with a full plain-English explainer.

Get the Binder in Order Before the Inspector Arrives. Are You Ready?

OSHA inspections come unannounced, apart from the few exceptions listed in 29 CFR 1903.6. Get the binder in order before the opening conference, not during it.

Serious Violation

$16,550

per violation (max)

HazComFast Pro

$199/mo

10 jobsites, unlimited chemicals, unlimited workers

New sign-ups are paused. The free tools below need no account, and customers can log in as usual.

Your account keeps working as usual. Cancel anytime.