Lighting Requirements Under OSHA

Construction areas have a minimum lighting table: 29 CFR 1926.56 sets 5 foot-candles for general area lighting, 3 for excavation and accessways, 10 for shops and 30 for first aid stations and offices while work is in progress. General industry has no such table. Its lighting rules sit in specific standards, such as exit routes in 1910.37.

Verified vs OSHA sources · Oct 21, 2026

29 CFR 1926.56(a), Table D-3, 29 CFR 1910.37(b)(1)

General industry and construction, side by side

The same question has two answers because OSHA writes two sets of rules. A shop, plant, warehouse or office follows 29 CFR part 1910. A construction jobsite follows 29 CFR part 1926.

TopicGeneral industry (29 CFR 1910)Construction (29 CFR 1926)
General work areasPart 1910 has no minimum illumination table for workplaces in general. The one table of this kind covers hazardous waste sites: areas accessible to employees are lighted to not less than the intensities in Table H-120.1 while work is in progress.29 CFR 1910.120(m)Construction areas, ramps, runways, corridors, offices, shops and storage areas shall be lighted to not less than the minimum intensities in Table D-3 while any work is in progress. General construction area lighting is 5 foot-candles, and general construction areas, excavation and waste areas, accessways, active storage, loading platforms and refueling areas are 3.29 CFR 1926.56(a), Table D-3
Exit routes and corridorsEach exit route must be adequately lighted so that an employee with normal vision can see along it. Each exit sign must be illuminated to a surface value of at least five foot-candles.29 CFR 1910.37(b)(1), 29 CFR 1910.37(b)(6)Indoor warehouses, corridors, hallways and exitways are lighted to 5 foot-candles under the table.29 CFR 1926.56(a), Table D-3
Shops and equipment roomsIllumination shall be provided for all working spaces about service equipment, switchboards, panelboards and motor control centers installed indoors.29 CFR 1910.303(g)(1)(v)General construction plant and shops, such as batch plants, carpenter shops, mechanical and electrical equipment rooms, locker rooms and mess halls, are lighted to 10 foot-candles under the table.29 CFR 1926.56(a), Table D-3
First aid stations and officesNo minimum figure. The hazardous waste table lists 30 foot-candles for first aid stations, infirmaries and offices at those sites only.29 CFR 1910.120(m)First aid stations, infirmaries and offices are lighted to 30 foot-candles under the table.29 CFR 1926.56(a), Table D-3
Powered industrial trucksWhere general lighting is less than 2 lumens per square foot, auxiliary directional lighting shall be provided on the truck.29 CFR 1910.178(h)(2)Loading platforms and refueling areas are lighted to 3 foot-candles under the table.29 CFR 1926.56(a), Table D-3
Underground work and specific industriesSpecific standards carry their own lighting rules. Examples: sawmills must have illumination supplying adequate general and local lighting, and telecommunications work must have artificial illumination when natural light is insufficient.29 CFR 1910.265(c)(9)(i), 29 CFR 1910.268(b)(8)Tunnels, shafts and general underground work areas are lighted to 5 foot-candles, with a minimum of 10 foot-candles at the tunnel and shaft heading during drilling, mucking and scaling.29 CFR 1926.56(a), Table D-3

What is OSHA's rule and what is not

LevelWhat it says
OSHA requirementThe table is a floor. The employer lights the area to not less than the listed intensity while work is in progress.29 CFR 1926.56(a)
Consensus standardFor areas or operations the table does not cover, the construction text refers to the American National Standard A11.1-1965 for recommended values of illumination. Those values are recommended and not a requirement written into the table.29 CFR 1926.56(b)
Recommended practiceHigher levels for detailed work, glare control and spare lamps are the employer's own choices. They are recommended, not required, by the table.29 CFR 1926.56(a), Table D-3

Does your state do it differently?

Some states run their own State Plan and write their own text, so the federal paragraphs above describe federal OSHA states. Look up your state on the State Plans page and read its rule before you rely on the federal wording.

What OSHA cited most under these standards in FY2025

ParagraphWhat it coversFY2025 citations
1926.56(a)Minimum illumination while work is in progress3
1910.37(a)(3)446
1910.37(b)(2)335
1910.37(b)(6)132
1910.37(b)(5)118
1910.37(a)(4)116
1910.37(b)(4)56

1926.56: 3 citations in FY2025 at 3 inspections, 2 of them at construction sites (NAICS 23). 1910.37: 1,296 citations in FY2025 at 1,080 inspections, 114 of them at construction sites (NAICS 23). Citation items issued Oct 1, 2024 to Sep 30, 2025, counted by HazComFast on U.S. Department of Labor enforcement data (extracted Oct 13, 2026). Inspected establishments, not the whole industry.

Mistakes that turn up in inspections

  • Looking for a foot-candle table in 1910 and quoting the construction table for a plant. The 5, 3, 10 and 30 foot-candle figures belong to 1926.56, and to the hazardous waste table for that kind of site.29 CFR 1926.56(a), Table D-3 and 29 CFR 1910.120(m)
  • Reading the table as a target for an average. The paragraph says areas are lighted to not less than the intensities, while any work is in progress.29 CFR 1926.56(a)
  • Leaving an exit sign dim. In general industry an exit sign is illuminated to a surface value of at least five foot-candles, by a reliable light source, or it uses a self-luminous or electroluminescent sign that meets the luminance in the paragraph.29 CFR 1910.37(b)(6)

Inside HazComFast

Show an inspector that every worker has read the exit plan

Publish a new version of the emergency plan in HazComFast and each worker reads it on their phone and confirms. The screen shows the count, for example 34 of 37 reviewed version 4, which is the review of 1910.38(f)(3) in a number you can show an inspector.

Questions about lighting requirements

How many foot-candles does OSHA require on a construction site?

It depends on the area. The table gives 5 foot-candles for general construction area lighting, 3 for excavation and waste areas and accessways, 5 for indoor corridors and exitways, 10 for shops and equipment rooms, and 30 for first aid stations, infirmaries and offices, while any work is in progress.

29 CFR 1926.56(a), Table D-3

Does OSHA set a minimum light level for offices and warehouses?

Part 1910 has no minimum illumination table for workplaces in general. It asks that exit routes be adequately lighted, that exit signs reach five foot-candles, and that working spaces about indoor electrical panels be illuminated.

29 CFR 1910.37(b)(1), 29 CFR 1910.37(b)(6) and 29 CFR 1910.303(g)(1)(v)