What 29 CFR 1910.36 requires (plain English)
29 CFR 1910.36 sets the design and construction requirements for exit routes: the permanent, continuous, and unobstructed paths of travel from any point in a workplace to a place of safety. It sets the number, arrangement, separation and dimensions of exit routes. It works with 1910.37 (maintenance and operational features) and the emergency action plan requirements of 1910.38. An employer demonstrating compliance with the exit-route provisions of NFPA 101 or the International Fire Code, 2009 editions, is deemed to comply with the corresponding requirements (1910.35).
At least two exit routes must be available in a workplace to permit prompt evacuation, located as far away as practical from each other so that if one is blocked by fire or smoke, employees can use the second ((b)(1)). More than two are required when the number of employees, the size of the building, its occupancy, or the arrangement of the workplace is such that all employees would not be able to evacuate safely ((b)(2)); a single exit route is permitted where all employees would be able to evacuate safely ((b)(3)). An exit is separated from other parts of the workplace by construction materials with a one-hour fire resistance-rating if the exit connects three or fewer stories and a two-hour rating if it connects four or more stories (1910.36(a)(2)). Openings into an exit are limited to those needed for access, and each is protected by a self-closing fire door, listed or approved by a nationally recognized testing laboratory, that remains closed or closes automatically on an alarm ((a)(3)).
The standard also fixes the physical dimensions of a route: the exit access must be at least 28 inches wide at all points (and the exit and exit discharge at least as wide when there is only one exit access), the ceiling at least 7 feet 6 inches high with any projection no lower than 6 feet 8 inches, the width sufficient for the maximum permitted occupant load of each floor, with the capacity never decreasing toward the exit discharge, and free of objects that reduce the width below the minimum (1910.36(g)(1) and (g)(2)). A door connecting a room to an exit route must be side-hinged, and must swing out in the direction of exit travel if the room is designed for more than 50 people or is a high hazard area (1910.36(e)). Employees must be able to open an exit route door from the inside at all times without keys, tools, or special knowledge, and exit route doors are free of any device or alarm that could restrict emergency use if it fails; a door may be locked from the inside only in mental, penal, or correctional facilities with supervisory personnel continuously on duty and a plan to remove occupants ((d)). Each exit discharge must lead directly outside or to a street, walkway, refuge area, public way or open space with access to the outside, large enough for the occupants likely to use it, and exit stairs that continue beyond the discharge level are interrupted at that level (1910.36(c)). An outdoor exit route has guardrails where a fall hazard exists, is covered where snow or ice is likely to accumulate unless it is removed before it presents a slipping hazard, is reasonably straight with smooth, solid, substantially level walkways, and has no dead-end longer than 20 feet ((h)).